Operating instructions

Code
no.
Parameter – Readings,
values [default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
33*
Error message in case of
'Maintenance required' and
'Out of specification' con
-
densed states
[YES] · No · ESC
YES: 'Failure', 'Maintenance required' and 'Out of specifica
-
tion' condensed state cause an error message to be gen
-
erated.
No: Only 'Failure' condensed state causes an error message
to be generated.
34*
Closing direction
CL · [CCL] · ESC
CL : Clockwise
CCL: Counterclockwise
Turning direction in which the valve is moved to the CLOSED po
-
sition (view onto the rotary switch motion when the positioner
cover is open).
Note: Only needs to be entered when the SUB initialization mode
(Code 6) is selected.
35*
Blocking position
[0] mm/° /% · ESC
Distance up to CLOSED position
Note: Only needs to be entered when the SUB initialization mode
(Code 6) is selected.
36*
Reset
STD · DIAG · DS · ESC
STD: Reset start-up
Parameters are reset to their default settings
Diagnosis data are reset
Information parameters (read only) remain unchanged
Positioner must be re-initialized
DIAG: Reset diagnosis data
Parameter settings, reference data and logging re
-
main unchanged
Re-initialization not required
DS: Reset positioner to default settings
Parameters are reset to their default settings
Diagnosis data are reset
Information parameters (read only) are deleted
Positioner must be re-initialized
92 EB 8384-6 EN
Code list