Specifications
80
JOHNSON CONTROLS
Form 201.28-NM1.EN.PED/CE (0211)
MICROPANEL
Lag selections of individual systems will appear as:
OPTIONS LEAD / LAG CONTROL MODE
< > MANUAL SYS 1 LEAD
OPTIONS LEAD / LAG CONTROL MODE
< > MANUAL SYS 2 LEAD
Remote Temperature Reset Selection
Remote temperature reset from an external source may
be tied directly into the chiller microprocessor board.
OPTIONS REMOTE TEMP RESET INPUT
< > DISABLED
Selections may be made for DISABLED (no signal), 0
to10 Vdc, 2 to 10 Vdc, 0 to 20 ma, and 4 to 20 ma.
OPTIONS REMOTE TEMP RESET INPUT
< > 0.0 TO 10.0 VOLTS DC
OPTIONS REMOTE TEMP RESET INPUT
< > 2.0 TO 10.0 VOLTS DC
OPTIONS REMOTE TEMP RESET INPUT
< > 0.0 TO 20.0 MILLIAMPS
OPTIONS REMOTE TEMP RESET INPUT
< > 4.0 TO 20.0 MILLIAMPS
The default setting for Remote Temp Reset is DISABLED.
This display will only appear if the remote temperature
limit option is enabled under the Unit Setup Mode.
Remote Current Limit Input Selection
Remote current limit from an external source may be tied
directly into the chiller microprocessor board.
OPTIONS REMOTE CURRENT LIMIT INPUT
< > DISABLED
Selections may be made for DISABLED (no signal), 0 to
10VDC, 2 to 10VDC, 0 to 20ma, and 4 to 20ma.
OPTIONS REMOTE CURRENT LIMIT INPUT
< > 0.0 TO 10.0 VOLTS DC
OPTIONS REMOTE CURRENT LIMIT INPUT
< > 2.0 TO 10.0 VOLTS DC
OPTIONS REMOTE CURRENT LIMIT INPUT
< > 0.0 TO 20.0 MILLIAMPS
OPTIONS REMOTE CURRENT LIMIT INPUT
< > 4.0 TO 20.0 MILLIAMPS
The default setting for Remote Current Reset is
DISABLED. This display will only appear if the remote
current limit option is enabled under the Unit Setup
Mode.
Remote Sound Limit Selection
Remote sound limit from an external source may be tied
directly into the chiller microprocessor board.
OPTIONS REMOTE SOUND LIMIT INPUT
< > DISABLED
Selections may be made for DISABLED (no signal), 0
to10VDC, 2 to 10VDC, 0 to 20ma, and 4 to 20ma.
OPTIONS REMOTE SOUND LIMIT INPUT
< > 0.0 TO 10.0 VOLTS DC
OPTIONS REMOTE SOUND LIMIT INPUT
< > 2.0 TO 10.0 VOLTS DC
OPTIONS REMOTE SOUND LIMIT INPUT
< > 0.0 TO 20.0 MILLIAMPS
OPTIONS REMOTE SOUND LIMIT INPUT
< > 4.0 TO 20.0 MILLIAMPS
The default setting for Remote Sound Limit is
DISABLED. This display will only appear if the remote
sound limit option is enabled under the Unit Setup Mode.
Low Ambient Cutout Enable/Disable
The low ambient cutout may be enabled or disabled.
OPTIONS LOW AMBIENT TEMP CUTOUT
< > ENABLED
OPTIONS LOW AMBIENT TEMP CUTOUT
< > DISABLED
When enabled, the chiller will cut OFF when the low
ambient cutout is reached. When disabled, the chiller
will run at any temperature.
The default setting for the low ambient cutout will be
ENABLED.