Automation System TROVIS 5100 District Heating Controller TROVIS 5179 Mounting and Operating Instructions EB 5179 EN ® Electronics from SAMSON Firmware version 1.
Disclaimer of liability Disclaimer of liability We are constantly developing our products and therefore, reserve the right to change the product or the information contained in this document at any time without notice. We do not assume any liability for the accuracy or completeness of these mounting and operating instructions. Moreover, we do not guarantee that the buyer can use the product for an intended purpose.
Contents Contents 1 1.1 1.1.1 1.1.2 1.2 1.3 1.4 1.5 1.6 1.6.1 1.6.2 1.6.3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Operating keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Operating switches . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Display. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents 5.8 5.9 5.10 5.11 5.12 5.13 5.14 5.15 Remote operation . . . . . . . . . . Optimization with room sensor. . . . Flash adaptation . . . . . . . . . . Adaptation . . . . . . . . . . . . . Room temperature-dependent control Pump management . . . . . . . . . Releasing the heating circuit . . . . . Position feedback in pre-control circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents 8.6 8.6.1 8.6.2 Error alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Sending text message in case of a fault alarm . . . . . . . . . . . . . 73 Sending fax in case of a fault alarm . . . . . . . . . . . . . . . . . . 73 9 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 9.1 RS-232-C system bus interface . . . . . . . . . . . . . . . . . . . . 76 9.2 RS-232/RS-485 system bus interface (for four-wire bus) in combination with cable converters . . . . . .
Operation 1 Operation The controller is ready for use with the temperatures and operating schedules preset by the manufacturer. On start-up, the current time and date need to be set at the controller (–> section 1.5). 1.1 Operating elements The operating controls are located in the front panel of the controller and protected by a Plexiglas door. 1.1.
Operation 1.1.2 Operating switches Heating circuit mode selector switch Automatic mode with switchover between rated operation and reduced operation Rated operation Reduced operation Manual operation: Control valve opens - stationary - closes (for on/off control: + ON, 0 OFF) DHW circuit mode selector switch The operating mode icon stickers are included in the scope of delivery and can be stuck on the front above the mode selector switch for control circuit 2 (middle), if required.
Operation The assignment of the control circuits to the mode selector switches depends on the system code number (Anl): System (Anl) Mode selector switch Top Middle Bottom 1 Heating circuit 1 Heating circuit 2 Pre-control circuit 2 Heating circuit 1 DHW heating Heating circuit 2 3 Heating circuit 1 Heating circuit 2 Heating circuit 3/Pre-control circuit 4 Heating circuit 1 DHW heating Pre-control circuit 5 Heating circuit 1 DHW heating Heating circuit 2/Pre-control circuit 6 Heatin
Operation 1.3 Display During operation, the display indicates the current time as well as information about the operation of the controller. The times-of-use are represented by black squares below the row of numbers at the top of the display. Icons indicate the operating status of the controller. The controller status can be displayed in the operating level (InF level) (–> section 1.4).
Operation 1.4 Displaying data Measured values, set points, times-of-use, public holidays and vacation periods can be retrieved and displayed in the InF1 to InF9 information levels. The various displays are listed in section 11.4.
Operation 1.5 Setting the controller time The current time and date need to be set immediately after start-up and after a power failure lasting longer than 24 hours. Proceed as follows: 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Switch to configuration and parameter level. Display: PA1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Select PA5 parameter level. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Open PA5 parameter level.
Operation 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Confirm date. Display: Year. Activate editing mode for the controller year. Change year setting. Confirm year. Exit PA5 parameter level. Return to the operating level. Note! The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
Operation 1.6 Setting the times-of-use Two times-of-use can be set for each day of the week. If just one time-of-use is required, the start and stop times of the second time-of-use must be programmed to identical times. The time schedules for the three heating circuits, DHW heating and the circulation pump can be read over Modbus. Pump circuits are treated as mixer circuits.
Operation 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Activate editing mode for times-of-use. Display: 1–7 Select period/day for which the times-of-use are to be valid: 1–7 = every day, 1 = Monday, 2 = Tuesday, ..., 7 = Sunday 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Activate editing mode for period/day. blinks Display shows: START; Edit start time (steps of 30 minutes). 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Confirm start time.
Operation 1.6.1 Copying the times-of-use The times-of-use of heating circuit 1 (2) can be copied and used for heating circuit 2 (3). Copy function Parameter level Icon HK1 –> HK2 HK2 –> HK3 PA1 PA2 COPY2 COPY3 Proceed as follows: Switch to configuration and parameter level. Display: PA1 Select parameter level. Open parameter level. Select “COPY_“ data point. Open copy program. The display blinks. Copy the times-of-use. Select End on the display. Exit the parameter level.
Operation 1.6.2 Entering public holidays On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public holidays may be entered. Parameters WE Level / Range of values Public holidays f. heating circuit 1 – PA1 / 01.01 to 31.12 Public holidays f. heating circuit 2 – PA2 / 01.01 to 31.12 Public holidays f. heating circuit 3 – PA3 / 01.01 to 31.
Operation Note! Public holidays that are not assigned to a specific date should be deleted by the end of the year so that they are not carried on into the following year. Deleting a public holiday: Select the holiday you wish to delete in the datapoint for public holidays. Confirm selection. Select – – – – . Delete the public holiday. Note! The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
Operation 1.6.3 Entering vacation periods During vacation periods, the controller constantly remains in the reduced operating mode. The system is monitored for frost. A maximum of 10 vacation periods can be entered. Parameters WE Level / Range of values Vacation period for heating circuit 1 – PA1 / 01.01 to 31.12 Vacation period for heating circuit 2 – PA2 / 01.01 to 31.12 Vacation period for heating circuit 3 – PA3 / 01.01 to 31.
Operation Return to the operating level. Note! Vacation periods that are not assigned to a specific date should be deleted by the end of the year so that they are not carried on into the following year. Deleting vacation periods: Select the vacation period you wish to delete in the datapoint for vacation periods. Confirm selection. Select – – – – . Delete vacation period. Note! The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
Start-up 2 Start-up 2.1 Setting the system code number 10 different hydraulic schematics are available. Each system configuration is represented by a system code number. The different schematics are dealt with in section 4. Available controller functions are described in sections 5, 6 and 7. Changing the system code number resets previously adjusted function blocks to their default settings (WE). The system code number is set in the configuration level.
