Installation manual
AA
20
Setting an indoor unit address and installation option
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power
supply in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air
conditioner.
- The default setting of an indoor unit installation option is “02000-100000-
200000-300000”.
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is
more than one indoor unit.
4. Set the indoor unit option by wireless remote controller.
Setting an indoor unit installation option (suitable for the condition of each installation location)
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 RESERVED
Exterior
temperature sensor
Central control RESERVED
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 Drain pump RESERVED RESERVED
RESERVED
Master / Slave
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 External control
External control
output
S-Plasma ion Buzzer
Number of hours
using lter
SEG19 SEG20 SEG21
3
Individual control of
a remote controller
Heating setting
compensation
▶ 1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to 'USE + 3minute delay' even if the drain pump is set to 0.
▶ 1 WAY/2WAY/4WAY,DUCT MODEL : Number of hours using lter(SEG18) will be set to '1000hour' even if the SEG18 is set to
exept for 2 or 6.
▶
If you input a number other than 0~4 of the individual control of the indoor unit(SEG20), the indoor is set as "indoor 1".
▶ 4WAY MODEL : Even when the value of Heating setting compensation(SEG21) is set to '0', it wil be recognized as '5°C'.
Indoor Unit
1(L)
F2
F1
2(N)