Operating instructions
Code
no.
Parameter – Readings,
values [default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
E4 – Unassigned –
E5* Activate PST tolerance band
monitoring
[No] · YES
Activates PST tolerance band monitoring (YES) or deactivates it
(No)
E6* PST tolerance band
0.1 to 100.0 % · ESC, [5.0]
The test is canceled when the deviation in valve position (in rela
-
tion to the upper range value of the step) exceeds the adjusted
value.
E7* Max. test duration
30 to 25000 s · ESC [30]
The test is canceled when the maximum test duration is reached.
E8 – Unassigned –
E9* Reset 'Partial stroke test pa-
rameters'
Resets partial stroke test parameters
F0 No test available
F1 – Unassigned –
F2 x cancelation The test was canceled.
The valve position fell below the
x monitoring value
(Code 49 -
E1).
F3
D
p_out cancelation The test was canceled.
The change in signal pressure (
D
p_out) fell below or exceeded
the reference value (Code 49 - A9).
F4 Tolerance band exceeded The deviation of the valve position exceeded the adjusted
PST tol
-
erance band
(Code 49 - E6).
F5 Max. test duration ex
-
ceeded
The test was canceled.
The
Max. test duration
(Code 49 - E7) was reached.
F6 Test canceled manually
F7 Measured data memory full The
Sampling time
(Code 49 - d9) is too low. After recording
100 data points per variable, logging is stopped, but the test
continues until it is completed.
F8 Cancelled by internal sole
-
noid valve/forced venting
The test was canceled.
The internal solenoid valve has been energized/the forced
venting has been activated.
EB 8384-6 EN 99
Code list