Unit installation

22 23
ENGLISH
Setting option switches and function of keys
DIP switch setting
S/W OFF (Default) ON
S/W #1 Heating and cooling Heating only
S/W #3 Target temp. : Water outlet temp. Target temp. : Indoor temp.
S/W #3 Air sensor in remote controller External air sensor
S/W #4 Master Remote controller Slave Remote controller
S/W #5
Error detection when outdoor communication is
broken
Error non-detection , For Commissioning /
Emergency
S/W #6 Normal operation Emergency
S/W #7 No use No use
S/W #8 No use No use
Wiring works
Solar Pump
Solar Panel
Connecting solar pump
1. Connect ‘Solar pump power line with ‘pin #25, 26 in TB-B.
If pin#25, 26 get AC230V, Control Kit will aware Solar Panel supply heat to DHW tank.)
Maximum Consumption Power
Each port use under 10mA
NOTE
Specification table
Part Specification
Connection pin
#25 : Output Power N
#26 : Detecting Power L
Connection load Direct connect from solar pump (AC230V)
Output AC 230V (MAX 10mA)
Condition for operation (NOT Define)