MIM-E03✴ SAMSUNG CONTROL UNIT installation manual imagine the possibilities Thank you for purchasing this Samsung product. To receive more complete service, please register your product at www.samsung.
Safety precautions Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Product specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Main components . . . . . . . . . . .
Product specifications Installing the unit Item Description Deciding on where to install the unit MIM-E03A Wired remote controller ENGLISH ffInstall the unit in indoor and do not install it outside. The unit is designed only for indoor. ffDirect heat can make the kit have some failures in operation. ffChoose locations that are dry and sunny, but not exposed to direct sunlight or strong winds. ffChoose location where pipes and cables can be easily connected to the indoor unit.
Installing the unit Installing the remote controller Connecting the wired remote controller cable to FTC NOTE • • • • Wiring wire No.×size(mm2) : 2×0.3(polar) The 5m wire is attached as an accessory. Max. 500 m Wiring size must comply with the applicable local and national codes. Circuit rating : DC12V Circuit rating is NOT always against the ground.
Wiring works Power and communication with outdoor unit Overall schematics ENGLISH Communication Wire Flow S/W Outdoor Unit Temp Sensor Power Wire Connecting the power wire Solar Main Power Booster Heater Recommended wire specification 2way Valve (Zone2) Relay 1. Connect ‘Live’ and ‘Neutral’ power line with ‘pin #1’ and ‘pin #2’ in TB-A. 2. Connect ‘Protective Earth’ line with ‘Earth screw’ in case.
Wiring works Booster heater Communication with wired remote controller ENGLISH Wired Remote Controller Heater Wire Connecting heater wire (in the case of resistor heater which is under 3kw) Connecting the wired remote controller 1. Connect ‘V1, V2, F3, F4 of control kit’ with ‘V1, V2, F3, F4 of wired remote controller’. ffYou can connect maximum 2 set of wired remote controller. ffIn case of 2 sets for wired remote controller installation, master/slave settings shall be implemented. 1.
Wiring works Backup boiler Backup heater ENGLISH Backup Boiler Connecting backup boiler Magnetic Contactor Wire Connecting magnetic contactor for backup heater (Not Directly Connect Heater) 1. Connect ‘Magnetic contactor wire’ with ‘pin #1, 2, 3’ in TB-B. ffIf control kit turns on the 1st step of backup heater pin#1 & pin#2 will output AC230V. ffIf control kit turns on the 2nd step of backup heater pin#1 & pin#3 will output AC230V.
Wiring works 2way valve for hot water Water pump ENGLISH 2way valve (#1) Connecting 2way valve (for hot water ) Water Pump 1. Directly connect ‘2way valve for ZONE.1’ with ‘pin #7, 8, 9, 10’ in TB-B. ffIf control kit orders opening water pump on, pin#7 & pin#10 will output AC230V. Connecting water pump 1. Directly connect ‘water circulation pump’ with ‘pin #5, 6’ in TB-B. ffIf control kit orders turning water pump on, pin#5 & pin#6 will output AC230V.
Wiring works 2way valve for zone 1 Example of valve connection *1) /L1 means opposite side signal of L1. ENGLISH ff2 pole (L1, N) type • L1 port of Valve is connected to #10 • N port of Valve is connected to #7 (If L1, N ports of Valve get power, water can NOT flow to DHW tank.) (If L1, N ports of Valve don`t get power, water can flow to DHW tank.
Wiring works 2way valve for zone 2 Example of valve connection *1) /L1 means opposite side signal of L1. ENGLISH ff2 pole (L1, N) type • L1 port of Valve is connected to #13 • N port of Valve is connected to #11 (If L1, N ports of Valve get power, water can flow to Zone1.) (If L1, N ports of Valve don`t get power, water can NOT flow to Zone1.
Wiring works Wired room thermostat Example of valve connection *1) /L1 means opposite side signal of L1. ENGLISH ff2 pole (L1, N) type • L1 port of Valve is connected to #17 • N port of Valve is connected to #15 (If L1, N ports of Valve get power, water can flow to Zone1.) (If L1, N ports of Valve don`t get power, water can NOT flow to Zone1.
Wiring works Setting option switches and function of keys Solar Pump DIP switch setting OFF (Default) ON Heating and cooling Heating only Target temp. : Indoor temp. S/W #3 Target temp. : Water outlet temp.
Setting option switches and function of keys Field setting mode Field Setting Value(FSV) Table Field Setting Value Main Menu & Code Sub Menu Function Water Out Temp for Cooling Room Temp for Cooling Remote Controller Setting Range Code 10✴✴ Water Out Temp for Heating Room Temp for heating DHW Tank Temp Outdoor Temp for Water Law (Heating) Water Out Temp for WL1 Heating (WL1-Floor) Sub Code Default Min Max Step Field Setting Value Main Menu & Code Unit Sub Menu Function Description Sub Code Defa
Setting option switches and function of keys Test operation Picture Mode ① Description Heating/DHW Priority Heat Pump Heating Code 40✴✴ Backup Heater Backup Boiler Outing Others Code 50✴✴ DHW Saving Mode TDM Variable Power Peak Control Sub Code Default ✴✴11 Min Max Step Unit 0(DHW) 0 1(Heating) - - Outdoor Temp for Priority ✴✴12 0 -15 20 1 ˚C Heating Off ✴✴13 25 14 35 1 ˚C Overshoot ✴✴14 2 1 4 1 ˚C Application ✴✴21 1(On) 0(Off) 1 - - BUH/BSH Priority ✴✴22
Test operation Before running the system Picture Explanation ① ⑦ For checking sensor ② ③ ④ ⑤ ⑥ ⑧ Cancel Control panel ENGLISH Mode 3. Emergency mode -- Emergency mode shall be possible regardless of outdoor communication error. It is available after change DIP#5 and DIP#6 into “ON” and re-set mode. -- Enable/ disable modes: allowed for heating and how water mode.
Troubleshooting Error codes This page is showing the useful technical information for diagnosing and making error correction for various troubles which may occur in the system. Before contacting your local installers, read this page carefully and implement visual inspections of the whole system. If the unit has some problem to work properly, the LED on hydro unit will flash and some error codes will be displayed on the controller.