24296A(1)_co 11/12/05 10:04 AM Page 1 MULTI AIR CONDITIONER INDOOR UNIT SERVICE OUTDOOR UNIT FREE JOINT FIXED FREE JOINT FIXED MH020FPEA MH023FPEA MH026FPEA MH035FPEA MH052FPEA MH052FPEA1 MH023FWEA MH026FWEA MH035FWEA MH052FWEA MH026FKEA MH035FKEA MH052FDEA MH023FEEA MH026FEEA MH035FEEA MH040FXEA2 MH052FXEA2 MH068FXEA4 MH080FXEA4 MH14VP2-07 MH16VP2-07 MH16VP2-09 MH18VP2-09 MH19VP2-07 MH19VP2-12 MH30VP2-09 MH30VP2-12 MH14VW2-07 MH16VW2-07 MH16VW2-09 MH18VW2-09 MH19VW2-07 MH19VW2-12 MH30VW2-09 MH30V
4296A(1)_1 11/11/05 5:02 PM Page 1 Contents 11. Precautions .......................................................................................................................................... 1-1 ......................................................................................................... 1-1 .............................................................................................. 1-1 ............................................................................................
24296A(1)_1 11/11/05 5:02 PM Page 2 Contents 19. Circuit Descriptions .................................................................................................................... 9-1 9-1 PCB Circuit Descriptions .............................................................................................................. 9-1 ....................................................................................................... 9-3 9-2 Refrigerating Cycle Diagram 10. PCB Diagram.............
24296A(1)_1 11/11/05 5:02 PM Page 1-1 1. Precautions 1-1 Installing the air conditioner ● Users should not install the air conditioner by themselves. Ask the dealer or authorized company to install the air conditioner except the window-type air conditioner in U.S.A and Canada. ● If you don’t install the air conditioner properly, it may cause a fire, a water leakage or an electric shock. ● You must install the air conditioner according to the national wiring regulations and safety regulations.
24296A(1)_1 11/11/05 5:02 PM Page 1-2 1-4 Disposing of the unit ● Before throwing out the air conditioner, remove the batteries from the remote control. ● When you dispose of the air conditioner, consult your dealer. If pipes are removed incorrectly, refrigerant may blow out and cause air pollution. When it contacts with your skin, it can cause skin injury. ● The package of the air conditioner should be recycled or disposed of properly for environmental reasons.
24296A(1)_1 11/11/05 5:02 PM Page 2-1 2. Product Specifications 2-1 The Feature of Product ■ Multi Inverter(Free Joint Multi) Series delivers comfort to 2~4 rooms with a Single Outdoor Unit. ■ Inverter for High Efficiency Operation. Thanks to inverter control, efficiency of operation of the outdoor unit is enhanced depending on the number of indoor units operated and the temperature setting. When only one indoor unit is used, power is saved, resulting in a smaller electricity bill.
24296A(1)_1 11/11/05 5:02 PM Page 2-2 2-2 Name of Each Part 2-2-1 Indoor Unit ■ MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳ The design and shape are subject to change according to the model.
24296A(1)_1 11/11/05 5:02 PM Page 2-3 Product Specifications Indoor Unit(cont.) ■ MH✳✳✳FWEA/MH✳✳VW2-✳✳ The design and shape can be changed according to the model.
24296A(1)_1 11/11/05 5:02 PM Page 2-4 Product Specifications Indoor Unit(cont.) ■ MH✳✳✳FKEA The figures are shown in this instruction may differ from yours depending on the model.
24296A(1)_1 11/11/05 5:02 PM Page 2-5 Product Specifications Indoor Unit(cont.) ■ MH✳✳✳FDEA/MH✳✳✳FEEA The figures are shown in this instruction may differ from yours depending on the model.
24296A(1)_1 11/11/05 5:02 PM Page 2-6 Product Specifications 2-2-2 Outdoor Unit ■ MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/MH19VP2X/ MH14VW2X/MH16VW2X/MH18VW2X/MH19VW2X Air Inlet (Rear) Air Outlet Connection Valve ■ MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X Air Inlet (Rear) Air Outlet Connection Valve Note : • If the heat exchanger in the outdoor unit gets dusty, cooling efficiency may fall. So clean the heat exchanger with water when it becomes dirty.
24296A(1)_1 11/11/05 5:02 PM Page 2-7 2-3 Product Specifications Model MH020FPEA MH✳✳VP2-07 Item MH026FPEA MH✳✳VP2-09 INDOOR UNIT Type Cooling kW Heating |/h Dehumidifying Performance MH023FPEA Cooling Air Volume m3/min Heating Cooling Noise dB Cooling WxHxD Refrigerant Pipe Refrigerant Control Unit Samsung Electronics 1.4 1.4 1.4 6.5 7.0 7.0 6.6 7.8 7.8 40 40 40 30 30 30 30 30 30 0.18 0.18 0.18 0.18 0.18 0.
24296A(1)_1 11/11/05 5:02 PM Page 2-8 Product Specifications(cont.) Model MH035FPEA MH✳✳VP2-12 Item INDOOR UNIT Type Cooling kW Heating |/h Dehumidifying Performance Cooling Air Volume m3/min Heating Cooling Noise dB Cooling WxHxD Refrigerant Pipe Refrigerant Control Unit 13.3 8.8 13.4 42 48 35 50 0.19 0.30 0.19 0.30 mm 890x285x179 1,080x315x205 inch 35.0x11.2x7.0 42.5x12.4x8.1 A kg 8.5 13 ø6.35x7.5 ø6.35x7.5 Gas mmxL(m) ø9.52x7.5 ø12.7x7.
24296A(1)_1 11/11/05 5:02 PM Page 2-9 Product Specifications(cont.) Model MH023FWEA/MH026FWEA MH✳✳VW2-07/MH✳✳VW2-09 Item MH052FWEA INDOOR UNIT Type Cooling kW Heating |/h Dehumidifying Performance MH035FWEA MH✳✳VW2-12 Cooling Air Volume m3/min Heating Cooling Noise dB Cooling WxHxD Refrigerant Pipe Refrigerant Control Unit Samsung Electronics 1.4 1.9 2.5 7.0 8.2 13.3 7.3 8.8 14.0 40 43 48 30 35 50 30 35 50 0.18 0.19 0.30 0.18 0.19 0.
24296A(1)_1 11/11/05 5:02 PM Page 2-10 Product Specifications(cont.) Model MH026FKEA MH035FKEA 1-Way Cassette 1-Way Cassette Silhouette Duct 2.60 3.50 5.20 2.90 3.80 5.60 7.0 7.5 15.0 7.5 8.0 15.5 40 42 43 40 42 43 1,220~240,50 1,220~240,50 1,220~240,50 40 45 145 40 45 145 0.20 0.23 0.
24296A(1)_1 11/11/05 5:02 PM Page 2-11 Product Specifications(cont.) Model MH023FEEA MH026FEEA Item INDOOR UNIT Type Cooling kW Heating Performance Cooling Air Volume m3/min Heating Cooling Noise dB Heating Power ø,V,Hz Power Consumption Cooling W Heating Power Operating Current Cooling A Outer Dimension Motor Refrigerant Control Unit Samsung Electronics 3.50 2.90 3.80 8.6 9.8 9.0 10.3 37 37 38 38 1,220~240,50 1,220~240,50 80 80 80 80 0.40 0.40 0.
24296A(1)_1 11/11/05 5:02 PM Page 2-12 Product Specifications(cont.) Model MH040FXEA2 MH052FXEA2 Item Free Joint Multi Capacity Cooling Air Volume Noise m /min 3 Cooling dB Heating Power Power Consumption Operating Current 4.0 4.6 2.2~6.0 2.2~7.3 4.4 5.1 48 48 48 48 56 56 56 56 57 57 57 57 1,220-240V~,50Hz 740~1,535 740 ~ 2,090 1,290 1,350 Heating 820~1,785 820 ~ 2,350 1,540 1,700 Cooling 3.4~6.7 3.4~9.0 5.8 6.0 3.7~8.1 3.7~10.2 6.7 7.
24296A(1)_1 11/11/05 5:02 PM Page 2-13 Product Specifications(cont.) Model MH18VP2X Item Cooling Air Volume Noise m /min 3 Cooling dB Heating Power Power Consumption Operating Current 5.50 5.20 5.90 5.80 6.00 5.80 6.57 48 48 48 48 56 56 56 56 57 57 57 57 1,220-240V~,50Hz ø,V,Hz 1,440 1,535 1,440 1,885 Heating 1,745 1,785 1,745 2,125 Cooling 6.3 6.7 6.3 8.3 7.8 8.1 7.8 9.
24296A(1)_1 11/11/05 5:02 PM Page 2-14 Product Specifications(cont.) Model MH068FXEA4 MH080FXEA4 Item Free Joint Multi Capacity Cooling Air Volume Noise m /min 3 Cooling dB Heating Power Power Consumption Operating Current 48 48 57 58 58 58 58 59 59 59 1,220-240V~,50Hz 1,230~2,705 2,750 2,655 3.9~10.9 10.0 9.5 5.6~11.9 5.6~11.9 11.4 10.
24296A(1)_1 11/11/05 5:02 PM Page 2-15 2-4 The Comparative Specifications of Product Item MH040FXEA2/MH052FXEA2 MH18AP2X Indoor Unit Design Outdoor Unit Indoor Unit Net Weight Outdoor Unit Samsung Electronics MH020FPEA MH026FPEA 7.5kg MH035FPEA 8.5kg MH023FWEA MH026FWEA MH035FWEA 9.0kg MH026FKEA MH035FKEA 15.0kg MH023FEEA MH026FEEA MH035FEEA 26.0kg MH040FXEA2 MH052FXEA2 58.0kg MH18AP2-09 7.5kg MH18AP2X 59.
24296A(1)_1 11/11/05 5:02 PM Page 2-16 The Comparative Specifications of Product(cont.
24296A(1)_1 11/11/05 5:02 PM Page 2-17 The Comparative Specifications of Product(cont.) MH14V✳2X/MH16V✳2X MH18V✳2X/MH19V✳2X Item MH18AP2X Indoor Unit Design Outdoor Unit Indoor Unit Net Weight Outdoor Unit Indoor Unit Outer Dimension Outdoor Unit Indoor Unit Noise Outdoor Unit The Feature of Product Samsung Electronics MH✳✳VP2-07 MH✳✳VP2-09 7.5kg MH✳✳VP2-12 8.5kg MH✳✳VW2-07 MH✳✳VW2-09 MH✳✳VW2-12 9.0kg MH✳✳VP2X MH✳✳VW2X 58.
24296A(1)_1 11/11/05 5:02 PM Page 2-18 The Comparative Specifications of Product(cont.) MH068FXEA4 MH080FXEA4 Item UMF30C2E4 Indoor Unit Power Standard Nature Saving Silence Timer Design Outdoor Unit MH023FPEA MH026FPEA 7.5kg MH035FPEA 8.5kg MH052FPEA✳ 13.0kg MH023FWEA MH026FWEA MH035FWEA 9.0kg MH052FWEA 13.0kg MH026FKEA MH035FKEA 15.0kg AMF09C2E AMF12C2E 7.7kg AMF18C2E 13.0kg UMF30C2E4 72.0kg Indoor Unit Net Weight Outdoor Unit 2-18 MH023FEEA MH026FEEA MH035FEEA 26.
