Installation manual

13
ENGLISH
If a concentrated drain pipe is installed, refer to the gure below.
Concentrated drain pipe
100mm or
more
1/100 or
more slope
Air ventilation
Check that the indoor unit is level with the ceiling by using the leveler.
Air ventilation
Ceiling
Install air ventilation to drain condensate water smoothly.
Do not give the hose and upward gradient after the
connection port. This will cause water to ow backwards
when the unit is stopped, resulting in water leaks.
Under gradient
Ceiling
Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as close
to the unit as possible.
Support pieces
1~1.5m
Ceiling
1/100 or more
If it is necessary to increase the height of the drainpipe,
install the drainpipe straightly within 300 mm from the
drain hose port. If it is raised higher than 550 mm, there
can be water leaks.
300mm or less
Ceiling
20mm or more
Drain hose
Band joint
1/100 or more
550mm or less
Install horizontally
Max. allowable bending angle
Max. allowable axis gap
Be horizontal
Indoor
Unit
Flexible hose
Max. 20mm
Indoor
Unit
Max. 30˚
Indoor
Unit