Start-up 2.2 Activating and deactivating functions A function is activated or deactivated in the associated function block. The numbers 0 to 24 in the top row of the display represent the respective function block numbers. When a configuration level is opened, the activated function blocks are indicated by a black square on the right-hand side below the function block number. For more details on function blocks, refer to section 12.1.
Start-up Confirm settings. If the function block is not closed, further function block parameters can be adjusted. Proceed as follows: Make the desired changes and confirm. If applicable, the next function block parameter is displayed. Confirm all parameters to exit the opened function block. To adjust additional function blocks, repeat the steps in the fields highlighted in gray. Exit configuration level. Return to the operating level.
Start-up 2.3 Changing parameters Depending on the set system code number and the activated functions, not all parameters listed in the parameter list in the Appendix (–> section 12.2) might be available.
Start-up 2.3.1 Enter key number Some functions are protected against unintentional or unauthorized access. These functions can only be activated or deactivated after the valid key number has been entered. The valid key number for initial start-up can be found on page 137. To avoid unauthorized use of the key number, remove the page or make the key number unreadable. Proceed as follows: 0 0 0 0 blinks on the display. Set valid key number. Confirm key number.
Start-up erence temperature) measured directly at the point of measurement. Sensor calibration is to be activated in Co6 via function block Fb23. Proceed as follows: Switch to configuration and parameter level. Display shows: PA1 Select Co6 level. Open Co6 level. Display shows: Fb00 Select function block Fb23. Confirm selection. Display shows: 0 0 0 0 Enter and confirm key number. Fb23 blinks on the display. Activate editing mode for function block. Activate function block. Start sensor calibration.
Start-up Note! The sensor values adjusted are not reset by the Loading default settings function. 2.6 Resetting to default values All parameters and function blocks from any parameter level can be reset to their default settings (WE). Proceed as follows: Reset to default settings. Function blocks and parameters are reset to their default settings (WE). Note! When the key number is active, the function blocks protected by the key number are also reset to their default settings.
Manual operation 3 Manual operation Switch to manual mode to configure all outputs (see wiring diagram in section 11). Proceed as follows: Position all selector mode switches to +, 0 or –. Select PU pump manual level. Open pump manual level. Select pump PU1 to PU5: PU1: BA11 PU2: BA12 PU3: BA13 PU4: BA14 PU5: BA15 Confirm pump selection. The display blinks. Activate output: Deactivate output: Confirm setting. The modified values remain active as long as the controller is in manual mode.
Systems 4 Systems There are 10 hydraulic schematics. System code number (Anl) 1 Heating Outdoor temperature compensated flow temperature control with variable return flow temperature limitation 2 3 4 5 7 8 9 10 Number of heating circuits 2 2 3 1 2 3 1 2 2 2 No. of heating circuits w.
Systems System Anl 1 RKFW RüFprim VFsek RKHK1 UP1 RüF1 VF1 RKHK2 VF2 RüF2 RF1 UP2 RF2 AF1 AF2 BE BA AE RK Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON Co2 -> Fb00 = OFF (without RF2) Co2 -> Fb01 = OFF (without RüF2) Co2 -> Fb02 = OFF (without AF2) Co5 -> Fb00 = ON (with VFsek) Co5 -> Fb01 = ON (with RüFprim) (with AF1) EB 5179 EN 29
Systems System Anl 2 RKFW RüFprim VFsek RKHK1 UP1 RüF1 VF1 RKHK2 VF2 RüF2 RF1 UP2 RF2 BE BA AE RK Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON Co2 -> Fb00 = OFF (without RF2) Co2 -> Fb01 = OFF (without RüF2) Co2 -> Fb02 = OFF (without AF2) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 -> Fb03 = ON (with VFS, with VFT) Co5 -> Fb00 = ON (with VFsek) Co5 -> Fb01 = ON (with RüFprim) 30 EB 5179 EN (with AF1) A
Systems System Anl 3 RKFW RüFprim VFsek RKHK1 UP1 RüF1 VF1 RKHK2 VF2 RüF2 RF2 UP3 RF1 UP2 VF3 AF1 AF2 BE BA AE RK Default setting * Co1 -> Fb00 = OFF (without RF1)* Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON Co2 -> Fb00 = OFF (without RF2)* Co2 -> Fb01 = OFF (without RüF2) Co2 -> Fb02 = OFF (without AF2) Co5 -> Fb00 = ON (with VFsek) Co5 -> Fb01 = ON (with RüFprim) (with AF1) Only for optimization and temperature reading EB 5179 EN 31
Systems System Anl 4 WW KW RKFW RüFprim VFsek RKHK1 UP1 RüF1 VF1 RF1 RKTW VFT RüFTW TLP VFS SLP SF2 ZP AF1 SF1 BE BA AE RK Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 -> Fb02 = OFF (without RüFTW) Co4 -> Fb03 = ON (with VFS, with VFT) Co5 -> Fb00 = ON (with VFsek) Co5 -> Fb01 = ON (with RüFprim) Set Co4 -> Fb11 = ON if the instrumentation represent
Systems System Anl 5 WW KW RKFW RüFprim RüF1 VFsek RKHK1 UP2 UP1 VF1 RF1 VF2 RKTW VFT RüFTW TLP VFS SLP SF2 AF1 ZP SF1 BE BA AE RK Default setting * Co1 -> Fb00 = OFF (without RF1)* Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 -> Fb02 = OFF (without RüFTW) Co4 -> Fb03 = ON (with VFS, with VFT) Co5 -> Fb00 = ON (with VFsek) Co5 -> Fb01 = ON (with RüFprim) Only for optimization and temperature read
Systems System Anl 6 VFsek RKHK1 RüF1 UP2 VF2 RüF2 UP3 VF3 RüF3 UP1 VF1 RF1 RKHK2 RF2 RKHK3 RF3 BE BA AE RK Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON Co2 -> Fb00 = OFF (without RF2) Co2 -> Fb01 = OFF (without RüF2) Co2 -> Fb02 = OFF (without AF2) Co3 -> Fb00 = OFF (without RF3) Co3 -> Fb01 = OFF (without RüF3) Co3 -> Fb02 = OFF (without AF3) Co5 -> Fb00 = ON 34 EB 5179 EN (with AF1) (with VFsek) AF1 AF2 AF3
Systems System Anl 7 WW KW RKTW RKFW RüFprim VFsek RKHK1 RüF1 UP1 VF1 RF1 VFT TLP RüFTW VFS SLP SF1 SF2 ZP AF1 BE BA AE RK Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 -> Fb02 = OFF (without RüFTW) Co4 -> Fb03 = ON (with VFS, with VFT) Co5 -> Fb00 = ON (with VFsek) Co5 -> Fb01 = ON (with RüFprim) Set Co4 -> Fb11 = ON if the instrumentation represented