296A(1)_1 11/11/05 5:02 PM Page 2-19 The Comparative Specifications of Product(cont.
24296A(1)_1 11/11/05 5:02 PM Page 2-20 The Comparative Specifications of Product(cont.) MH30VP2X MH30VW2X Item MH26AP2X Indoor Unit Design Outdoor Unit Indoor Unit Net Weight Outdoor Unit Indoor Unit Outer Dimension Outdoor Unit Indoor Unit Noise Outdoor Unit The Feature of Product 2-20 MH30VP2-09 7.5kg MH30VP2-12 8.5kg MH30VW2-09 MH30VW2-12 MH26AP2-07 7.5kg 9.0kg MH26AP2-12 8.5kg MH30VP2X MH30VW2X 72.0kg MH26AP2X 71.
24296A(1)_1 11/11/05 5:02 PM Page 2-21 2-5 Accessory and Option Specifications 2-5-1 Indoor Unit Accessories ■ MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳ Item Descriptions Code-No.
24296A(1)_1 11/11/05 5:02 PM Page 2-22 Product Specifications Indoor Unit Accessories(cont.) ■ MH✳✳✳FWEA/MH✳✳VW2-✳✳ Item Descriptions Code-No.
24296A(1)_1 11/11/05 5:02 PM Page 2-23 Product Specifications Indoor Unit Accessories(cont.) ■ MH✳✳✳FKEA Item Descriptions Code-No.
24296A(1)_1 11/11/05 5:02 PM Page 2-24 Product Specifications Indoor Unit Accessories(cont.) ■ MH✳✳✳FDEA Item Descriptions Code-No.
24296A(1)_1 11/11/05 5:02 PM Page 2-25 Product Specifications Indoor Unit Accessories(cont.) ■ MH✳✳✳FDEA(cont.) Item Descriptions Code-No. Q'TY Cable-tie DB65-10088C 4 Drain Socket DB67-00111A 1 Wired remote controller Box DB97-01904G 1 Remark Indoor Unit ✳ The design and shape can be changed according to the model. ■ MH✳✳✳FEEA Item Descriptions Code-No.
24296A(1)_1 11/11/05 5:02 PM Page 2-26 Product Specifications Indoor Unit Accessories(cont.) ■ MH✳✳✳FEEA(cont.) Item Descriptions Code-No. Q'TY Rubber (Grommet Hanger) DB63-00237A 8 Insulation-Drain Out DB62-03439H 1 Insulation-Out DB62-03439J 2 Insulation-Drain In DB62-03440H 1 Cable-tie DB65-10088C 8 Drain Pipe Holder DB90-02064A 2 Wired remote controller Box DB97-01904G 1 Remark Indoor Unit ✳ The design and shape can be changed according to the model.
24296A(1)_1 11/11/05 5:02 PM Page 2-27 Product Specifications 2-5-2 Outdoor Unit Accessories ■ MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/MH19VP2X/MH14VW2X/MH16VW2X/MH18VW2X/MH19VW2X Item Descriptions Code-No.
24296A(1)_1 11/11/05 5:02 PM Page 2-28 Product Specifications Outdoor Unit Accessories(cont.) ■ MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X Item Descriptions Code-No. Q'TY Drain Plug Out DB67-20011A 2 Transmitter power cable (Ass'y Connector Wire-DC Power) DB93-03011B 1 Remark DB98-24514B (MH068FXEA4) DB98-24514A Energy Label (Ass'y-Label Energy) (MH080FXEA4) 1 DB98-21848J (MH30VP2X) DB98-21848R (MH30VW2X) Rubber Leg DB73-20134A 4 Flare Nuts, 6.
24296A(1)_1 11/11/05 5:02 PM Page 2-29 Product Specifications 2-5-3 Transmitter Unit Accessories : MIM-B04 Item Descriptions Code-No.
24296A(1)_1 11/11/05 5:02 PM Page 2-30 3.
24296A(1)_1 11/11/05 5:03 PM Page 2-31 Alignment and Adjustments ■ MH✳✳✳FKEA Indicators Abnormal conditions Operating Green Red Power reset Error of temperature sensor in indoor unit (OPEN/SHORT) Error of heat exchanger sensor in indoor unit Error of heat exchanger OUT sensor in indoor unit Error of outlet temperature sensor in indoor unit (OPEN/SHORT): For heat pump models only Error of mixed operation Error of indoor fan motor : Below 450RPM for 15 minutes Error of outdoor temperature sensor Error
24296A(1)_1 11/11/05 5:03 PM Page 2-32 Alignment and Adjustments ■ MH✳✳✳FDEA/MH✳✳✳FEEA The error indicated on the LED display of Indoor unit Indicators Concealed Type Abnormal conditions Blue Red Operating Standard Type Power reset Error of temperature sensor in indoor unit(OPEN/SHORT) Error of heat exchanger sensor in indoor unit Error of heat exchanger OUT sensor in indoor unit Error of outlet temperature sensor in indoor unit (OPEN/SHORT): For heat pump models only Displayed on appropriate i
24296A(1)_1 11/11/05 5:03 PM Page 2-33 Alignment and Adjustments ■ MH✳✳✳FDEA/MH✳✳✳FEEA(cont.) The error indicated on the LED display of Indoor unit Indicators Concealed Type Abnormal conditions Blue Red Operating Standard Type 5. Breakaway of COND MID sensor 6. 2 detection of refrigerant completely leak nd 7. 2nd detection of high temperature COND 8. 2nd detection of high temperature DISCHARGE Displayed on appropriate indoor unit which is operating Displayed on outdoor unit 9.
24296A(1)_1 11/11/05 5:03 PM Page 2-34 Alignment and Adjustments 3-1-2 Outdoor Unit Display 3-5 Explanation Main checking Point Communication error (indoor unable to receive data) Communication cable connection Communication error (outdoor unable to communicate) Indoor unit Indoor unit room temperature sensor error (Open/Short) Indoor unit Indoor unit heat exchanger in temperature sensor error (Open/Short) Indoor unit Indoor unit heat exchanger out temperature sensor error (Open/Short) Indo
24296A(1)_1 11/11/05 5:03 PM Page 2-35 Alignment and Adjustments Outdoor Unit(cont.
24296A(1)_1 11/11/05 5:03 PM Page 2-36 3-2 Setting Option Setup Method ■ MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳ ex) Option No. : Step 1 : Enter the Option Setup mode. 1st Take out the batteries of remote control. 2nd Press the temperature insert the battery again. 3rd Make sure the remote control display shown as button simultaneously and . Step 2 : Enter the Option Setup mode and select your option according to the following procedure. 1 The default value is Otherwise, push the . button to .
24296A(1)_1 11/11/05 5:03 PM Page 2-37 Alignment and Adjustments 7 Press button, then the default value is . 8 Push the button to set the display panel to . Every time you push the button, the display panel reads ... repeatedly. 9 8 9 Push the 7 . Every time you push the button, the display panel reads ... repeatedly. 10 11 button to set the display panel to 10 12 Push the button to set the display panel to . Every time you push the button, the display panel reads ... repeatedly.
24296A(1)_1 11/11/05 5:03 PM Page 2-38 Alignment and Adjustments ■ MH✳✳✳FWEA/MH✳✳VW2-✳✳ ex) Option No. : Step 1 : Enter the Option Setup mode. 1st Take out the batteries of remote control. 2nd Press the temperature insert the battery again. 3rd Make sure the remocon display shown as button simultaneously and . Step 2 : Enter the Option Setup mode and select your option according to the following procedure. 1 The default value is Otherwise, push the . button to .
24296A(1)_1 11/11/05 5:03 PM Page 2-39 Alignment and Adjustments 7 Press button, then the default value is . 8 Push the button to set the display panel to . Every time you push the button, the display panel reads ... repeatedly. 9 8 9 Push the button to set the display panel to . Every time you push the button, the display panel reads ... repeatedly. 7 10 10 11 Push the 12 button to set the display panel to . Every time you push the button, the display panel reads ... repeatedly.
24296A(1)_1 11/11/05 5:03 PM Page 2-40 Alignment and Adjustments ■ MH✳✳✳FKEA/MH✳✳✳FDEA/MH✳✳✳FEEA ex) Option No. : Step 1 : Enter the Option Setup mode. 1st Take out the batteries of remote control. 2nd Press the temp. button simultaneously and insert the battery again. 3rd Make sure the remote control display shown as . Step 2 : Enter the Option Setup mode and select your option according to the following procedure. 1 The default value is Otherwise, push the . button to .
24296A(1)_1 11/11/05 5:03 PM Page 2-41 Alignment and Adjustments 7 Press button, then the default value is . 8 Push the button to set the display panel to . Every time you push the button, the display panel reads ... repeatedly. 7 8 9 9 Push the button to set the display panel to . Every time you push the button, the display panel reads ... repeatedly. 10 11 10 Push the 12 button to set the display panel to . Every time you push the button, the display panel reads ... repeatedly.
24296A(1)_1 11/11/05 5:03 PM Page 2-42 Alignment and Adjustments ■ Table of the option code MODEL OPTION CODE MH020FPEA MH14VP2-07 MH16VP2-07 MH19VP2-07 0d7400-13223F MH023FPEA MH026FPEA MH16VP2-09 MH18VP2-09 MH30VP2-09 0d6400-142351 MH035FPEA MH19VP2-12 MH30VP2-12 0d7404-162362 MH052FPEA MH052FPEA1 0d5408-192351 MH023FWEA MH026FWEA MH14VW2-07 MH16VW2-07 MH16VW2-09 MH18VW2-09 MH19VW2-07 MH30VW2-09 0E8400-142228 MH035FWEA MH19VW2-12 MH30VW2-12 0E7400-16226E MH052FWEA 0E5404-19225F MH026FK
24296A(1)_1 11/11/05 5:03 PM Page 4-1 4. Disassembly and Reassembly Stop operation of the air conditioner and remove the power cord before repairing the unit. 4-1 Indoor Unit 4-1-1 MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳ No Parts 1 Front Panel Procedure Remark 1) Stop the air conditioner operation and shut off the main power. 2) Detach tape of Front Panel upper. 3) Slide the lower Front Grille down, then disassemble it by pulling it forwards.
24296A(1)_1 11/11/05 5:03 PM Page 4-2 Disassembly and Reassembly No Parts Procedure Remark 10) At first, press the left and center hook of the back side of the Panel Grille with the thumb to remove the hook. And press the right of the upper side of the Panel Grille with the fingers. And then disassemble the Panel Grille. 2 Electrical Parts (Main PCB) 3 Tray Drain 4-2 1) Take all the connector of PCB upper side out.
