Technical data
29
Specifications
INDOOR UNITS
X Ratings shown are net capacities.
X Capacities are based on following conditions;
- Equivalent refrigerant piping length : 5m / Level difference : 0m.
;
Note
2-2. Capacity tables
1) RC026DHXEA + ACN026NDEHA
(1) Cooling
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-10 21 35 46
WB DB TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14 20
2.7 2.1 0.6 2.6 2.1 0.5 2.4 1.9 0.7 2.5 2.0 1.2
16 22
2.7 2.2 0.6 2.7 2.1 0.5 2.4 1.9 0.7 2.5 2.0 1.3
18 25
2.8 2.2 0.6 2.8 2.2 0.5 2.5 2.0 0.7 2.6 2.1 1.3
19 27
2.9 2.3 0.6 2.8 2.3 0.5 2.6 2.0 0.7 2.7 2.1 1.3
22 30
2.9 2.4 0.6 2.9 2.3 0.5 2.6 2.1 0.7 2.7 2.2 1.4
24 32
3.0 2.4 0.6 3.0 2.4 0.5 2.7 2.1 0.8 2.8 2.2 1.4
(2) Heating
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-15 -10 7 24
DB TC PI TC PI TC PI TC PI
16
2.3 1.0 2.7 1.1 3.4 0.9 4.7 1.3
18
2.3 1.0 2.6 1.1 3.3 0.9 4.7 1.3
20
2.3 1.0 2.6 1.1 3.3 0.9 4.7 1.3
21
2.2 1.0 2.6 1.1 3.3 0.9 4.6 1.3
22
2.2 1.0 2.5 1.1 3.2 0.9 4.6 1.3
24
2.2 1.0 2.5 1.1 3.2 0.9 4.5 1.3
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-15 -10 7 24
DB TC PI TC PI TC PI TC PI
16
2.5 1.1 2.9 1.2 4.1 1.1 5.3 1.3
18
2.5 1.1 2.9 1.1 4.0 1.1 5.3 1.3
20
2.4 1.1 2.8 1.1 4.0 1.1 5.2 1.3
21
2.4 1.0 2.8 1.1 4.0 1.1 5.1 1.3
22
2.4 1.0 2.8 1.1 3.9 1.1 5.1 1.3
24
2.4 1.0 2.7 1.1 3.9 1.1 5.0 1.3
(2) Heating
TC(Total Capacity, kW), SHC(Sensible Heat Capacity, kW), PI(Power Input, kW)
2) RC035DHXEA + ACN035NDEHA
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-10 21 35 46
WB DB TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14 20
3.5 2.8 0.9 3.4 2.7 0.8 3.3 2.6 1.0 2.5 2.0 1.2
16 22
3.6 2.9 0.9 3.5 2.8 0.8 3.3 2.7 1.0 2.5 2.0 1.3
18 25
3.7 3.0 0.9 3.6 2.8 0.8 3.4 2.7 1.1 2.6 2.1 1.3
19 27
3.8 3.0 0.9 3.6 2.9 0.9 3.5 2.8 1.1 2.7 2.1 1.3
22 30
3.9 3.1 1.0 3.7 3.0 0.9 3.6 2.9 1.1 2.7 2.2 1.4
24 32
4.0 3.2 1.0 3.8 3.1 0.9 3.7 2.9 1.1 2.8 2.2 1.4
(1) Cooling
TC(Total Capacity, kW), SHC(Sensible Heat Capacity, kW), PI(Power Input, kW)
TC(Total Capacity, kW), PI(Power Input, kW)
TC(Total Capacity, kW), PI(Power Input, kW)