Systems System Anl 8 WW KW RKTW RKFW RüFprim VFsek RKHK1 RüF1 UP2 VFT UP1 VF1 RF1 VF2 TLP RüFTW VFS SLP SF1 SF2 ZP AF1 BE BA AE RK Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 -> Fb02 = OFF (without RüFTW) Co4 -> Fb03 = ON (with VFS, with VFT) Co5 -> Fb00 = ON (with VFsek) Co5 -> Fb01 = ON (with RüFprim) Set Co4 -> Fb11 = ON if the instrumentation repre
Systems System Anl 9 WW KW RKTW VFsek RKHK1 RüF1 UP2 RüF2 VFT UP1 VF1 RF1 RKHK2 VF2 RF2 TLP RüFTW VFS SLP SF2 SF1 ZP AF1 AF2 BE BA AE RK Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON Co2 -> Fb00 = OFF (without RF2) Co2 -> Fb01 = OFF (without RüF2) Co2 -> Fb02 = OFF (without AF2) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 -> Fb02 = OFF (without RüFTW) Co4 -> Fb03 = ON (with VFS, with VFT) Co5 -> Fb00 = ON (w
Systems System Anl 10 WW KW RKFW RüFprim VFsek RKHK1 RüF1 UP2 VF2 RüF2 RKTW RüFTW UP1 VF1 RF1 RKHK2 TLP RF2 VFT VFS SLP BE BA AE RK Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON Co2 -> Fb00 = OFF (without RF2) Co2 -> Fb01 = OFF (without RüF2) Co2 -> Fb02 = OFF (without AF2) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 -> Fb02 = OFF (without RüFTW) Co4 -> Fb03 = ON (with VFS, with VFT) Co5 -> Fb00 = ON (with V
Functions of the heating circuit 5 Functions of the heating circuit Which controller functions are available depends on the selected system code number (Anl). 5.1 Functioning principle The heating circuit with the highest flow set point has priority. This principle applies to all heating circuits with mixing valves. In systems Anl 3, 5 and 8, the pump circuit has priority. The flow set point of the heating circuit with priority is controlled by the valve in the pre-control circuit.
Functions of the heating circuit If just one outdoor sensor should be connected, connect it to AF1. This outdoor temperature is then used also for HK2 and HK3. 5.2.1 Gradient characteristic Basically, the following rule applies: a decrease in the outdoor temperature causes the flow temperature to increase. By varying the Gradient and Level parameters, you can adapt the characteristic to your individual requirements.
Functions of the heating circuit The Max. flow temperature and Min. flow temperature parameters mark the upper and lower limits of the flow temperature. tVL [˚C] 100 P1 to 4 Points 1 to 4 tVLmax 90 tVL 80 P1 70 60 P2 50 Outdoor temperature ...min Minimum tVL ...max Maximum tVL 4-point characteristic Reduced 4-point characteristic P3 40 P4 30 Flow temperature tA tVLmin 20 tA 10 20 15 10 5 0 –5 –10 –15 –20 [˚C] Fig.
Functions of the heating circuit Note! The 4-point characteristic function can only be activated when the Adaptation function is not active (Co1, 2, 3 -> Fb07 = OFF). 5.3 Fixed set point control During the times-of-use, the flow temperature can be controlled according to a fixed set point. Outside the times-of-use, this set point is reduced by the Set-back difference. Both Minimum flow temperature and Maximum flow temperature parameters are set to identical values.
Functions of the heating circuit Function WE Configuration Differential temperature control using variable weighting factors OFF Co1, 2, 3 -> Fb18 = ON 0.5 200 s Proportional gain factor KP /0.1 to 999 Reset time TN / 1 to 999 s 20 °C Intended temp. difference / 0 to 40 °C 90 % Analog value max. / 0 to 100 % 30 % Analog value min. / 0 to 100 % WE Parameter level / Range of values Parameters Max. return flow temperature* 65 °C PA1, 2, 3 / 20 to 90 °C Min.
Functions of the heating circuit When the outdoor temperature falls below this value (less 0.5 °C hysteresis), heating operation is restarted immediately. With the default settings, this means that, at night, the system is switched off at an outdoor temperature of 10 °C to save energy. Nevertheless, remember that the system requires some time in the morning to heat up the building (–> Outdoor temperature-dependent advance heating, section 5.7).
Functions of the heating circuit Note! Summer mode only becomes effective when the controller is in automatic mode ( 5.6 ). Delayed outdoor temperature adaptation The calculated outdoor temperature is used to determine the flow temperature set point. The heat response is delayed when the outdoor temperature either decreases, or increases and decreases.
Functions of the heating circuit 5.8 Remote operation Apart from measuring the room temperature, the Type 5244 Room Sensor (PTC sensor) and Type 5257-5 Room Sensor (Pt 1000 sensor) offer the following options to influence the control process: 4 Selection of the operating mode: Automatic mode · Day mode · Night mode 4 Set point correction: during rated operation, the room temperature set point can be increased or reduced by up to 5 °C using a continuously adjustable rotary knob.
Functions of the DHW circuit There are two types of optimization depending on the activation conditions: 4 Outdoor temperature-dependent advance heating, room temperature-dependent deacti- vation The controller activates the heating depending on the outdoor temperature before the time-of-use starts in normal operation. The Advance heating time is based on an outdoor temperature of –12 °C. The advance heating time is shorter when the outdoor temperature is higher (see section 5.7).
Functions of the DHW circuit Parameters WE Parameter level / Range of values Day set point 20 °C PA1, 2, 3 / 10 to 90 °C Night set point 17 °C PA1, 2, 3 / 10 to 90 °C Sustained temperature 10 °C PA1, 2, 3 / 10 to 90 °C 5.10 Flash adaptation Direct reactions to deviations in room temperature can be achieved using the function block setting: Co1, 2, 3 -> Fb08 = ON. Flash adaptation counteracts room temperature deviations by increasing or decreasing the flow temperature by up to 30 °C.
Appendix Parameter WE Parameter level / Range of values Day set point 20 °C PA1, 2, 3 / 10 to 90 °C 5.12 Room temperature-dependent control In systems Anl 6 and 9, the Room temperature-dependent control function can be separately activated for each heating circuit. The Room sensor function must be activated for this function. Flow and return flow sensors only serve to display the temperature and can therefore be deactivated.