24296A(1)_1 11/11/05 5:03 PM Page 4-3 Disassembly and Reassembly No Parts 4 Heat Exchanger Procedure 1) 2) 3) 4) Remark Loosen 2 fixing earth screws of right side. Detach the Connection Pipe. Detach the Holder Pipe at the rear side. Loosen 3 fixing screws of right and left side. 5) Detach the Heat Exchanger from the indoor unit. 5 Fan Motor & Cross Fan 1) Loosen 2 fixing screws and detach the Motor Holder. 2) Loosen the fixing screw of Fan Motor.
24296A(1)_1 11/11/05 5:03 PM Page 4-4 Disassembly and Reassembly 4-1-2 MH✳✳✳FWEA/MH✳✳VW2-✳✳ No Parts 1 Panel Front Procedure Remark 1) Stop the air conditioner operation and shut off the main power. 2) Detach the Front Grille after pushing out it. 3) Loosen 1 of the right screw and detach the Ass'y display. 4) Loosen 1 of the right screw and detach the Terminal Cover. 5) Detach the cover PCB-DVM and thermistor from the Panel Front.
24296A(1)_1 11/11/05 5:03 PM Page 4-5 Disassembly and Reassembly No Parts Procedure Remark 6) Loosen 5 fixing screws of Panel Front. 7) Unlock 2 hooks to fix Panel Front and Tray Drain. 8) Unlock 2 hooks to fix Panel Front and Back Body. 2 Tray Drain 1) Detach the connected wire of Stepping Motor. 2) Pull Tray Drain out from the Back Body. 3 Heat Exchanger 1) Loosen 1 fixing earth screw of right side.
24296A(1)_1 11/11/05 5:03 PM Page 4-6 Disassembly and Reassembly No Parts Procedure Remark 2) Detach the Room Sensor. 3) Detach the Holder Pipe at the rear side of the unit. 4) Loosen 3 fixing screws of left Holder Evap. 5) Loosen 1 fixing screw of right Holder Motor. 6) Detach the Heat Exchanger from the indoor unit.
24296A(1)_1 11/11/05 5:03 PM Page 4-7 Disassembly and Reassembly No Parts Procedure 4 Electrical Parts (Main PCB) 1) Loosen 4 fixing screws of right Holder control. 2) Take all the connector of PCB upper side out.(Including Power Cord) 3) Detach the outdoor unit connection wire from the Terminal Block. 4) Pull the PCB up to detach. 5 Fan Motor & Cross Fan Samsung Electronics Remark 1) Loosen 2 fixing screws and detach the Motor Holder. 2) Loosen 1 fixing screw of Fan Motor.
24296A(1)_1 11/11/05 5:03 PM Page 4-8 Disassembly and Reassembly 4-1-3 MH✳✳✳FKEA No Parts Procedure 1 Front Grille & Filter 1) Open the Front-Grille by pushing the tabs on the Grille. Remark You must give attention when disassembling the Front-Grille and must check the safety clips have been installed. If you don’t ensure them, the Front Grille will drop suddenly and you will be hurt. 2) Detach the Front Grille. (1) Remove the safety clips.
24296A(1)_1 11/11/05 5:03 PM Page 4-9 Disassembly and Reassembly No Parts 2 Front Panel Procedure Remark 1) Loosen 6 fixing screws holding the panel as shown picture. 2) Detach the Front-Panel pressing the 2 hooks on the both sides of the indoor unit.
24296A(1)_1 11/11/05 5:03 PM Page 4-10 Disassembly and Reassembly No Parts 3 Drain Panel Procedure Remark 1) Loosen 4 fixing screws for Ass'y Drain Panel around as shown in pictures. 2) Detach Ass'y Drain Panel as shown in Pictures.
24296A(1)_1 11/11/05 5:03 PM Page 4-11 Disassembly and Reassembly No Parts 4 Control In Procedure Remark 1) Detach the Control Cover after disassembling 2 screws as shown in pictures. 2) Detach the wire connection part of the Ass'y Main PCB as shown in picture.
24296A(1)_1 11/11/05 5:03 PM Page 4-12 Disassembly and Reassembly No Parts Procedure Remark 3) Loosen 2 fixing screws of Case Control as shown in pictures. 4) Loosen the fixing screw. 5) Detach the Ass'y Case Control part pulling up.
24296A(1)_1 11/11/05 5:03 PM Page 4-13 Disassembly and Reassembly No Parts Procedure Remark 6) Loosen the fixing screw and detach earth cable. 7) Loosen the fixing screw and detach Terminal Cover as shown in pictures. 8) Loosen 2 fixing screws as shown in pictures.
24296A(1)_1 11/11/05 5:03 PM Page 4-14 Disassembly and Reassembly No Parts Procedure Remark 9) Loosen 2 fixing indicating screws of earth cable and the fixing screw of Base Terminal. 10) Detach Base Terminal as shown in picture.
24296A(1)_1 11/11/05 5:03 PM Page 4-15 Disassembly and Reassembly No Parts Procedure 5 Drain Panel Sub 1) Detach Ass'y Drain Panel Sub after loosen 2 fixing screws both side of it. 6 Evap 1) Loosen 3 fixing screws of Ass'y Evap around. Remark 2) Loosen 2 fixing screws as shown in picture and detach Ass'y Cabinet-Side LF B.
24296A(1)_1 11/11/05 5:03 PM Page 4-16 Disassembly and Reassembly No Parts Procedure Remark 3) Detach Ass'y Evap pulling up from the indoor unit as shown in picture. 7 Cross Fan 1) Loosen 3 fixing screws of cover Fan Motor and detach cover Fan Motor. 2) Detach Ass'y Cross Fan as shown in picture. 8 Drain Pump 1) Loosen 4 fixing screws as shown in picture. 2) Detach Drain Hose and detach Ass'y Drain Pump as shown in pictures.
24296A(1)_1 11/11/05 5:03 PM Page 4-17 Disassembly and Reassembly 4-1-4 MH✳✳✳FDEA (Silhouette Duct) No Parts 1 Filter-Pre Procedure Remark 1) Disassemble screws of indication part and then assemble the direction of 2 Plate-Handle places by use of screw as shown in 2). 2) Turn the Plate Handle by hand when removing the Filter-Pre. 3) When pulling the Filter-Pre handle, the Filter-Pre can be assembled. ✳ Be sure to remove the cushion on the marked part after initial installation.
24296A(1)_1 11/11/05 5:03 PM Page 4-18 Disassembly and Reassembly No Parts Procedure Remark 2) Disassemble indicating screws. 3) Detach the sensor holder from the Ass'y Fan case. 4) Detach from Ass'y Control in the capacitor connection wire between the Motor-Fan in and Housing Connector. 5) Detach the Ass'y Blower and Duct from the set.
24296A(1)_1 11/11/05 5:03 PM Page 4-19 Disassembly and Reassembly No Parts 3 Control In Procedure Remark 1) After disassembling indicating screw, detach the Cover-Control. 2) Detach the Motor-Fan in and Sensor Connector connected to PCB. 3) Hold the Ass'y Control In by hand to lift up a little and then release the status of hanging on the hanging slot.
24296A(1)_1 11/11/05 5:03 PM Page 4-20 Disassembly and Reassembly No Parts Procedure 4 Drain Pan 1) Disassemble indicating screws to detach Ass'y Drain Pan. (screws each at left and right side) 5 Evap Remark ✳ Work is possible when disassembling the Ass'y Drain Pan. 1) Disassemble indicating screws. (each at left and right side) 2) Disassemble indicating screws. 3) Disassemble indicating screws. ✳ It is possible at the status of No.3 Ass'y Control In disassembly at the time.
24296A(1)_1 11/11/05 5:04 PM Page 4-21 Disassembly and Reassembly No Parts Procedure Remark 4) After disassembling indicating screws. 5) Pull the Cabinet-Side LF, RH by hand to disassemble. 6) Separate indicating screws. (each at left and right side) 7) Detach it from the set if the Ass'y-Evap pull up.
24296A(1)_1 11/11/05 5:04 PM Page 4-22 Disassembly and Reassembly No Parts Procedure 6 Holder Outlet ✳ When connecting canvas to the discharge side. 1) Disassemble indicating screws. (each at left and right side) Remark 2) Disassemble indicating screws. (each at upper and lower side) ✳ After connecting canvas to the disassembled Ass'y Holder Outlet 2), attach the Ass'y Holder Outlet to the set in the reverse order.
24296A(1)_1 11/11/05 5:04 PM Page 4-23 Disassembly and Reassembly 4-1-5 MH✳✳✳FEEA (Slim Duct) No Parts 1 Motor & Blower Procedure Remark 1) Disassemble the Cabinet Top Motor. – Unscrew 8 screws 2) Disassemble 2 Cover Blower Uppers. – After unscrewing 2 screws – Disassemble the Cover Blower Upper with pushing its hook. 3) Disassemble the Cover Control. – Unscrew 2 screws 4) Disassemble Motor Wires connected to the inside of PCB and connected to the Capacitor.
24296A(1)_1 11/11/05 5:04 PM Page 4-24 Disassembly and Reassembly No Parts Procedure Remark 5) Disassemble the Motor earth wire connected to the Partition. – Unscrew a screw 6) Disassemble the band Motor for fixing the Motor. – Unscrew 2 screws 7) After disassembling the Motor and Blower for the set, disassemble the Blower by use of 3mm wrench. 2 4-24 Drain Pan 1) Disassemble the Cabinet Top Evap.
24296A(1)_1 11/11/05 5:04 PM Page 4-25 Disassembly and Reassembly No Parts Procedure Remark 2) Disassemble the Bracket Outlet Sub that fixes the Drain Pan equipped on the front of the set. – Unscrew 6 screws 3) Disassemble the Drain Cushion from the set. 3 Evaporator ✳ The Evaporator should be disassembled after disassembling the Cover Control 1-3) and the Drain Pan 2-1), 2-2), 2-3). 1) Disassemble the Cover Pipe that fixes the high/low pressure Pipe.
24296A(1)_1 11/11/05 5:04 PM Page 4-26 Disassembly and Reassembly No Parts Procedure Remark 3) Disassemble the Support Evap. LF that fixes the Evaporator. – Unscrew 2 screws 4) Disassemble the Support Evap RH. – Unscrew 2 screws 5) Disassemble the Evaporator form the set. 4 Control In ✳ The Control In should be disassembled after disassembling the Cover Control 1-3). 1) Disassemble all Control Wires connected to the inside of PCB.
24296A(1)_1 11/11/05 5:04 PM Page 4-27 Disassembly and Reassembly No Parts Procedure Remark 3) In case of disassembling the Capacitor separately, disassemble the Capacitor from the Case. 4) In case of disassembling the Case Control, disassemble the Case Control from the set after unscrewing the screw connected to the direction of Blower. ✳ Disassemble if after disassembling the Cabinet Top Motor 1-1). 5) In case of disassembling the Trans Power, unscrew the screw fixing on the Case.
