Operating instructions

Code
no.
Parameter – Readings,
values [default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
d3* Upper range value
0.0 to 100.0 % · ESC, [90.0]
Final value of the test
d4* Activate ramp function
No · [YES]
YES: The valve is ramped through the test range within the
adjusted ramp time.
No: The valve is moved in steps through the test range (step
response).
d5* Ramp time (decreasing)
0 to 9999 s · ESC, [45]
Time period in which the valve moves through the operating
range from the closed to the open position
The time to move from
Lower range value
(Code 49 - d2) to
Upper range value
(Code 49 - d3) is calculated:
Upper range value – Lower range value
/ 100 x
Ramp time (in
-
creasing)
d6* Ramp time (increasing)
0 to 9999 s · ESC, [45]
Time period in which the valve moves through the operating
range from the open to the closed position
The time to move from
Upper range value
(Code 49 - d3) to
Lower range value
(Code 49 - d2) is calculated:
Lower range value – Upper range value
/ 100 x
Ramp time (de-
creasing)
d7* Settling time before starting
test
1 to 240 s · ESC, [10]
Settling time between reaching the upper range value (Code 49 -
d3) and the valve moving through the test range in the reverse
direction
d8* Waiting time after step
change
1.0 to 240.0 s · ESC, [2.0]
Waiting time between step change from
Lower range value
(Code 49 - d2) to
Upper range value
(Code 49 - d3) and vice
versa
d9* Sampling time
[0.2] to 250.0 s · ESC
Time interval between measuring data
E0* Activate x monitoring
No · [YES]
Activates x monitoring (YES) or deactivates it (No)
E1* x monitoring value
–10.0 to 110.0 % of the en
-
tire travel · ESC, [85.0]
The test is canceled when the valve moves below the adjusted
value.
E2 – Unassigned –
E3 – Unassigned –
98 EB 8384-6 EN
Code list