Appendix Functions WE Configuration Room sensor RF1, 2, 3 OFF Co1, 2, 3 -> Fb00 = ON Room temperature dependent control OFF Co1, 2, 3 -> Fb06 = ON Parameter optimization OFF Co1, 2, 3 -> Fb16 Flow sensor OFF when room temperature dependent control is used OFF Co1, 2, 3 -> Fb17 5.13 Pump management To control the circulation pumps for the heating circuits (UP1 and UP2), reed relay outputs can be used instead of the relay output.
Appendix 5.14 Releasing the heating circuit The release of the heating circuit in automatic mode is a default setting after the time schedule has been programmed. In addition, it is possible to release the heating circuit over the corresponding potentiometer inputs. When no signal exists at these inputs and the slide switch of the heating circuit is positioned to automatic mode ( ), the heating circuit is in stand-by mode (i.e. just the frost protection is active).
Functions of the DHW circuit 6 Functions of the DHW circuit 6.1 DHW heating in the storage tank charging system SLP TLP VFT VFS TW SF1 ZP SF2 KW TLP Heat exchanger charging pump VFS/VFT Flow sensors SLP Storage tank charging pump SF1 Storage sensor 1 SF2 Storage sensor 2 ZP Circulation pump TW DHW KW Cold water Fig.
System-wide functions The Mixing valve always active function allows the heat exchanger to maintain the charging temperature using the mixing valve. The heat exchanger charging pump remains switched on and the return flow temperature is not limited outside the times-of-use.
Appendix Parameters WE Parameter level / Range of values DHW demand ON 40 °C PA4 / 20 to 90 °C DHW demand OFF 45 °C PA4 / 20 to 90 °C Charging temperature 55 °C PA4 / 20 to 90 °C Heat exchanger charging pump deactivation limit 50 °C PA4 / 20 to 90 °C Storage tank charging pump deactivation limit 50 °C PA4 / 20 to 90 °C Maximum charging temperature 120 °C PA4 / 20 to 120 °C 6.2 DHW heating in the storage tank system SLP VL SLP VFS SF1 RL TW ZP Zirk.
Appendix When there is no heating operation or when the flow temperature in the system is lower, the storage tank charging pump is switched on immediately. If a storage tank thermostat is used, the storage tank charging pump is switched on when the temperature T = Charging temperature – 5 °C is reached at sensor VFS. Note! The charging temperature VFS is controlled in system Anl 2 by the primary valve.
Appendix Parameters WE Parameter level / Range of values DHW demand ON 40 °C PA4 / 20 to 90 °C Hysteresis 5 °C PA4 / 0 to 30 °C Charging temperature 55 °C PA4 / 20 to 90 °C Storage tank charging pump deactivation limit 50 °C PA4 / 20 to 90 °C 6.3 Priority operation In many district heating systems with primary DHW heating, the allotted amount of water is only intended to supply the heating system.
Appendix 6.3.2 Set-back operation In all systems with DHW heating and at least one heating circuit with control valve, DHW heating can be given priority by applying set-back operation. The charging temperature can be monitored with the setting Co4 -> Fb06 = OFF and Activate priority in case of deviation > 0.
Appendix Thermal disinfection for preventing legionella infection causes 4 high return flow temperatures during the disinfection cycle (return flow temperature limitation suspended), 4 high storage temperatures after thermal disinfection has been concluded, 4 lime scale (possibly), which can have a negative effect on heat exchanger performance. Note! This function is not available when a storage tank thermostat is used.
System-wide functions 7 System-wide functions 7.1 Automatic summer time/winter time changeover The clock is automatically adjusted on the last Sunday in March at 2.00h and on the last Sunday in October at 3.00h. Function WE Configuration Summer time/winter time changeover ON Co5 -> Fb05 = ON 7.2 Frost protection The Frost protection function does not work in manual mode. The heating system is automatically monitored for frost protection.
System-wide functions Function WE Configuration Return flow sensor RüF1, 2, 3 OFF Co1, 2, 3 -> Fb01 = ON 1.0 Limitation factor / 0 to 25.5 Parameters WE Parameter level / Range of values Max. return flow temperature 65 °C PA1, 2, 3 / 20 to 90 °C Min. return flow temperature 20 °C PA1, 2, 3 / 20 to 90 °C In systems with a DHW in a secondary circuit, the control during DHW heating uses the Return flow limitation temperature for DHW parameter (systems Anl 2, 4, 5 and 10).
System-wide functions 7.5 Condensate accumulation control Activate the Condensate accumulation control function to start up condensate accumulation plants, in particular to avoid problematic excess temperatures. The controller response to set point deviations which cause the primary valve to open is attenuated. The controller response to set point deviations which cause the control valve to close remains unaffected.
System-wide functions 7.7 Three-step control The flow temperature can be controlled using a PI algorithm. The valve reacts to pulses that the controller emits when a system deviation occurs. The length of the first pulse, in particular, depends on the extent of the system deviation and the selected Proportional gain KP (the pulse length increases as KP increases). The pulse and pause lengths change continuously until the system deviation has been eliminated.
System-wide functions 7.8 On/off control The flow temperature can be controlled by an on/off signal. The controlled valve is opened when the flow temperature falls below the set point by T = 0.5 x Hysteresis. When the flow temperature exceeds the set point by T = 0.5 x Hysteresis, the control valve is closed. The greater the Hysteresis selected, the lower the switching frequency.
System-wide functions Functions WE Configuration Continuous-action control for heating circuit OFF Co1, 2, 3 -> Fb14 = ON 0.5 200 s 0s KP (gain) / 0.1 to 50.0 TN (reset time) / 1 to 999 s TV (derivative-action time) / 0 to 999 s OFF Co4 -> Fb14 = ON 0.5 200 s 0s KP (gain) / 0.1 to 50.0 TN (reset time) / 1 to 999 s TV (derivative-action time) / 0 to 999 s OFF Co5 -> Fb19 = ON 0.5 200 s 0s KP (gain) / 0.1 to 50.
System-wide functions A heat meter with pulse output connected at input Vmax (terminal 30) can be used either to limit the system flow rate (parameter code: U) or the system capacity (parameter code: P). The pulse weighting of the heat meter (WMZ) and the type of limitation selected must be entered. The displayed value corresponds to the unit l/pulse or kWh/pulse. When the pulse rate reaches the current maximum limit, the flow set point of the control circuit RK1 is reduced.