24296A(1)_1 11/11/05 5:04 PM Page 4-28 4-2 Outdoor Unit Take care of the electrical shock by contact on the charging parts before the discharge after power off. (If takes approximately 2 minutes to discharge.) 4-2-1 MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/MH19VP2X/MH14VW2X/MH16VW2X/MH18VW2X/MH19VW2X No Parts 1 Common Work & Control Out Procedure Remark 1) Loosen the fixing screw and detach the Cover-Control. 2) Detach the Cable-Connector Wire from the Terminal-Block.
24296A(1)_1 11/11/05 5:04 PM Page 4-29 Disassembly and Reassembly No Parts Procedure Remark 7) Loosen 9 fixing screws and detach the Cabinet Side. 8) Detach the Terminal and detach the Compressor Lead Wire. 2 Fan & Motor 1) Loosen the fixing nut and detach the Fan. 2) Loosen 4 fixing bolts and detach the Motor. 3) Loosen 2 fixing bolts and detach the Bracket Motor.
24296A(1)_1 11/11/05 5:04 PM Page 4-30 Disassembly and Reassembly No Parts Procedure 3 Heat Exchanger & Compressor 1) Release the refrigerant at first. 2) Disassemble the Inlet and Outlet Pipe by welding. 3) Loosen the fixing screws of the Heat Exchanger. 4) Detach the Heat Exchanger. Remark 5) Loosen 3 nuts of the Compressor. 6) Detach the Compressor.
24296A(1)_1 11/11/05 5:04 PM Page 4-31 Disassembly and Reassembly 4-2-2 MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X No Parts 1 Common Work & Control Out Procedure Remark 1) Loosen the fixing screw and detach the Cover-Control. 2) Detach the Cable-Connector Wire from the Terminal-Block. 3) Loosen 2 fixing screws of the Ass'y Control Out. 4) Loosen 8 fixing screws and detach the Cabinet Upper. 5) Loosen 6 fixing screws, 7 bolts and detach the Cabinet Front.
24296A(1)_1 11/11/05 5:04 PM Page 4-32 Disassembly and Reassembly No Parts Procedure Remark 7) Loosen 12 fixing screws and detach the Cabinet Side. 8) Detach the Terminal Cover and detach the comp lead wire. 2 Fan & Motor 1) Loosen the fixing nut and detach the Fan. 2) Loosen 4 fixing bolts and detach the Motor. 3) Loosen 3 fixing bolts and detach the Bracket Motor.
24296A(1)_1 11/11/05 5:04 PM Page 4-33 Disassembly and Reassembly No Parts Procedure 3 Heat Exchanger & Compressor 1) Release the refrigerant at first. 2) Disassemble the Inlet and Outlet Pipe by welding. 3) Loosen the fixing screw of the Heat Exchanger. 4) Detach the Heat Exchanger. Remark 5) Loosen 3 nuts of the Compressor. 6) Detach the Compressor.
24296A(1)_1 11/11/05 5:04 PM Page 4-34 5.
24296A(1)_1 11/15/05 11:12 AM Page 4-35 Exploded Views and Parts List ■ Parts List Q'TY Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-36 Exploded Views and Parts List ■ Parts List(cont.) Q'TY Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-37 MEMO Samsung Electronics 5-4
24296A(1)_1 11/11/05 5:04 PM Page 4-38 Exploded Views and Parts List 5-1-2 MH052FPEA/MH052FPEA1 9 7 7-4 11 12 7-7 7-8 12-4 12-6 7-1 12-1 12-3 7-6 7-2 12-2 7-5 12-5 7-3 3 6 8 13 1 10 1-2 1-1-2 1-1 1-1-3 1-1-1 1-3 1-1-4 1-1-5 2 1-1-6 1-4 5 4 5-5 Samsung Electronics
24296A(1)_1 11/11/05 5:04 PM Page 4-39 Exploded Views and Parts List ■ Parts List Q'TY No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-40 Exploded Views and Parts List 5-1-3 MH023FWEA/MH026FWEA/MH035FWEA/MH14VW2-07/MH16VW2-07/MH16VW2-09/ MH18VW2-09/MH19VW2-07/MH19VW2-12/MH30VW2-09/MH30VW2-12 17 14 6 14-1 15 11 14-2 12 7 14-3 14-4 22 14-5 16 18 3 14-6 22-1 3-1 13 9 19 3-2 9-2 3-4 10 20 9-3 22-2 3-3 9-1 1 5 1-1 23 4 2-5 8 2-4 1-2 2-1 2-5-1 2-2 2-6 2-3 2 21 5-7 Samsung Electronics
24296A(1)_1 11/11/05 5:04 PM Page 4-41 Exploded Views and Parts List ■ Parts List Q'TY Description Specification MH023FWEA MH026FWEA MH035FWEA SA /SNA MH✳✳VW2-07 MH✳✳VW2-12 MH✳✳VW2-09 No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-42 Exploded Views and Parts List ■ Parts List(cont.) Q'TY Description Specification MH023FWEA MH026FWEA MH035FWEA SA/ SNA MH✳✳VW2-07 MH✳✳VW2-12 MH✳✳VW2-09 No. Code No. 17 DB70-00514A PLATE-HANGER SGCC-M, T0.
24296A(1)_1 11/11/05 5:04 PM Page 4-43 MEMO Samsung Electronics 5-10
24296A(1)_1 11/11/05 5:04 PM Page 4-44 Exploded Views and Parts List 5-1-4 MH052FWEA 17 14 6 15 14-1 11 14-2 12 7 14-3 14-4 21 14-5 16 18 3 14-6 21-1 9 3-1 13 24 3-2 10 3-4 19 21-2 23 3-3 1 1-1 5 22 4 2-5 8 2-4 2-1 2-5-1 1-2 2 2-2 2-6 2-3 20 5-11 Samsung Electronics
24296A(1)_1 11/11/05 5:04 PM Page 4-45 Exploded Views and Parts List ■ Parts List Description Specification Q'TY No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-46 Exploded Views and Parts List 5-1-5 MH026FKEA / MH035FKEA 1 24 3 23 3-1 2 9 10 22 11 13 8 12 4 7 14-2 6 14 5 14-1 15 18 16 17 20 19 21 5-13 Samsung Electronics
24296A(1)_1 11/11/05 5:04 PM Page 4-47 Exploded Views and Parts List ■ Parts List Q'TY SA/ SNA ASS'Y 1 SA HOLDER DRAIN PUMP Fire-Resistant P.S(V0) 1 SNA DB31-00303A DRAIN PUMP FUJIKOKI 1 SA 3-1 DB31-00303A DRAIN HOSE-SOCKET POM 1 SNA 4 DB69-00298A CUSHION BODY EPS 1 SNA 5 DB61-00363A CASE-FAN SIDE Fire-Resistant P.
24296A(1)_1 11/11/05 5:04 PM Page 4-48 Exploded Views and Parts List ■ PK118MG 4 1 5 2 3 6 7 8 9 10 11 5-15 Samsung Electronics
24296A(1)_1 11/11/05 5:04 PM Page 4-49 Exploded Views and Parts List ■ Parts List Q'TY SA/ SNA HIPS (UL94-V0) 1 SA BLADE-V HIPS (UL94-V0) 10 SA DB66-00157A LINK BLADE-LF POM 2 SA 4 DB63-00163A COVER PCB CASE HIPS (UL94-V0) 1 SA 5 DB93-01021A ASS'Y PCB DISPLAY - 1 SA 6 DB31-10153D MOTOR STEP MSFCC20A05 1 SA 7 DB61-00535A HOLDER MOTOR HIPS (UL94-V0) 1 SNA 8 DB64-00234B PANEL FRONT HIPS (UL94-V0) 1 SA 9 DB66-00159A BLADE-H HIPS (UL94-V0) 1 SA 10 DB64-0024
24296A(1)_1 11/11/05 5:04 PM Page 4-50 Exploded Views and Parts List 5-1-6 MH052FDEA 1 2 19 5 19-2 13 19-3 18 19-6 5-5 19-1 5-3 19-4 5-6 19-5 5-4 5-7 12 5-1 17 5-2 10 9 11 4 8 16 7 14 6 15 3 5-17 Samsung Electronics
24296A(1)_1 11/11/05 5:04 PM Page 4-51 Exploded Views and Parts List ■ Parts List Q'TY SA/ SNA SGCC-M T0.8 1 SNA SGCC-M T0.8 1 SNA ASS'Y-DRAIN PAN ASS'Y, BLK 1 SA DB61-00099A CASE-BOTTOM SGCC-M, T0.8 1 SNA 5 DB94-00023C ASS'Y-BLOWER DUCT ASS'Y 1 SA 5-1 DB64-00071A PANEL-DUCT HOLDER SGCC-M, T1.2 1 SNA 5-2 DB61-00155A BRACKET-MOUNT MOTOR SGCC-M, T2.
24296A(1)_1 11/11/05 5:04 PM Page 4-52 Exploded Views and Parts List 5-1-7 MH023FEEA/MH026FEEA/MH035FEEA 1 8 20 2 17 18 19 16 21 13 15 12 11 24 25 23 4 14 3 9 5 22 10 8 6 7 23-5 23-6 23-4 23-1 23-7 23-8 23-3 23-2 5-19 Samsung Electronics
24296A(1)_1 11/11/05 5:04 PM Page 4-53 Exploded Views and Parts List ■ Parts List Q'TY SA/SNA ASS'Y 1 SA ASS'Y CABINET SIDE LF ASS'Y 1 SA DB90-01951A ASS'Y CABINET SIDE RH ASS'Y 1 SA 4 DB90-01938A ASS'Y COVER PIPE ASS'Y 1 SA 5 DB90-01950A ASS'Y COVER DRAIN PUMP ABS T2.0 1 SA 6 DB64-01326A CABINET TOP MOTOR SGCC-M, T0.8 1 SA 7 DB90-02069A ASS'Y CABINET TOP EVAP ASS'Y 1 SA 8 DB61-02274A PLATE HANGER SGCC-M T2.
24296A(1)_1 11/11/05 5:04 PM Page 4-54 5-2 Outdoor Unit 5-2-1 MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/MH19VP2X/MH14VW2X/ MH16VW2X/MH18VW2X/MH19VW2X 17 8 17-1 12 7 11 18 6 5 4 13 3 16-1 16 16-2 2 13-1 15 1 14 9 20 10 19 1-1 5-21 Samsung Electronics
24296A(1)_1 11/11/05 5:04 PM Page 4-55 Exploded Views and Parts List ■ Parts List Q'TY SA/SNA ASS'Y 1 SA GUARD FAN PP,SC-90073R 1 SA DB90-01908A ASS'Y BASE OUT ASS'Y 1 SNA 3 DB67-00438A FAN PROPELLER PP 1 SA 4 DB31-00268B MOTOR FAN SGCC-M 1 SA 5 DB90-00966B ASS'Y BRACKET MOTOR ASS'Y 1 SA 6 DB94-00694A ASS'Y PARTITION ASS'Y 1 SNA 7 DB96-04466A ASS'Y CONDENSER ASS'Y 1 SA 8 DB61-02364A GUIDE SCREEN P.E.
