Technical data

191
Installation
2) RC777D/P/Z/S7
K1
K5
K2 K3 K4
21

K1 (Push Time) Key Operation 7-Segment DIsplay
1 Heating Trial Operation “K” “1”
2 Defrost Test Mode “K” “2”
- End Key Operation -
K2 (Push Time) Key Operation 7-Segment DIsplay
1 Cooling Trial Operation “K” “3”
2 End Key Operation -
K3 (Push Time) Key Operation 7-Segment DIsplay
1 Initializing(Reset) Operation -
K4(Push Time) Key Operation
F7-Segment DIsplay
SEG 1 SEG 2,3,4
1 Order Frequency 1 Ex) 100Hz
¬
1, 0 , 0
2 Current Frequency 2 Ex) 105Hz
¬
1, 0 , 5
3 The Number of Current Indoor Units 3 Ex ) 1
¬
0, 0, 1
4 The Sensor for Outdoor Air Intake 4 Ex) 30°C
¬
0, 3, 0
5 Discharge Sensor 5 Ex) 30°C
¬
0, 3, 0
6 Eva-Mid Sensor 6 Ex) 30°C
¬
0, 3, 0
7 Cond. Sensor 7 Ex) 30°C
¬
0, 3, 0
8 Current 8 Ex) 2A
¬
0, 0, 2
9 Fan RPM 9 Ex) 50rpm
¬
0, 5, 0
10 Target Discharge Temperature A Ex) 30°C
¬
0, 3, 0
11 EEV B Ex) 100steps
¬
1, 0, 0
12 The Capacity Sum of Indoor Units C Ex) 14kW
¬
0, 1, 4