System-wide functions Settings for flow rate limitation Functions WE Configuration Limitation of heat meter (WMZ) OFF Co5 -> Fb08 = OFF Pulse input for flow rate or capacity limitation OFF Co5 -> Fb09 = ON, select: U Parameters CONST: Limitation constant 4-Pt: Limitation acc. to 4-point characteristic 10 Pulse weighting / 0.1 to 10 WE Parameter level / Range of values 9 m3/h PA5 / 0.01 to 99.9 m3/h Maximum flow rate of the DHW heating 9 m3/h PA5 / 0.01 to 99.
Operational faults 8 Operational faults Malfunctions or faults are indicated by the icon blinking on the display. Error immediately appears on the display. Press the enter key to open the error level. It may be possible to view several error alarms by pressing the enter key. As long as an error alarm is present, the error level appears in the display loop, even though it has not been opened by pressing the enter key.
Operational faults 4 Room sensor RF: Upon failure of the room sensor, the controller functions according to the 4 settings for operation without a room sensor. For example, optimized operation is switched over to reduced operation. Adaptation operation is interrupted. The last determined heating characteristic is not changed anymore. Storage tank sensors SF1 and SF2: Upon failure of one of these sensors, the storage tank is not charged anymore.
Operational faults Sensor breakage status: Number = Bit no. in HR 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Flow sensor VF1 Return flow sensor RüF1 Outdoor sensor AF1 Room sensor RF1 Flow sensor VF2 Return flow sensor RüF2 Outdoor sensor AF2 Room sensor RF2 Flow sensor VF3 Return flow sensor RüF3 Outdoor sensor AF3 Room sensor RF3 Pot. input FG1 (not monitored) Pot. input FG2 (not monitored) Pot.
Operational faults 8.3 Temperature monitoring The flow temperature and the room temperature can be monitored for any deviations. This function is activated in Co5 -> Fb20. The controller issues an alarm when: the flow temperature deviates from its set point by more than 10 °C for more than 30 minutes the room temperature falls below its set point by 2 °C for more than 30 minutes the return flow temperature limitation is active for more than 30 minutes.
Operational faults 8.4 Monitoring the input terminals for limit violations The controller provides the option to apply limits (in % of measuring range) to two selected inputs (temperature sensor or analog inputs) and to issue an alert to a higher-level control system by writing in the error status register.
Operational faults 8.5 Error status register The HR 60 and HR 61 error status registers (holding register - 16-bit) are used to indicate controller or system errors. HR 60 contains general alarms, whereas special faults are entered in HR 61. In modem mode (Co9 -> Fb01 = ON), the change in state of HR 60 or HR 61 causes the controller to dial the control system.
Operational faults Example of a transfer to the control system: The error status register is transferred as a word in a holding register (HR) whose value is calculated as follows: = ([D0] x <1> + [D1] x <2> ) +...+ ([D11] x <2048>) Holding register 61 (A set bit is indicated by Number = Bit no.
Operational faults 8.6.1 Sending text message in case of a fault alarm Currently, text messages can only be sent to the German D1 network. The corresponding access numbers into the D1 network as well as the mobile phone number of the recipient must be set in the PA9 level: 4 D1 access number: 0171 252 10 02 4 (add 0 in front when dialing from a private branch exchange) Digits 0 to 9, P = pause, - = end, max. 22 characters The access number is assigned by Deutsche Telekom and may alter.
Operational faults 4 Station ID: Digits 0 to 9, P = pause, - = end, max.
Communication 9 Communication Using the serial system bus interface, the TROVIS 5179 District Heating Controller can communicate with a building control system. In combination with a suitable software for process visualization and communication, a complete control system can be implemented. The following communication settings are possible: – Operation with a dial-up modem at the RS-232-C system bus interface Basically, communication is only established automatically when errors occur.
Communication GND TD DTR DCD RD RTS Fig. 8 · Pin assignment of RJ-12 system bus interface 9.1 RS-232-C system bus interface The system bus connection is located at the back of the controller housing (RJ-12 jack). In this case, the controller can be connected either directly to the serial interface of a PC (point-to-point connection) or to a (dial-up) modem. A dial-up modem is required if the controller is to be connected to the telecommunications network.
Communication Functions WE Configuration Modem OFF Co9 -> Fb01 = ON Modem dialing procedure OFF Co9 -> Fb02 Lock dial-up OFF Co9 -> Fb03 Dial-up also upon corrected fault OFF Co8 -> Fb00 Parameters* WE Parameter level / Range of values Station address (ST.
Communication Functions WE Configuration Modbus ON Co9 -> Fb00 = ON Modem OFF Co9 -> Fb01 = OFF Modbus 16-bit addressing OFF Co9 -> Fb04 Parameters* WE Parameter level / Range of values Station address (ST.-NR) 255 PA9 / 1 to 247 (1 to 999 with Co9 -> Fb04 = ON) Baud rate (BAUD) 9600 PA9 / 300 to 19200 * –> Section 9.3 (“Description of communication parameters to be adjusted“) 9.3 Description of communication parameters to be adjusted Station address (ST.
Communication Modem timeout (t) When the controller connects to the GLT but without addressing a Modbus data point, the connection is closed after the time specified for Modem time-out has elapsed. If the error status register has not been read during the GLT connection, the controller dials up to the GLT again after the Modem dialing pause (P) has elapsed.
Communication Note! The initialization settings described here are indispensable for operation on a dial-up modem. Nevertheless, it cannot be guaranteed that data are transferred after the initialization settings have been adjusted. Due to the broad range of modems available on the market and the different commands, refer to the operating manual of the modem for further details. 9.
Communication 4 Flow temperature (b, °C) 4 Return flow temperature (b, °C) 4 Meter identification number (L without enter key, H with enter key) 4 Meter bus address (sent by WMZ) (A, –) Blinking values in combination with black squares in the top row of the display (fault status of the associated meter –> TV-SK 6311) indicate different faults.
Communication 4 A system with simultaneous room heating and DHW heating requires maximum energy. 4 A system with a fully charged storage tank which performs only room heating requires less energy. 4 A system which suspends room heating during DHW heating requires less energy. As a result, three different maximum limit values can be specified: 4 Max. limit value to determine the absolute upper limit 4 Max. limit value for heating for exclusive operation of the room heating 4 Max.
Communication Outdoor temperature Point 1 Point 2 Point 3 Point 4 –15 °C – 5 °C 5 °C 15 °C PA5 /–30 to 90 °C Maximum limit of flow rate, points 1 to 4 9 m3/h PA5 / 0.01 to 99.9 m3/h 9.5 LON communication Note! The following section only applies to devices with LON interface and CO7 -> Fb00 = ON. On connecting LONMARK devices, CO7 -> Fb00 = OFF needs to be configured. Each controller is assigned a LON station address, which needs to be set in the PA7 parameter level.