24296A(1)_1 11/11/05 5:04 PM Page 4-56 Exploded Views and Parts List 5-2-2 MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X 8 17 12 17-1 7 11 18 5 6 4 13 3 16-1 16-2 16-3 16-4 16 1 2 13-1 14 21 9 20 15 1-1 10 5-23 19 Samsung Electronics
24296A(1)_1 11/15/05 11:13 AM Page 4-57 Exploded Views and Parts List ■ Parts List Q'TY No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-58 6. Electrical Parts List ■ MAIN PCB : DB93-02779B(MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳) Location No. Code No. Description Specification Q'TY SA/SNA Remark BD71 0402-001298 DIODE-BRIDGE DF06S,600V,1A,SMD-4,TP 1 SNA BZ61 3002-001129 BUZZER-PIEZO 85DB,-,-,2KHz,- 1 SNA C102 2401-003895 C-AL 15uF,20%,450V,GP,TP,12.
24296A(1)_1 11/11/05 5:04 PM Page 4-59 ■ MAIN PCB : DB93-02779B(MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳)(cont.) Location No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-60 Electrical Parts List ■ MAIN PCB : DB93-02779B(MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳)(cont.) Location No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-61 Electrical Parts List ■ MAIN PCB : DB93-02779B(MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark Q601 0501-000534 TR-SMALL SIGNAL 2SC2412K,NPN,200mW,SOT-23,TP,1 1 SNA Q602 0501-002296 TR-SMALL SIGNAL MMST2907A,PNP,200mW,SMT3,TP,100-3 1 SNA Q603 0501-000534 TR-SMALL SIGNAL 2SC2412K,NPN,200mW,SOT-23,TP,1 1 SNA R101 2007-000290 R-CHIP 100ohm,5%,1/8W,TP,2012 1 SNA R102 2007-000493 R-CHIP 2.
24296A(1)_1 11/11/05 5:04 PM Page 4-62 Electrical Parts List ■ MAIN PCB : DB93-02779B(MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark R406 2007-000766 R-CHIP 330ohm,5%,1/8W,TP,2012 1 SNA R501 2007-000468 R-CHIP 1Kohm,5%,1/8W,TP,2012 1 SNA R502 2007-000468 R-CHIP 1Kohm,5%,1/8W,TP,2012 1 SNA R503 2007-001071 R-CHIP 6.
24296A(1)_1 11/11/05 5:04 PM Page 4-63 Electrical Parts List ■ MAIN PCB : DB93-03542A(MH023/026/035FWEA,MH✳✳VW2-✳✳) Location No. Code No. Description Specification Q'TY SA/SNA Remark R11 2007-000023 DIODE-BRIDGE 120ohm,5%,1/8W,TP,2012 1 SNA R12 2007-000023 BUZZER-PIEZO 120ohm,5%,1/8W,TP,2012 1 SNA BD71 0402-001298 C-AL DF06S,600V,1A,SMD-4,TP 1 SNA BZ61 3002-001129 C-CER,CHIP 85DB,-,-,2KHz,- 1 SNA C102 2401-003895 C-AL 15uF,20%,450V,GP,TP,12.
24296A(1)_1 11/11/05 5:04 PM Page 4-64 Electrical Parts List ■ MAIN PCB : DB93-03542A(MH023/026/035FWEA,MH✳✳VW2-✳✳)(cont.) Location No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-65 Electrical Parts List ■ MAIN PCB : DB93-03542A(MH023/026/035FWEA,MH✳✳VW2-✳✳)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark IC06 0506-000175 IC-BUS TRANSCEIVER 2003,NPN,7,1W,SOP-16,ST,1000 1 SNA IC07 0506-000175 IC-CMOS LOGIC 2003,NPN,7,1W,SOP-16,ST,1000 1 SNA IC08 1003-001462 IC-EEPROM TD62783AFW,SOL,18P,-,8,-500mA 1 SNA IC18 1006-001325 THERMISTOR-NTC 1487,SO,8P,4.9x3.
24296A(1)_1 11/11/05 5:04 PM Page 4-66 Electrical Parts List ■ MAIN PCB : DB93-03542A(MH023/026/035FWEA,MH✳✳VW2-✳✳)(cont.) Location No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-67 Electrical Parts List ■ MAIN PCB : DB93-03542A(MH023/026/035FWEA,MH✳✳VW2-✳✳)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark SS71 3502-000115 RESONATOR-CERAMIC 12Vdc,-,2A,1mS,1mS 1 SNA ST11 DB26-00015A C-FILM,LEAD-PPF -,JT1916-09,-,310V,FERRITE,-,E 1 SNA VA71 1405-000154 C-FILM,LEAD-PPF 560V,2500A,17.5x7.5mm,TP 1 SNA X501 2802-001179 DIODE-ZENER 4MHz,0.5%,BK,8x3x5.
24296A(1)_1 11/11/05 5:04 PM Page 4-68 Electrical Parts List ■ MAIN PCB : DB93-03542B(MH052FWEA) Location No. Code No. Description Specification Q'TY SA/SNA Remark R11 2007-000023 DIODE-BRIDGE 120ohm,5%,1/8W,TP,2012 1 SNA R12 2007-000023 BUZZER-PIEZO 120ohm,5%,1/8W,TP,2012 1 SNA BD71 0402-001298 C-AL DF06S,600V,1A,SMD-4,TP 1 SNA BZ61 3002-001129 C-CER,CHIP 85DB,-,-,2KHz,- 1 SNA C102 2401-003895 C-AL 15uF,20%,450V,GP,TP,12.
24296A(1)_1 11/11/05 5:04 PM Page 4-69 Electrical Parts List ■ MAIN PCB : DB93-03542B(MH052FWEA)(cont.) Location No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-70 Electrical Parts List ■ MAIN PCB : DB93-03542B(MH052FWEA)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark IC06 0506-000175 IC-BUS TRANSCEIVER 2003,NPN,7,1W,SOP-16,ST,1000 1 SNA IC07 0506-000175 IC-CMOS LOGIC 2003,NPN,7,1W,SOP-16,ST,1000 1 SNA IC08 1003-001462 IC-EEPROM TD62783AFW,SOL,18P,-,8,-500mA 1 SNA IC18 1006-001325 THERMISTOR-NTC 1487,SO,8P,4.9x3.
24296A(1)_1 11/11/05 5:04 PM Page 4-71 Electrical Parts List ■ MAIN PCB : DB93-03542B(MH052FWEA)(cont.) Location No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-72 Electrical Parts List ■ MAIN PCB : DB93-03542B(MH052FWEA)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark SS71 3502-000115 RESONATOR-CERAMIC 12Vdc,-,2A,1mS,1mS 1 SNA ST11 DB26-00015A C-FILM,LEAD-PPF -,JT1916-09,-,310V,FERRITE,-,E 1 SNA VA71 1405-000154 C-FILM,LEAD-PPF 560V,2500A,17.5x7.5mm,TP 1 SNA X501 2802-001179 DIODE-ZENER 4MHz,0.5%,BK,8x3x5.
24296A(1)_1 11/11/05 5:04 PM Page 4-73 Electrical Parts List ■ SUB PCB : DB93-03692A(MH✳✳✳FWEA, MH✳✳VW2-✳✳) Location No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-74 Electrical Parts List ■ MAIN PCB : DB93-02335D(MH✳✳✳FKEA) Location No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-75 Electrical Parts List ■ MAIN PCB : DB93-02335D(MH✳✳✳FKEA)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark C111 2401-001363 C-AL 470uF,20%,16V,GP,TP,10x12.5,5 1 SNA L101 2702-001118 INDUCTOR-RADIAL 5mH,10%,8x11mm 1 SNA L102 - INDUCTOR-RADIAL 4.7uH,10%,6.5x7.5mm 1 SNA SNA X301 2802-000103 RESONATOR-CERAMIC 10MHz,0.5%,TP,10.0x5.0x8.0mm 1 F702 3601-001209 FUSE-RADIAL LEAD 250V,1A,TIME-LAG,-,8.
24296A(1)_1 11/11/05 5:04 PM Page 4-76 Electrical Parts List ■ MAIN PCB : DB93-02335D(MH✳✳✳FKEA)(cont.) Location No. Code No. Description Specification CN75 3711-000203 CONNECTOR-HEADER YW396-03AV,WHT,1WALL,2P,1R,7.92mm,STRAIGHT,SN 1 SNA CN71 3711-003404 CONNECTOR-HEADER YW396-03AV,BLU,1WALL,2P,1R,7.92mm,STRAIGHT,SN 1 SNA CN73 3711-003405 CONNECTOR-HEADER YW396-03AV,BLK,1WALL,2P,1R,7.92mm,STRAIGHT,SN 1 SNA CN72 3711-000262 CONNECTOR-HEADER YW396-05AV,WHT,1WALL,3P,1R,7.
24296A(1)_1 11/11/05 5:04 PM Page 4-77 Electrical Parts List ■ MAIN PCB : DB93-01764D(MH✳✳✳FDEA) Location No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-78 Electrical Parts List ■ MAIN PCB : DB93-01764D(MH✳✳✳FDEA)(cont.) Location No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-79 Electrical Parts List ■ MAIN PCB : DB93-03213D(MH✳✳✳FEEA) Location No. Code No.
24296A(1)_1 11/11/05 5:04 PM Page 4-80 Electrical Parts List ■ MAIN PCB : DB93-03213D(MH✳✳✳FEEA)(cont) Location No. Code No. Description Specification Q'TY SA/SNA Remark F701 3602-000147 FUSE-CLIP 250V,7.5A,30mohm 2 SNA F701_1 3601-000263 FUSE-CARTRIDGE 250V,3.15A,TIME-LAG,GLASS,5x20mm 1 SNA F702 3601-001308 FUSE 250V,1.6A,TIME-LAG,PLASTIC,8.4x7.6mm 1 SNA FT71 DB27-00019A COIL CHOKE 250V,2.
24296A(1)_1 11/11/05 5:04 PM Page 4-81 Electrical Parts List ■ OUTDOOR PCB : DB93-03143A(MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/ MH19VP2X/MH14VW2X/MH16VW2X/MH18VW2X/MH19VW2X) Location No. Code No. Description Specification Q'TY SA/SNA Remark *CN50 3711-000795 CONNECTOR-HEADER BOX,2P,1R,2.
24296A(1)_1 11/11/05 5:04 PM Page 4-82 Electrical Parts List ■ OUTDOOR PCB : DB93-03143A(MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/ MH19VP2X/MH14VW2X/MH16VW2X/MH18VW2X/MH19VW2X)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark CN52 3711-000940 CONNECTOR-HEADER BOX,4P,1R,2.5mm,STRAIGHT,SN 1 SNA CN53 3711-000998 CONNECTOR-HEADER BOX,5P,1R,2.5mm,STRAIGHT,SN,RED 1 SNA CN54 3711-001000 CONNECTOR-HEADER BOX,5P,1R,2.
