Technical data

198
7
Setting an indoor unit address & installation option
7-3. Setting an indoor unit installation option
(suitable for the condition of each installation location)
1) Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power
supply in the indoor unit.
2) The panel(display) should be connected to an indoor unit to receive option.
3) Set the installation option according to the installation condition of an air
conditioner.
- The default setting of an indoor unit installation option is
“02000-100000-200000-300000”.
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is more
than one indoor unit.
4) Set the indoor unit option by wireless remote controller.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 RESERVED
Exterior temperature
sensor
Central control
FAN RPM
compensation
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 Drain pump Hot water heater Electronic heater
Opening the
electronic expansion
valve
Master / Slave
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 External control
External control
output
S-Plasma ion Buzzer
Number of hours
using filter
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3
Individual control of a
remote controller
Heating setting
compensation
EEV opening of an
indoor unit stopped
during oil return or
Defrost operation.
Motion Detect
sensor
-
f 1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to 'USE + 3minute delay' even if the drain pump is set to 0.
f 1 WAY/2WAY/4WAY,DUCT MODEL : Number of hours using filter(SEG18) will be set to '1000hour' even if the SEG18 is set to exept
for 2 or 6.
f MINI 4WAY MODEL : Motion detect sensor(SEG23) will be set.
f If you input a number other than 0~4 of the individual control of the indoor unit(SEG20), the indoor is set as "indoor 1".
Indoor Unit
1(L)
F2
F1
2(N)