Installation manual

E-14
DMS External Display
LED Status Display
1
2
3
4
5
6
7
8
9
10
Power (Red)
Power display.
The power display is on when there’s a power input.
CPU Alive(Yellow)
Flickers every second if the CPU is operating normally.
(The CPU is in waiting status and the CPU Alive display is off
initially when powered up.)
Linked (Green)
Internet cable connection status display.
The display is on when connected to the internet.
Active (Green)
Flickers during data transceive.
RS485 Tx (Green)
Flickers during data transmission from the DMS to
the centralized controller.
(Starts flickering once the tracking is complete.)
RS485 Rx (Green)
Flickers during data transmission from the centralized
controller to the DMS.
DI 1 Status (Green)
Lights on when using the external contact signal control.
(Refer to page 23)
DI 2 Status (Green)
Lights on when using the external contact signal control.
(Refer to page 23)
A/C Running
(Green)
DMS status indicator/Running status of indoor unit indicator
You may setup A/C Running LED to indicate either DMS status
or Indoor unit operation.
- DMS status: Green light will flicker every 5 seconds when
DMS operates normally.
- Running status of indoor unit: Solid green light will turn on
when the indoor units operate normally.
(at least 1 indoor unit)
Error (Green)
Lights on if there is an error on at least one indoor or outdoor
unit. Also Lights on when there is a communication error.
MIM-D00_IM_E_29919-1.indd 14 2008-09-10 ソタネト 1:27:23