24296A(1)_1 11/11/05 5:04 PM Page 4-83 Electrical Parts List ■ OUTDOOR PCB : DB93-03143A(MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/ MH19VP2X/MH14VW2X/MH16VW2X/MH18VW2X/MH19VW2X)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark R103,R512,R601,R604 2007-000468 R-CHIP 1Kohm,5%,1/8W,TP,2012 4 SNA R104 2007-000686 R-CHIP 3.3Kohm,5%,1/8W,TP,2012 1 SNA R105 2007-001222 R-CHIP 9.09Kohm,1%,1/8W,TP,2012 1 SNA R106,R203,R204 2007-000263 R-CHIP 1.
24296A(1)_1 11/11/05 5:04 PM Page 4-84 Electrical Parts List ■ OUTDOOR PCB : DB93-03143A(MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/ MH19VP2X/MH14VW2X/MH16VW2X/MH18VW2X/MH19VW2X)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark R808,R412 2007-000931 R-CHIP 470ohm,5%,1/8W,TP,2012 2 SNA R901~R907 2007-001318 R-CHIP 1Kohm,5%,1/4W,DA,TP,3216 7 SNA R908~R910 2007-001175 R-CHIP 8.2Kohm,1%,1/10W,TP,1608 3 SNA RY01 3501-001169 RELAY-POWER 12VDC,0.
24296A(1)_1 11/11/05 5:04 PM Page 4-85 Electrical Parts List ■ OUTDOOR PCB : DB93-02893A(MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X) Location No. Code No. Description Specification Q'TY SA/SNA Remark CN50 3711-000795 CONNECTOR-HEADER BOX,2P,1R,2.
24296A(1)_1 11/11/05 5:04 PM Page 4-86 Electrical Parts List ■ OUTDOOR PCB : DB93-02893A(MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark CN53 3711-000998 CONNECTOR-HEADER BOX,5P,1R,2.5mm,STRAIGHT,SN,RED 1 SNA CN54 3711-001000 CONNECTOR-HEADER BOX,5P,1R,2.5mm,STRAIGHT,SN 1 SNA CN55 3711-000997 CONNECTOR-HEADER BOX,5P,1R,2.5mm,STRAIGHT,SN 1 SNA CN56 3711-000996 CONNECTOR-HEADER BOX,5P,1R,2.
24296A(1)_1 11/11/05 5:04 PM Page 4-87 Electrical Parts List ■ OUTDOOR PCB : DB93-02893A(MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X)(cont.) Location No. Code No. Description Specification Q'TY SA/SNA Remark R106,R203,R204 2007-000263 R-CHIP 1.82Kohm,1%,1/8W,TP,2012 3 SNA R107 2003-000708 R-OXIDE 47ohm,5%,1W,MOR1W47ohmJTB 1 SNA R112,R113,R114 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 3 SNA R115 2007-000385 R-CHIP 14.3Kohm,1%,1/4W,TP,3216 1 SNA R202 R207 2007-002667 R-CHIP 90.
24296A(1)_1 11/11/05 5:04 PM Page 4-88 Electrical Parts List ■ OUTDOOR PCB : DB93-02893A(MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X)(cont.) Location No. Code No. Description RELAY-POWER Specification Q'TY SA/SNA Remark RY01 3501-001169 12VDC,0.9W,20000mA,SPST,20mS,10mS 1 SA RY31 3501-001248 RELAY-MINIATURE 12V,-,11.7mA,DPDT,4mS,4mS 1 SNA VA01,VA02,VA03,VA04,VA05 1405-000154 VARISTOR 560V,2500A,17.5x7.5mm,TP 5 SNA XTAL01 2802-001221 RESONATOR-CERAMIC 6.25MHz,+/-0.5%,TP,8.5x6.5x4.
24296A(1)_1 11/11/05 5:04 PM Page 4-89 MEMO Samsung Electronics 6-32
24296A(1)_2 11/11/05 5:06 PM Page 4-78 7. Wiring Diagram 7-1 Indoor Unit ■ MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳ This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:06 PM Page 4-79 Indoor Unit(cont.) ■ MH✳✳✳FWEA/MH✳✳VW2-✳✳ This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:06 PM Page 4-80 Wiring Diagram ■ MH✳✳✳FKEA This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:06 PM Page 4-81 Wiring Diagram ■ MH✳✳✳FDEA This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:06 PM Page 4-82 Wiring Diagram ■ MH✳✳✳FEEA This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:06 PM Page 4-83 7-2 Outdoor Unit ■ MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/MH19VP2X/MH14VW2X/MH16VW2X/MH18VW2X/MH19VW2X This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:06 PM Page 4-84 Wiring Diagram ■ MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X This Document can not be used without Samsung's authorization.
11/11/05 5:06 PM Page 8-1 8. Schematic Diagram 8-1 Indoor Unit ■ MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳ STEP MOTOR 24296A(1)_2 This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:06 PM Page 8-2 Schematic Diagram ■ MH✳✳✳FWEA/MH✳✳VW2-✳✳ This Document can not be used without Samsung's authorization.
11/11/05 5:06 PM Page 8-3 Schematic Diagram ■ MH✳✳✳FKEA STEP MOTOR 24296A(1)_2 This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:06 PM Page 8-4 Schematic Diagram ■ MH✳✳✳FDEA This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:06 PM Page 8-5 Schematic Diagram ■ MH✳✳✳FEEA This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:06 PM Page 8-6 8-2 Outdoor Unit ■ MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/MH19VP2X/MH14VW2X/MH16VW2X/MH18VW2X/MH19VW2X This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:06 PM Page 8-7 Schematic Diagram ■ MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:10 PM Page 8-8 9. Circuit Descriptions 9-1 PCB Circuit Descriptions 9-1-1 Outdoor Unit(MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/MH19VP2X/MH14VW2X/MH16VW2X/MH18VW2X/MH19VW2X) Compressor Inverter Drive Communication SMPS Temperature Sensor Detect Zero Crossing Detect Display Drive EEV & Relay Drive Power Factor Control EMI Filter Block This Document can not be used without Samsung's authorization.
24296A(1)_2 11/11/05 5:10 PM Page 8-10 Circuit Descriptions Circuit Descriptions 9-1-2 Outdoor Unit(MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X) Compressor Inverter Drive Communication SMPS Temperature Sensor Detect Zero Crossing Detect Display Drive EEV & Relay Drive Power Factor Control EMI Filter Block This Document can not be used without Samsung's authorization.
11/11/05 5:06 PM Page 8-12 9-2 Refrigerating Cycle Diagram ■ MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/MH14VW2X/MH16VW2X/MH18VW2X ex) 2 Rooms(MH026FPEA+MH026FPEA, MH✳✳✳✳✳-07+MH✳✳VP2-07, MH✳✳✳✳✳-07+MH✳✳✳✳✳-09, MH✳✳VP2-09+MH✳✳✳✳✳-09) OUTDOOR UNIT INDOOR UNIT ROOM A Header (5/8") Distributor ROOM B 1/4" 1/2" 1/2" Muffler 4-Way valve 1/2" Service valve 1 2 3/8" 3/8" 3/8" Inverter MainCompressor accumulator Receiver EEV Service valve 24296A(1)_2 1 2 1/4" 1/4" Subaccumulator 9-3 Sams
11/11/05 5:06 PM Page 8-13 Circuit Descriptions ■ MH19VP2X/MH19VW2X ex) 2 Rooms(MH✳✳✳✳✳-07+MH✳✳✳✳✳-12) OUTDOOR UNIT INDOOR UNIT ROOM A Header (5/8") Distributor ROOM B 1/4" 1/2" 1/2" 4-Way valve Muffler 1/2" Service valve 1 2 3/8" 3/8" 3/8" Inverter Compressor Mainaccumulator Receiver Service valve 24296A(1)_2 EEV 1 2 1/4" 1/4" Subaccumulator Samsung Electronics 9-4
24296A(1)_2 11/11/05 5:06 PM Page 8-14 Circuit Descriptions ■ MH30VP2X/MH30VW2X ex) 3 Rooms(MH30✳✳2-09+MH30✳✳2-09+MH30✳✳2-12) OUTDOOR UNIT INDOOR UNIT ROOM A Header (5/8") Distributor 3/8" ROOM B 1/2" ROOM C 1/2" Service valve (5/8") 1/2" Inverter MainCompressor accumulator 1 2 3 4 3/8" 3/8" 3/8" EEV Service v/v (3/8") Receiver 1/4" 1/4" 1/4" Subaccumulator 9-5 Samsung Electronics
24296A(1)_2 11/15/05 11:15 AM Page 8-15 Circuit Descriptions ■ MH068FXEA4/MH080FXEA4 ex) 4 Rooms(MH026FPEA+MH026FPEA+MH035FPEA+MH052FPEA✳) OUTDOOR UNIT INDOOR UNIT ROOM A Header (5/8") Distributor 3/8" ROOM B 1/2" ROOM C 1/2" Service valve (5/8") 1/2" Inverter MainCompressor accumulator 1 2 3 4 ROOM D 3/8" 3/8" 3/8" 1/2" EEV Service v/v (3/8") Receiver 1/4" 1/4" 1/4" 1/4" Subaccumulator Samsung Electronics 9-6
24296A(1)_2 11/11/05 5:06 PM Page 8-16 10. PCB Diagram 10-1 MAIN PCB(Indoor Unit) ■ MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳ The red number connecter is not used.
24296A(1)_2 11/11/05 5:06 PM Page 8-17 ■ MH✳✳✳FWEA/MH✳✳VW2-✳✳(MAIN PCB) The red number connecter is not used.
24296A(1)_2 11/11/05 5:06 PM Page 8-18 PCB Diagram ■ MH✳✳✳FWEA/MH✳✳VW2-✳✳(SUB PCB) The red number connecter is not used.
24296A(1)_2 11/11/05 5:06 PM Page 8-19 PCB Diagram ■ MH✳✳✳FKEA The red number connecter is not used.
24296A(1)_2 11/11/05 5:06 PM Page 8-20 PCB Diagram ■ MH✳✳✳FDEA ! @ # $ % ^ & ) * ( 1 2 3 5 6 ! Heat-Thermal ( Float Switch @ EVA out Temperature ) Heater Room Temperature 1 Fan Motor EVA in Temperature 2 Drain Pump $ Display 3 Ventilator % EEV 4 Water Coil ^ 12V Power 5 Power & COM 2 6 Trans in * COM 1 7 Trans out # 10-5 4 7 Samsung Electronics
24296A(1)_2 11/11/05 5:06 PM Page 8-21 PCB Diagram ■ MH✳✳✳FEEA ! @ 4# $( % ^ & * ) 5 1 2 6 3 7 8 9 0 ! “ ‘ + = Float Switch 3 COM 2 Room Temperature 4 Load Control Signal EVA in Temperature 5 Heater # EVA out Temperature 6 Address Switch $ Heater Temperature 7 Option Switch % Wired Remote Controller Power(12V) 8 Fan (Tap Control) ^ Control Signal 9 Ventilator & EEV 0 Drain Pump * Display “ Hot Coil ( Operating Check Signal ‘ Fan (SSR) ) HALL IC +
24296A(1)_2 11/11/05 5:06 PM Page 8-22 10-2 MAIN PCB(Outdoor Unit) ■ MH040FXEA2/MH052FXEA2/MH14VP2X/MH16VP2X/MH18VP2X/MH19VP2X/MH14VW2X/MH16VW2X/MH18VW2X/MH19VW2X ! @ # $ 4 ) * &^ % ( 1 2 3 10-7 ! Compressor C/W * Thermistor-O.L.
