Operating instructions
Code
no.
Parameter – Readings,
values [default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
9*
Upper travel/angle range
value (upper x-range value)
20.0 to [100.0] % of the
nominal range · ESC
Specified in mm or angle°,
provided Code 4 is acti
-
vated.
Upper range value for the travel/angle of rotation in the oper
-
ating range.
Nominal range and characteristic are automatically adapted.
Example: The operating range is modified, for example, to limit
the range of a valve which has been sized too large. For this
function, the entire resolution range of the set point is converted
to the new limits. 0 % on the display corresponds to the adjusted
lower limit and 100 % to the adjusted upper limit.
10*
Lower travel/angle limit
(lower x-limit)
[No] · 0.0 to 49.9 % of the
operating range · ESC
Lower limitation of the travel/angle of rotation to the entered
value.
The characteristic is not adapted.
11*
Upper travel/angle limit
(upper x-limit)
No · 50.0 to120.0 % of the
operating range · ESC,
[100.0]
Upper limitation of the travel/angle of rotation to the entered
value.
The characteristic is not adapted.
Example: In some applications, it is better to limit the valve
travel, e.g. if a certain minimum medium flow is required or a
maximum flow must not be reached.
The lower limit must be adjusted with Code 10 and the upper
limit with Code 11.
If a tight-closing function has been set up, it has priority over the
travel limitation!
When set to 'No', the valve can be opened past the nominal
travel with a set point outside of the 4 to 20 mA range.
86 EB 8384-6 EN
Code list