Technical data
188
Ê In case of 4indoor units connection
4
Refrigerant piping works
4-4. DPM Installation
1) Space requirements for indoor and outdoor units and piping installation
• Two indoor units should be installed in one area which is not divided by a wall.
• The distance between two indoor units should be within a straight-line of 10m.
• After branching, the distance between the piping connected to the two indoor units should be within 1m.
• The height difference between two units should be within 0.5m.
• Use the joint KIT that is only for DPM. (Please refer to the table below)
2) Connecting communication line and wired remote controller
J The wired remote controller can be used with any of the DPM indoor units.