24296A(1)_2 11/11/05 5:06 PM Page 8-23 PCB Diagram ■ MH068FXEA4/MH080FXEA4/MH30VP2X/MH30VW2X ! @ # $ 6 2* & ^ % ) ( 1 4 3 5 ! Compressor C/W ( Thermistor-Out/Discharge @ Communication ) Thermistor-O.L.
24296A(1)_2 11/11/05 5:07 PM Page 8-24 11. Operating Instructions 11-1 MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳ 11-1-1 The Feature of Key in remote control No 1 BUTTON FUNCTION (On/Off) On/Off button. Press the button to stop or run the air conditioner. (UP) Temperature adjustment button(UP). The temperature is increased by the pressing the temperature button. (DOWN) Temperature adjustment button(DOWN). The temperature is decreased by the pressing the temperature button. 2 3 Mode selection button.
24296A(1)_2 11/11/05 5:07 PM Page 8-25 The Feature of Key in remote control(cont.) No BUTTON 9 FUNCTION Off Timer button. The Off Timer enables you to switch off the air conditioner automatically after a given period of time that is from 30 minutes to 24 hours. To set the operating time, press the time display. 10 Timer Set/Cancel button. After setting On Timer or Off Timer, press the And press the 11 Samsung Electronics button one or more times until the required button to set it completely.
24296A(1)_2 11/11/05 5:07 PM Page 8-26 Operating Instructions 11-1-2 Wireless Remote Control-Buttons and Display Operating mode Remote control transmission indicator Battery discharge indicator Fan speed Sleep mode ( AUTO, FAN, COOL, HEAT) DRY, Turbo mode Temperature setting Air flow direction Off Timer setting On Timer setting On/Off button Temperature adjustment buttons Mode selection button (AUTO, COOL, DRY, FAN, HEAT) Fan speed adjustment button Turbo button On Timer button Off Timer button
24296A(1)_2 11/11/05 5:07 PM Page 8-27 11-2 MH✳✳✳FWEA/MH✳✳VW2-✳✳ 11-2-1 Basic Function Mode Explanation Remark Auto Mode Press the button on the remote control until is displayed. Cool Mode Press the button on the remote control until is displayed. Press the is displayed. button to select the fan speed until the required setting Automatic (rotated : ) Low Medium High Heat Mode Press the button on the remote control until Press the is displayed.
24296A(1)_2 11/11/05 5:07 PM Page 8-28 Operating Instructions Basic Function(cont.) Mode 11-5 Explanation Remark Dry Mode Press the button on the remote control until is displayed. Fan Mode Press the button on the remote control until is displayed.
24296A(1)_2 11/11/05 5:07 PM Page 8-29 Operating Instructions 11-2-2 Applied Function Mode Turbo Function Explanation Press the Remark button. • After 30 minutes, the air conditioner is reset automatically to the previous setting. • You can select the Turbo function in the Auto, Cool and Heat mode. If you select this function in the Dry or Fan mode, the mode changes to the Auto mode. Energy Saving Function Press the button. Auto Cleaning Function Press the button.
24296A(1)_2 11/11/05 5:07 PM Page 8-30 Operating Instructions 11-2-3 Wireless Remote Control-Buttons and Display Operating mode Remote control transmission indicator ( AUTO, COOL, FAN, HEAT) DRY, Sound On /Off indicator Battery life indicator Fan speed indicator Anions indicator Sleep mode indicator On Timer indicator Turbo function indicator Temperature setting Air flow direction Off Timer indicator Energy saving indicator Power (On/Off) button Temperature adjustment buttons Mode selection but
24296A(1)_2 11/11/05 5:07 PM Page 8-31 11-3 MH✳✳✳FKEA/MH✳✳✳FDEA/MH✳✳✳FEEA 11-3-1 The Feature of Key in remote control No BUTTON FUNCTION On/Off & Timer Set/Cancel button. Press the button to stop and run the air conditioner or set up On/Off timer. 1 Mode selection button. Each time you press this button, mode is changed in the following order. √ In case of Heat pump model 2 : Auto Mode : Fan Mode : Cool Mode : Heat Mode : Dry Mode √ In case of Cooling only model (UP) Temp.
24296A(1)_2 11/11/05 5:07 PM Page 8-32 Operating Instructions 11-3-2 Wireless Remote Control-Buttons and Display Mode selection button Operating mode Temperature adjustment buttons Temperature setting Filter Reset button Fan speed Fan speed adjustment button Swing button Air flow direction On Timer setting On Timer button Off Timer setting Off Timer button Battery discharge indicator On/Off & Timer Set/Cancel button Note : • After cleaning the air filter, press the 11-9 button.
24296A(1)_2 11/11/05 5:07 PM Page 12-1 12. Troubleshooting 12-1 Items to be checked first 1. The input voltage should be rating voltage ±10% range. The air conditioner may not operate properly if the voltage is out of this range. 2. Is the link cable linking the indoor unit and the outdoor unit linked properly? The indoor unit and the outdoor unit shall be linked by 4 wires. 2 wires are for power and other 2 wires are for communication, total 4 wires on each indoor unit.
24296A(1)_2 11/11/05 5:07 PM Page 12-2 12-2 Checking and Testing operations To complete the installation, perform the following checks and tests to ensure that the air conditioner is operating correctly. 1. 1. 1. 1. 1. 1. 1. 1. 1. 1. 1.
24296A(1)_2 11/11/05 5:07 PM Page 12-3 Troubleshooting 2. Apply the power to the outdoor unit. Outdoor unit will try to communicate the specified number of indoor units by SW01 on outdoor display PCB. Does LED show "Normal display"? "Normal display" means, right 2 digit of LED on Display PCB displays '00' and left 2 digit of LED displays indoor unit address number. Yes OK : This number is displayed only while communicating, so each number is displayed for a short time in order.
24296A(1)_2 11/11/05 5:07 PM Page 12-4 Troubleshooting ■ In case of MANUAL ADDRESSING mode. (SW02-1:OFF) 2. ■ Checking the address number correctly on each indoor unit PCB. 2. ■ - "PIPE CHECK MODE" is also able to use. ● If Error code is displayed on indoor or outdoor LED, check as follows; SW01 setting number and the number of indoor unit installed are the same. Yes SW01 setting number must same as the number of indoor unit. Yes Check communication wire and power wire connection.
24296A(1)_2 11/11/05 5:07 PM Page 12-5 12-3 Fault Diagnosis by Symptom 12-3-1 Basic Check Flow Preparation : multimeter (AC voltage, DC voltage, Resistance) START Short check for safety Check point Detach cable cover of the terminal blocks (HANDLE CABI RH) on outdoor unit. Check resistance value between L and N of Main power terminal block.
24296A(1)_2 11/11/05 5:07 PM Page 12-6 Troubleshooting Basic Check Flow(cont.
24296A(1)_2 11/11/05 5:07 PM Page 12-7 Troubleshooting 12-3-2 Checking Outdoor Controller 1. Making sure the wire connections. Live side 2. Checking AC line 1) Checking FUSE 2) Checking resistance between 'L wire (BRN)' and 'DB01 Live side' normal value : 190 - 210Ω If value is ∞ then check R001. 3) Checking resistance between 'N wire (SKYBLU)' and 'DB01 Neutral side' normal value : 0 - 0.1Ω Neutral side BD01 3.
24296A(1)_2 11/11/05 5:07 PM Page 12-8 Troubleshooting 4. Checking Display PCB LED if Error code is displayed. See error code table if displayed. 5. Checking DC voltage on each point Item Measuring point Normal value Q803 E(-)~D101 Cathode (+) about 1.4 times as much as Power AC Voltage ex) AC220V → 305~310Vdc C803 voltage 14.5V~15.5V Main control 12V CN59 pin 1~pin 3 12V~15V Main control 5V CN59 pin 1~pin 2 4.75V~5.25V DC LINK inverter 15V 6. Checking PFC 6. When Input current is over 3.
24296A(1)_2 11/11/05 5:07 PM Page 12-9 Troubleshooting 12-3-3 Checking Indoor controller 1. MH✳✳✳FPEA✳ /MH✳✳VP2-✳✳ 1. 1. 1. 1. 1. 1. 1) Checking FUSE 1) This control PCB has 2 fuses, F701 and F702. 1) If F702 is blown PCB circuit has some damage and replace PCB. 2) Checking DC voltage ■ Measure voltage between CN32 pin 1 (+12V) and CN32 pin 2 (GND). ■ Normal voltage is between 11.5V and 12.5V.
24296A(1)_2 11/11/05 5:07 PM Page 12-10 Troubleshooting 12-3-6 Checking EEV See 12-5 "Fault Diagnosis of Major Parts". Current EEV step value can monitored with "VIEW MODE" Press K4 key on the outdoor display PCB for several time to change the display to current EEV value. Left 1 digit of the LED is data index and Right 3 digits is the value.
24296A(1)_2 11/11/05 5:07 PM Page 12-11 12-4 PCB Inspection 12-4-1 Cautions for Part Replacement 1. The human body carries much static electricity. Before touching a part for repair, replacement or the similar purpose, be sure to touch a grounded metallic portion by hand to let the static electricity go through the metallic portion to the earth. Especially when handling any micro computer or IC, carefully remove such static electricity before touching them. 2.
24296A(1)_2 11/11/05 5:07 PM Page 12-12 12-5 Fault Diagnosis of Major Parts Preparation : multimeter (AC voltage, DC voltage, Resistance) Part Indoor Temperature sensor Heat exchanger in/out sensor Outdoor Temperature sensor Condenser temperature sensor Diagnosis Measure the resistance between terminals of the sensor connector housing. In case of outdoor unit sensor, "view mode" is used for checking sensor temperature.
24296A(1)_2 11/11/05 5:07 PM Page 12-13 Fault Diagnosis of Major Parts(cont.) Preparation : multimeter (AC voltage, DC voltage, Resistance) Part Diagnosis Measure the resistance between terminals Crank case heater Normal 1.1-1.3KΩ Abnormal ∞, 0Ω...
13-1 Wireless remote controller Infrared signal receiver Ionizer Display Ass'y Fan motor Front panel stepping motor SMPS SSR AC zero voltage detect Comm. Interface (RS485) Indoor Unit control MICOM Comm.
24296A(1)_2 11/11/05 5:07 PM Page 12-15 14. Reference for Installation 14-1 Selecting Area for Installation Select an area for installation that is suitable to customer’s needs. 14-1-1 Indoor Unit 1. Make sure that you install the indoor unit in an area providing good ventilation. It must not be blocked by an obstacle affecting the airflow near the air inlet and the air outlet. 2.
