Unit installation

30 31
ENGLISH
Error codes
If the unit has some problem to work properly, the LED on hydro unit willash and some error codes will be displayed on the
controller. The following table described the explanation of error codes on the LCD display.
Thermistor
Check its resistance. 10kΩ@24°C (Outdoor unit), 220kΩ@2C (DHW Tank, Solar)
Check its location as shown at the diagram.
Check its contact status with pipe.
Final solution is to change parts
Display Explanation
EVA inlet thermistor SHORT or OPEN
EVA outlet thermistor SHORT or OPEN
Wired remote controller thermistor SHORT or OPEN
FRAM Read/Write Error (Wired remote controller data error)
Water inlet thermistor SHORT or OPEN
PHE outlet thermistor SHORT or OPEN
Water outlet thermistor SHORT or OPEN
Water tank thermistor SHORT or OPEN
Abnormal communication between wired remote controller and hydro unit
Communication tracking error between wired remote controller and hydro unit
FRAM Read/Write error (Wired remote controller data error)
Flow switch ‘OFF’ error (Condition: Flow switch signal is off during 10 seconds when the water pump
signal is ON)
Flow switch ‘ON’ error (Condition: Flow switch signal is on during 10 seconds when the water pump
signal is off)
Troubleshooting
This page is showing the useful technical information for diagnosing and making error correction for various troubles which
may occur in the system. Before contacting your local installers, read this page carefully and implement visual inspections of
the whole system.
Possible causes Actions
Heating or cooling performance are not good
Check the temperature adjustment in the controller
Check if the water is filled in the system fully
Check the water flow rate
Loud noise from water pump
Check air purge valve (Make it open and close)
Check if the water is filled in the system fully
Check if strainer is full of foreign materials
System does not work even power source does not
have problem
Check if wiring connections are installed well
Check if water flow rate is low (system will not work in condition
of below 16 LPM)
Solar pump is not working
Check TB-B and wire connections
Remote controller cannot be set
Check if it has the mode of master or slave
If there are 2 controllers, either one shall have slave mode.
Always make sure to turn off the system before implementing the visual checking or disassemble for detail
checks.
CAUTION
Incorrect handling of thermostat, safety valve or other valves may lead to tank rupture. When servicing the unit
follow instructions carefully:
- Always turn off main power supply when water supply is being shut off.
- Test the free operation of the safety valve regularly by opening the valve ensuring the water flows freely.
- Electrical connection and all servicing of the electrical components should only be carried out by an
authorized electrician.
- Fitting and all servicing of plumbing fixtures should only be carried out by an authorized installer.
- When replacing the thermostat, safety valve or any other valve or part supplied with this unit, use only
approved parts of the same specification.
WARNING