Operating instructions

Code
no.
Parameter – Readings,
values [default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
d5* Zero point limit
0.0 to 100.0 % of the nom
-
inal range · ESC, [5.0]
Valve position limit in relation to the nominal range
When the limit is exceeded, a 'Zero point' message (Code 58) is
generated according to the status classification selected.
Note: The 'Zero point' message (Code 58) has the default status
classification 'Maintenance required'. This classification can only
be changed in the operator software (e.g. TROVIS-VIEW 4) .
d6 Condensed state
Read only
Summary of all the classified status messages according to the
NAMUR Recommendation NE 107
OK: No message
C: Maintenance required
CR: Maintenance demanded
S: Out of specification
B: Failure
I: Function check
d7 Supply pressure p
s
Read only
Current supply pressure [bar]
d8 Signal pressure p
out
Read only
Current signal pressure [bar]
d9 Flow rate
Read only
Current flow rate through the valve
Note: – – – – appears on the display when the flow rate calcula
-
tion is not active or has failed.
d10 Differential pressure
Read only
Current differential pressure [bar]
d11* Direction of action (actuator)
[-/-] · SA · DA · ELSE · ESC
Indicates the actuator's direction of action
SA: Single-acting
DA: Double-acting
ELSE: Other
EB 8384-6 EN 95
Code list