Communication 9.6 Requesting/processing an external demand Requesting an external demand The flow temperature set points can be passed on over the LON network in complex heating systems. The external flow set point is compared with the controller’s own flow set point. The higher of the two flow set points is passed on.
Communication Note! In controllers with a firmware version lower than 1.05, the master controller receives the Subnet 1 address and node address 1 and is the decisive controller in LON network terms. It is the only controller that can send alarms over a modem. 9.7 Sending outdoor temperatures and controller time Two outdoor temperatures and the controller time can be sent over the LON bus which are taken on by all the other controllers. Any controller in the system can send these data.
Communication EB 5179 EN 87
Installation 10 Installation The controller consists of the housing with the electronics and the back panel with the terminals. It is suitable for panel, wall, and top hat rail mounting (Fig. 9). Panel mounting 1. 2. 3. 4. 5. Remove both screws (1). Pull apart the controller housing and back panel. Make a cut-out of 138 x 91 mm (width x height) in the control panel. Insert the controller housing through the panel cut-out. Insert one mounting clamp (2) each at the top and bottom or at the sides.
Installation Panel mounting 2 Back of the controller 1 2 Controller housing Top hat rail mounting 5 15 62 Wall mounting 57 42 4 5 3 Fig.
11 Electrical connection ! Caution! For electrical installation, you are required to observe the relevant electrotechnical regulations of the country of use as well as the regulations of the local power suppliers. Make sure all electrical work is performed by trained and experienced personnel! Notes on installing the electrical connections 4 Install the 230 V power supply lines and the signal lines separately! To increase noise immu4 4 4 4 nity, observe a minimum distance of 10 cm between the lines.
Connecting the sensors Cables with a minimum cross-section of 2 x 0.5 mm² can be connected to the terminals at the back panel of the housing. Connecting the actuators Connect cables with at least 1.5 mm² suitable for damp locations to the terminals of the controller output. The direction of travel needs to be checked at start-up. 4 Set mode switch to (+). Valves must open. 4 Set slide switch to (–). Valves must close. Connecting the pumps Connect all cables with at least 1.
System Anl 1 3 1 2 Option: Type 5244, Type 5257-5 System Anl 2 Option: 3 1 2 Type 5244, Type 5257-5 Option: Option: 5244, 5257-5 Type Type 5244, Type Type 5257-5 92 EB 5179 EN
System Anl 3 Option: Type 5244, Type 5257-5 System Anl 4 Option: Type 5244, Type 5257-5 EB 5179 EN 93
System Anl 5 Option: Type 5244, Type 5257-5 System Anl 6 Option: Type 5244, Type 5257-5 94 EB 5179 EN
System Anl 7 Option: Type 5244, Type 5257-5 System Anl 8 _ + _ + _ + 3 1 2 Option: Type 5244, Type 5257-5 EB 5179 EN 95
Electrical connection System Anl 9 Option: Type 5244, Type 5257-5 System Anl 10 _ + _ + + 3 1 2 A1 Voltage supply 24 V/30 mA 96 EB 5179 EN + A2 _ A1 A2 14 11 14 11 _ + Relay: Phoenix Contact, Type PLC-BSC-24 DC/21, Article no.
Appendix 12 Appendix 12.1 Function block lists Co1 to Co3: Heating circuit 1 to 3 Fb Function WE Anl Comments Function block parameters / Range of values (default settings) 00 Room sensor RF1, 2, 3 OFF All Co1, 2, 3 -> Fb00 = ON: Room sensor active 01 Return flow sensor RüF1, 2, 3 OFF All Co1, 2, 3 -> Fb01 = ON: Return flow sensor active Function block parameters: Limitation factor / 0 to 25.5 (1.
Appendix Fb Function WE Anl 09 RK switched off when switch at MAN-CLOSED OFF All 10 4-point characteristic OFF 11 Summer mode ON Comments Function block parameters / Range of values (default settings) Co1, 2, 3 -> Fb09 = ON: UP still runs until 1 x TY. The flow sensor is no longer be read. Not Co1, 2, 3 -> Fb10 = ON: 4-point characteristic 3, 5, Co1, 2, 3 -> Fb10 = OFF: Gradient characteristic 8, 10 All Co1, 2, 3 -> Fb11 = ON: Function block parameters: Start summer mode / 01.01 to 31.12 (01.
Appendix WE Anl Comments Function block parameters / Range of values (default settings) 17 Flow sensor OFF OFF with room temperature-dependent control 6, 9 Co1, 2, 3 -> Fb17 = ON: Deactivate flow sensor 18 Differential temper- OFF ature control using variable weighting factors All Co1, 2, 3 -> Fb18 = ON: Only for mixer circuits Function block parameters: Proportional gain (KP) / 0.1 to 999 (0.5) Reset time (TN) / 1 to 999 s (200 s) Intended temp. difference / 0 to 40 °C (20 °C) Analog value max.
Appendix WE 06 Reverse control ON 07 Time until reverse control ON 08 Thermal disinfection OFF 09 Three-point stepping control for DHW heating ON 10 Storage tank system OFF Not Co4 -> Fb10 = ON: DHW heating in storage tank system 1, 3, 6 11 Mixing valve always active OFF Not Co4 -> Fb11 = ON: Heating maintained to prevent circulation 1, 3, 6 losses 12 Public holiday and vacation data apply to DHW circuit OFF Co4 -> Fb12 = ON: Function block parameter: Not Data for heating circuit / 1 to 3
Appendix Co5: General functions and pre-control circuit Comments Function block parameters / Range of values (default setting) Fb Function WE Anl 00 Flow sensor secondary VFsek ON All Co5 -> Fb00 = ON: In systems Anl 6 and 9 not possible with Co5 -> Fb06 = ON 01 Return flow sensor primary ON Not 6, 9 Co5 -> Fb01 = ON: Return flow limitation active, Option steig Limitation acc. to gradient characteristic 4-pt Limitation acc.
Appendix Fb Function WE Anl 09 Pulse input for flow OFF rate or capacity limitation Not 6, 9 Comments Function block parameters / Range of values (default setting) Co5 -> Fb09 = ON: Type of limitation Option: U: Flow rate limitation P: Capacity limitation CONST Limitation constant 4-Pt: Limitation acc. to 4-point characteristic Function block parameter: Pulse weighting / 0.