24296A(1)_2 11/11/05 5:07 PM Page 12-16 Reference for Installation 14-1-2 Outdoor Unit 1. Make sure that you install the outdoor unit in area not exposed to the rain or direct sun light.(Install a separate sunblind if exposed to direct sun light.) 2. Make sure that you install the outdoor unit in area allowing the good air moment, not amplifying noise or vibration, especially to avoid disturbing neighbors. (Fix the unit firmly if it is mounted in a high place.) 3.
24296A(1)_2 11/11/05 5:07 PM Page 12-17 14-2 Connecting Up and Purging the Circuit • The air in the indoor unit and in the pipe must be purged. If air remains in the refrigeration pipes, it will affect the compressor, reduce to cooling capacity and could lead to a malfunction. Refrigerant for air purging is not charged in the outdoor unit. Use Vacuum Pump as shown at the right figure. Each unit must be purged in turn. ■ MH040FXEA2/MH052FXEA2/MH14✳✳2X/MH16✳✳2X/MH18✳✳2X/MH19✳✳2X 1.
24296A(1)_2 11/11/05 5:07 PM Page 12-18 Reference for Installation ■ MH068FXEA4/MH080FXEA4/MH30✳✳2X 1. Check the piping connections. 2. Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port (5/8'' Packed valve) as shown at the figure (Value stem: 1/2'' - 20UNF). 3. Open the valve of the low pressure side of manifold gauge counterclockwise. 4. Purge the air from the system using vacuum pump for about 30 minutes.
24296A(1)_2 11/11/05 5:07 PM Page 12-19 14-3 Refrigerant Refill 14-3-1 MH040FXEA2/MH052FXEA2/MH14✳✳2X/MH16✳✳2X/MH18✳✳2X/MH19✳✳2X Refill an air conditioner with refrigerant when refrigerant has been leaked at installing or using. 1) Purge air(for new installation only). 2) Turn the 3-Way valve clockwise to close, connect the pressure gauge (low pressure side) to the service valve, and open the 3-Way valve again.
24296A(1)_2 11/11/05 5:07 PM Page 12-20 Reference for Installation 14-3-2 MH068FXEA4/MH080FXEA4/MH30✳✳2X Refill an air conditioner with refrigerant when refrigerant has been leaked at installing or using. 1) Purge air(for new installation only). 2) Turn the 5/8" service valve clockwise to close, connect the pressure gauge (low pressure side) to the service valve, and open the 5/8" service valve again.
24296A(1)_2 11/11/05 5:07 PM Page 12-21 14-4 Refrigerant Adjustment ■ MH040FXEA2/MH052FXEA2/MH14✳✳2X/MH16✳✳2X/MH18✳✳2X/MH19✳✳2X Class At service At installation Connection Pipe Length Standard < TOTAL ≤ 20m Max. < TOTAL = 40m Air-Purge Method Refrigerant Adjustment Air-Purge Method Refrigerant Quantity Refer to the detailed Connecting up and purging the circuit. (14-3 page) Unnecessary Purge air using a vacuum pump or an additional refrigerant cylinder.
24296A(1)_2 11/11/05 5:07 PM Page 12-22 14-6 "Pump down" Procedure 14-6-1 MH040FXEA2/MH052FXEA2/MH14✳✳2X/MH16✳✳2X/MH18✳✳2X/MH19✳✳2X Pump down will be carried out when an evaporator is replaced or when the unit is relocated in another area. 1) Remove the caps from the 2-Way valve and the 3-Way valve. 2) Turn the 3-Way valve clockwise to close and connect a pressure gauge (low pressure side) to the service valve, and open the 3-Way valve again.
24296A(1)_2 11/11/05 5:07 PM Page 12-23 Reference for Installation 14-6-2 MH068FXEA4/MH080FXEA4/MH30✳✳2X Pump down will be carried out when an evaporator is replaced or when the unit is relocated in another area. 1) Remove the caps from the 3/8" service valve and the 5/8" service valve. 5/8" Service Valve 2) Turn the 5/8" service valve clockwise to close and connect a pressure gauge (low pressure side) to the service valve, and open the 5/8" service valve again.
24296A(1)_2 11/11/05 5:07 PM Page 12-24 15. Reference Information 15-1 Common sense of refrigeration 15-1-1 Air supplier ■ Air supplier? It supplies fresh air to the building or room through procedure of air circulation for fresh environment. ■ Effectiveness of air supplier It diminishes the stress or fatigue and enhances vivid desire through fresh air circulation. Also, filthy air indoor is being cleaned by Air-Filter and it keeps clean and fresh environment and dehumidification.
24296A(1)_2 11/11/05 5:07 PM Page 12-25 15-2 Technical Document (Pressure Graph) 15-2-1 MH052FXEA2(MH040FXEA2/MH14✳✳2X/MH16✳✳2X/MH18✳✳2X/MH19✳✳2X refer to the 100% combination) ■ Cooling(7.5m–Piping) 135% (ex. 035+035) Outdoor Indoor 21 35 43 P_high P_low T_dis 21 21.10 8.60 27 22.00 9.50 32 22.90 21 31.29 27 32 100% (ex. 026+026) T_suc P_high P_low T_dis T_suc 61.40 8.70 19.60 8.00 58.30 7.40 59.50 11.30 21.00 8.78 59.30 9.30 10.65 58.50 14.30 22.20 10.11 58.
24296A(1)_2 11/11/05 5:07 PM Page 12-26 Reference Information 2-1-1 MH18AP1(P2) ■ Cooling(20m–Piping) 135% (ex. 035+035) Outdoor Indoor 21 19.60 8.30 60.23 11.19 18.40 7.33 61.80 9.80 21 27 20.40 9.23 58.90 13.62 19.30 8.50 58.80 12.10 32 21.50 10.26 58.20 15.10 20.30 9.80 57.70 14.20 21 29.10 7.60 85.10 9.20 26.40 7.82 81.60 10.70 27 32.20 8.70 84.00 11.60 27.30 8.99 78.40 13.10 32 33.20 9.90 81.70 14.50 28.40 10.13 76.80 15.
24296A(1)_2 11/11/05 5:07 PM Page 12-27 Reference Information ■ Heating(7.5m–Piping) 135% (ex. 035+035) Outdoor -15 7 24 100% (ex. 026+026) Indoor P_high P_low T_dis T_suc P_high P_low T_dis T_suc 20 19.41 2.82 65.20 -19.10 19.52 2.81 68.20 -18.70 27 23.30 2.83 71.40 -18.90 24.42 2.92 70.20 -17.30 20 30.20 6.60 81.20 -1.40 29.60 6.90 80.48 -0.10 27 31.50 7.00 87.00 0.60 31.80 7.30 83.50 1.60 20 32.20 10.58 79.50 13.11 29.90 11.20 73.10 15.
24296A(1)_2 11/11/05 5:07 PM Page 12-28 Reference Information ■ Heating(20m–Piping) 135% (ex. 035+035) Outdoor -15 7 24 15-5 Indoor P_high P_low T_dis 100% (ex. 026+026) T_suc P_high P_low T_dis T_suc 20 17.59 2.65 63.40 -20.90 18.80 2.72 67.40 -17.50 27 22.50 2.84 70.10 -19.60 23.70 2.95 71.20 -17.00 20 27.20 6.40 80.10 -0.80 28.70 6.80 80.11 -0.40 27 30.20 6.96 85.70 0.40 29.20 7.10 83.40 1.40 20 30.70 11.80 78.50 13.90 29.80 11.10 73.80 15.
24296A(1)_2 11/11/05 5:07 PM Page 12-29 Reference Information 15-2-2 MH068FXEA4/MH080FXEA4 (MH30VP2X/MH30VW2X refer to the 100% combination) ■ Cooling(7.5m–Piping) 170%(ex.026+026+035+052) Outdoor Indoor 21 21.2 8.7 58.4 10.9 21.2 8.2 58.7 8.2 21 27 21.9 10.1 57.5 13.9 21.7 9.4 57.1 11.4 32 22.4 11.3 56.0 16.4 22.2 10.6 55.8 14.5 21 30.3 9.4 78.5 12.8 30.2 9.0 78.5 10.2 27 30.9 10.6 78.7 16.8 30.7 10.0 78.0 14.2 32 31.6 12.0 76.3 19.4 31.7 11.4 76.
24296A(1)_2 11/11/05 5:07 PM Page 12-30 Reference Information 2-1-1 MH18AP1(P2) ■ Cooling(17.5m–Piping) 170%(ex.026+026+035+052) Outdoor Indoor 21 / 15 20.0 8.3 20.0 7.8 21 / 15 27 / 19 20.7 9.7 20.5 9.0 32 / 23 21.2 10.9 21.0 10.2 21 / 15 29.1 9.0 29.0 8.6 27 / 19 29.7 10.2 29.5 9.6 32 / 23 30.4 11.6 30.5 11.0 35 / 24 43 / 26 15-7 P_high P_low 100%(ex.026+026+052) P_high P_low 21 / 15 34.9 9.4 35.0 9.0 27 / 19 35.8 10.7 35.6 10.2 32 / 23 36.4 12.1 36.
24296A(1)_2 11/11/05 5:07 PM Page 12-31 Reference Information ■ Heating(7.5m–Piping) 170%(ex.026+026+035+052) Outdoor -10 7 24 100%(ex.026+026+052) Indoor P_high P_low T_dis T_suc P_high P_low T_dis T_suc 20 18.0 6.4 60.1 -18.9 18.8 6.7 59.8 -17.4 27 20.8 7.0 66.3 -17.1 21.7 7.1 67.0 -15.7 20 21.2 10.6 57.9 -1.8 23.2 10.6 64.9 -0.2 27 24.4 11.0 63.0 -0.9 26.3 11.0 69.1 0.5 20 22.5 12.9 60.8 16.4 26.4 13.4 71.9 17.3 27 25.5 13.8 64.3 16.8 29.
24296A(1)_2 11/11/05 5:07 PM Page 12-32 Reference Information ■ Heating(17.5m–Piping) 170%(ex.026+026+035+052) Outdoor -10 7/6 24 / 18 15-9 Indoor P_high P_low 100%(ex.026+026+052) P_high P_low 20 / 15 16.8 6.0 17.6 6.3 27 / 15 19.6 6.6 20.5 6.7 20 / 15 20.0 10.2 22.0 10.2 27 / 15 23.2 10.6 25.1 10.6 20 / 15 21.3 12.5 25.2 13.0 27 / 15 24.3 13.4 28.3 13.
24296A(1)_2 11/11/05 5:07 PM Page 12-33 MEMO Samsung Electronics 15-10
24296A(1)_2 11/11/05 5:07 PM Page 12-34 MEMO 15-11 Samsung Electronics
24296A(1)_co 11/12/05 10:04 AM Page 2 ELECTRONICS This Service Manual is a property of Samsung Electronics Co., Ltd. Any unauthorized use of Manual can be punished under applicable International and/or domestic law. © Samsung Electronics Co., Ltd. Nov. 2005. Printed in Korea. Code No.