Technical data

189
Installation
3) Additional refrigerant charging
4) Set-up indoor unit quantity by key switch (K1, K2)
Press and hold K1 switch to enter the setting mode on the number of the installed indoor unit : Check “A0” sign on
7-segment
Press K2 switch to set the number of the installed indoor unit :
Ex) If there are two indoor units, press K2 switch twice, and check "A2" sign on 7-segment.
If there are three indoor units, press K3 switch three times, and check "A3" sign on 7-segment.
If there are four indoor units, press K4 switch four times, and check "A4" sign on 7-segment.
Press K1 switch to complete setting the number of the installed indoor unit : Check "AA" sign on 7-segment.
5) Operation and specification
The two indoor units are equally controlled by wired and wireless remote controller.
(All controls such as ON/OFF, Cooling/Heating/Dehumidification/Ventilation,
High/Medium/Low wing, Fixing louver angle/swing are equally applied.)
Thermo Off which stops when indoor temperature reaches set temperature works by the average sensor value of
the indoor temperature of two indoor units.
When either of the two indoor units has a problem, the two indoor units protect operation or stop working.
6) Instruction for installation and operation
You should install the DPM models according to the proper installation specification and eliminate the factors that
give electrical load to the both indoor units when installing and operating.
(Heater/Window/Front door/Ventilation/Partition that divides space)
You should provide sufficient instructions about the operation method and specification features to users and fill in
caution phrases on wired remote controller when necessary.
(Ex. The air-conditioners in this area are special type to be controlled simultaneously)
Type Model Installation condition Amount of additional refrigerant charging
DPM
󱐻
RC071DHXE/
RC071PHXE
L
1+L2+L3 d 50 m
(L
1-5) x 0.04 + (L2+L3) x A, A=0.03kg/m (ø=6.35mm)
A=0.04kg/m (ø=9.52mm)
J "A" refer to diameter of pipe after joint-distributer
󱐽
RC100DHXAL1+…+Ln+1 d 50 m
(L
1+a+b-5) x 40[g] + (L2+...+Ln+1) x 30[g]
If (L
1+a+b)< 5m, (L2+...+Ln+1) x 30[g]
󱐿
RC100PHXA/RC125DHXEB/
RC125DHXGA/RC125PHXA/
RC140DHXEB/RC140DHXGA/
RC140PHXA
L
1+…+Ln+1 d 75 m
(L
1+a+b-5) x 40[g] + (L2+...+Ln+1) x 30[g]
If (L
1+a+b)< 5m, (L2+...+Ln+1) x 30[g]
J "n" means the number of indoor unit connection of DPM.