Fb Function WE Anl Comments Function block parameters / Range of values (default setting)
Appendix Co6: Sensor initialization Fb Function WE Anl 00 Sensor selection general ON All Comments Function block parameters / Range of values (default setting) Co6 -> Fb00 = ON: Pt 100; Pt 1000 Co6 -> Fb00 = OFF: Pt 100; PTC Any sensor inputs that are different from the settings for function block Fb00 01 Sensor input 1 to to 17 sensor input 17 OFF All Co6 -> Fb01 to Fb17 = ON: select: Outdoor temperature input: 0/4 to 20 mA, 0 to 10 V = –40 to 50 °C Other temperature inputs: 0/4 to 20 mA, 0 to 1
Appendix Co8: Error initialization Fb Function WE Anl 00 Dial-up also upon corrected fault OFF All Comments Function block parameters / Range of values (default setting) CO8 -> Fb00 = ON: Dial-up to the building control station both when a fault was detected and a fault was corrected CO8 -> Fb00 = OFF: Dial-up to building control station only when fault was detected 01 BE1 in FSr to to 17 BE 17 in FSr OFF All Co8 -> Fb01 to Fb17 = ON: Option: Rising signal edge/make contact Negative signal edge/b
Appendix FB Function 21 Meter bus #1 to to 23 Meter bus #3 Comments WE Function block parameters / Range of values (default setting) OFF CO9 -> Fb21, 22, 23 = ON: Function block parameters: Meter bus address WMZ_ / 0 to 255 (255) Model code WMZ_ / P15, PS2, 1434, CAL3, APAtO, SLS (1434) Reading mode WMZ_ / 24h, con, CoiL (con) Fb Function block, WE Default setting 106 EB 5179 EN
Appendix 12.2 Parameter list PA1 to PA3: Heating circuits HK1 to HK3 Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Parameter designation Range of values (default settings) Gradient of the heating characteristic, flow 0.4 to 3.2 (1.
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 4-point characteristic Point 1: Flow temperature Flow temperatures of the points 2, 3, 4 are marked by squares below the numbers 2, 3, 4.
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Set-back difference ˚C 0 to 50 °C (20 °C) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Day set point ˚C 10 to 90 °C (20 °C) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Night set point ˚C 10 to 90 °C (17 °C) Optimization 2, 3 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Sustained temperature ˚C
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Level of the heating characteristic, return flow ˚C –30 to 30 °C (0 °C) Characteristic is shifted parallel. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Max. return flow temperature ˚C 20 to 90 °C (65 °C) Only with Co5 -> Fb01 = ON, select: steig 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Min.
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 OT deactivation value in rated operation ˚C STOP 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 0 to 90 °C (22 °C) Times-of-use Freely configurable (daily 7:00 to 24:00 h) –> Section 1.6 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Public holidays Freely configurable –> Section 1.
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Copy times-of-use of HK2 for HK3 Only in systems Anl 3, 6 PA4: DHW heating Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 DHW demand ON ˚C 20 to 90 °C (40 °C) Systems with a storage sensor SF1 Co4 -> Fb02 = ON , Fb02 = OFF 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 2
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 DHW demand OFF ˚C 20 to 90 °C (45 °C) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Charging temperature ˚C 20 to 90 °C (55 °C) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Heat exchanger charging pump, deactivation limit ˚C 20 to 90 °C (50 °C) STOP Lag of heat exchanger charging pump until the heat exchanger flow tem
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Maximum charging temperature ˚C 20 to 120 °C (120 °C) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time schedule of DHW heating 00:00 to 24:00 h 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time schedule of circulation pump 00:00 to 24:00 h PA5: Capacity and flow rate limitation Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Date (day.month) 01.01 to 31.12 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Date (year) Freely configurable 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Gradient of the heating characteristic, return flow 0.4 to 3.2 (1.
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Minimum return flow temperature ˚C 20 to 90 °C (20 °C) Only with Co5 -> Fb01 = ON, select: steig Control according to fixed set point: Min. return flow temperature = Max. return flow temperature 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Maximum capacity of the entire system 0.
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 m3/h 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 m3/h 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 m3/h 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 m3/h Maximum flow rate of the entire system 0.01 to 99.9 m3/h (9 m3/h) Maximum flow rate of the heating 0.01 to 99.
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 m3/h kW 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 4-point characteristic Press key to adjust the following parameters: outdoor temperature, return flow temperature (see page 108), maximum flow rate or maximum capacity.
Appendix Parameter designation Range of values (default settings) Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 kW P-offset of the entire system –3000 to 3000 kW (0.0 kW) PA9: Communication Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ST.-NR 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Parameter designation Range of values (default settings) Station address (ST.
Appendix Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Parameter designation Range of values (default settings) Modem dialing pause (P) 1 to 255 min (5 min) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Modem timeout (t) 1 to 255 min (5 min) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Number of dialing attempts (C) 0 to 99 (5) 0 1 2 3 4 5 6 7 8 910 11 12 13141516 171819202122 2324 Co9 -> Fb01 = ON: Phone number of control station (tE
Appendix 12.3 Display The following displays are typical displays that can appear. Icons at the edge of the display may vary depending on the operating mode and how the controller is configured; they cannot be shown in this case. Inf1 to Inf3: Heating circuits HK1 to HK3 Display Parameter designation 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Current flow temperature at VF1, VF2, VF3 ˚C Press enter key to confirm. The set point is displayed.
Appendix Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Parameter designation Tendency of the room temperature Valve position The actual value of the analog output with differential temperature control using variable weighting factors Press enter key to confirm. The set point is displayed. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time Press enter key to confirm. The time-of-use for Monday (1) is displayed.
Appendix Display 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Parameter designation Vacations Press enter key to confirm.. The first vacation period is displayed. Press arrow key to scroll between other vacation periods. Inf4: DHW heating Display Parameter designation Charging temperature (supply of heat exchanger) Press enter key to confirm. The set point is displayed. Charging temperature (supply of storage tank) Press enter key to confirm. The set point is displayed.
Appendix Display Parameter designation Storage tank temperature at sensor SF2 Press enter key to confirm. The set point is displayed. Storage tank temperature at return flow sensor Press enter key to confirm. The set point is displayed. Control signal for continuous-action control Only with Co4 -> Fb14 = ON 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time; Times-of-use for DHW demand Press enter key. The times-of-use for Monday (1) are shown.
Appendix Inf5: District heating circuit Display Parameter designation Charging temperature Press enter key to confirm. The set point is displayed. Return flow temperature at sensor RüF or RüFprim Press enter key to confirm. The set point is displayed.
