Operating instructions

Code
no.
Parameter – Readings,
values [default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
45
Internal solenoid valve/
forced venting
Read only
Indicates whether a solenoid valve/forced venting is installed.
If a voltage supply is connected at the terminals +81/–82,
YES
and
HIGH
appear on the display in alternating sequence. If a
voltage supply is not connected (actuator vented, fail-safe posi
-
tion indicated on the display by the S icon),
YES
and
LOW
ap
-
pear on the display in alternating sequence.
46*
Bus address
[0] to 15 · ESC
Using the HART
®
protocol, all connected control room devices
and field devices can be addressed individually using a
point-to-point connection or the standard (multidrop) bus.
Point-to-point: HART
®
master drive connected on HART
®
field
device. With this connection, the positioner address must
always be set to '0'.
Standard (multidrop) bus: A maximum of 15 field devices can be
connected in parallel to a single pair of wires. The
HART
®
master drive tells them apart by their addresses
in the range from 1 to 15.
47*
HART
®
write protection
[No] · YES · ESC
When the write protection function is activated, device data can
only be read, but not overwritten over HART
®
communication.
48 - Diagnosis
Note: For more details, refer to the Operating Instructions EB 8389-1 EN on EXPERTplus Valve
Diagnostics.
d0 Temperature
Read only
Current operating temperature [°C] inside the positioner
(accuracy
±
3 %)
d1 Minimum Temperature
Read only
Lowest temperature [°C] inside the positioner since the operating
hours counter started counting
d2 Maximum temperature
Read only
Highest temperature [°C] inside the positioner since the operating
hours counter started counting
d3 Number of zero calibrations
Read only
The number of zero calibrations performed since the last initial
-
ization.
d4 Number of initializations
Read only
The number of initializations that have been performed since the
last start with default settings.