Appendix InF7: LON communication Display Parameter designation Connected LON controller, e.g. a TROVIS 5174 with LON address 2 Press enter key. “FSr“ of the corresponding controller is displayed. Inf8: Error status register/sensor failure Display 0 1 2 3 4 5 6 7 8 910 11 12 13141516171819202122 2324 Parameter designation Error status register FSr 1 Press enter key.
Appendix InF9: Communication (only with Co9 -> Fb01 = ON, Co9 -> Fb06 = ON or Co9 -> Fb10 = ON) In the main display loop, the connection status appears in the InF9 level and only exists when the modem, SMS or fax function is active, otherwise just “END“ appears on the display. In this display, the applicable status from the following list of states appears when a modem connection is established.
Appendix 12.
Appendix 12.5 Technical data Inputs Sensor inputs Max.
Appendix 12.
Appendix PA1 to PA3: Heating circuits HK1 to HK3 Parameters PA1 PA2 PA3 Range of values Gradient, flow 0.4 to 3.2 Level, flow –30 to 30 °C Maximum flow temperature 20 to 130 °C Minimum flow temperature 20 to 130 °C Set-back difference 0 to 50 °C Gradient, return flow 0.4 to 3.
Appendix Parameters PA1 PA2 PA3 Range of values Times-of-use Monday Start – Stop (1) 00:00 to 24:00 h Monday Start – Stop (2) 00:00 to 24:00 h Tuesday Start – Stop (1) 00:00 to 24:00 h Tuesday Start – Stop (2) 00:00 to 24:00 h Wednesday Start – Stop (1) 00:00 to 24:00 h Wednesday Start – Stop (2) 00:00 to 24:00 h Thursday 00:00 to 24:00 h Start – Stop (1) Thursday Start – Stop (2) 00:00 to 24:00 h Friday Start – Stop (1) 00:00 to 24:00 h Friday Start – Stop (2) 00:00 to 24:0
Appendix Differential temperature control using variable weighting factors (Fb18 = ON) 0 to 40 °C Function block parameters Co1, Co2, Co3 Analog value max. (Fb18 = ON) 0 to 100 % Analog value min.
Appendix PA4: DHW heating Parameters PA4 Range of values DHW demand ON 20 to 90 °C DHW demand OFF 20 to 90 °C Hysteresis 0 to 30 °C Charging temperature 20 to 90 °C Heat exchanger charging pump, deactivation value 20 to 90 °C Storage tank charging pump, deactivation value 20 to 90 °C Return flow limitation temperature 20 to 90 °C Maximum charging temperature Times-of-use 134 20 to 120 °C DHW ZP Monday Start – Stop (1) 00:00 to 24:00 h Monday Start – Stop (2) 00:00 to 24:00 h Tues
Appendix Function block parameters Co4 Limitation factor (Fb02 = ON) 0 to 25.5 Activate priority in case of deviation (Fb06 = ON) 0 to 30 °C Day of week (Fb08 = ON) 0, 1 to 7 Disinfection temperature (Fb08 = ON) 60 to 90 °C Boost of charging temperature 0 to 30 °C Start – Stop (Fb08 = ON) 00:00 to 23:30 TY (valve transit time) (Fb09 = ON) 15 to 240 s KP (proportional gain) (Fb09/14 = ON) 0.
Appendix Parameters PA5 Range of values Outdoor temperature, point 3 –30 to 90 °C Outdoor temperature, point 4 –30 to 90 °C Return flow temperature, point 1 20 to 90 °C Return flow temperature, point 2 20 to 90 °C Return flow temperature, point 3 20 to 90 °C Return flow temperature, point 4 20 to 90 °C Max. limit of flow rate, point 1 0 to 99.9 m3/h Max. limit of flow rate, point 2 0 to 99.9 m3/h Max. limit of flow rate, point 3 0 to 99.9 m3/h Max. limit of flow rate, point 4 0 to 99.
Appendix Co9: Modbus and meter bus communication Parameters Range of values Station number (ST.-NR) 1 to 247, 999 Baud rate (BAUD) 300 to 19200 Cyclic initialization (I) 1 to 255 min Modem dial interval between calls (P) 0 to 255 min Modem timeout (t) 0 to 255 min Number of redial attempts (C) 1 to 99 Phone number of control station Phone number of alternative recipient max.
Index Index 4-point characteristic . . . . . . . . . . . . . . . 40 Display . . . . . . . . . . . . . . . . . . . . . . . . . . 9 A E Adaptation . . . . . . . . . . . . . . . . . . . . . . 48 Advance heating outdoor temperature-dependent. . . . . 45 Arrow keys . . . . . . . . . . . . . . . . . . . . . . . 6 Automatic mode . . . . . . . . . . . . . . . . . 7 - 8 Electrical connection . . . . . . . . . . . . 90 - 96 Enter key . . . . . . . . . . . . . . . . . . . . . . . . . 6 Error archive register . . .
Index Interface Position feedback . . . . . . . . . . . . . . . . . . 51 Meter bus. . . . . . . . . . . . . . . . . . . . . 81 Priority RS-232-C. . . . . . . . . . . . . . . . . . . . . 77 DHW heating . . . . . . . . . . . . . . . . . . 56 RS-485 . . . . . . . . . . . . . . . . . . . . . . 78 Pump management . . . . . . . . . . . . . . . . 50 K R Key number . . . . . . . . . . . . . . . . . . . . . . 24 Rated operation . . . . . . . . . . . . . . . . . 7 - 8 entering . . . . . . . . . . . . . . . . . . .
Index Time delays, compensating for . . . . . . . . 61 Time-controlled operation . . . . . . . . . . . . . 8 Times-of-use copying . . . . . . . . . . . . . . . . . . . . . . 15 setting . . . . . . . . . . . . . . . . . . . . . . . 13 U Universal inputs . . . . . . . . . . . . . . . . . . . 24 V Vacation periods . . . . . . . . . . . . . . . . . . 18 W Weather-compensated control. . . . . . . . .
00:00 InF1 InF1: Heating circuit 1 InF2: Heating circuit 2 InF3: Heating circuit 3 InF4: DHW heating InF5: Primary control circuit InF7: LON communication InF8: Error status register InF9: Communication PU: Pump/manual level bIn-E: Binary inputs and outputs Error: Error indication PA1: Heating circuit 1 PA2: Heating circuit 2 PA3: Heating circuit 3 PA4: DHW heating PA5: Capacity/flow rate limitation PA7: LON communication PA9: Communication Anl: System InF2 Error or Op
EB 5179 EN 2006-03 SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.samson.