Operating instructions
14 Code list
Code
no.
Parameter – Readings,
values [default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
0
Operating mode
[MAN] Manual mode
AUtO Automatic mode
SAFE Fail-safe position
ESC Escape
Switchover from automatic to manual mode is smooth.
Automatic mode is only possible after the positioner has been ini
-
tialized.
Refer to section 6 for reading under Code 0
1
Manual set point (manual w)
0 to 100 [0] %
of the nominal range
An on/off valve can be
moved past 100 % of the
nominal range (with the
closed position for ATO) or
below 0 % of the nominal
range (with the closed posi-
tion for ATC).
Adjust the manual set point with the rotary pushbutton, the
current travel/angle is displayed in % when the positioner is ini
-
tialized, otherwise the position of the lever in relation to the cen
-
tral axis is indicated in degrees °.
Note: Can only be selected when Code 0 = MAN
2
Reading direction
Normal or upside down
ESC
The reading direction of the positioner display, depending on the
location of the pneumatic connection
3
Enable configuration
[No] · YES · ESC
Enables the option to modify data (automatically deactivated when
the rotary pushbutton has not been operated for 120 s.)
Codes marked with an asterisk (*) can only be read and not
overwritten.
HART
blinks on the display when the on-site operation is locked
over HART
®
communication.
PST
appears on the display when the on-site operation is locked
by the time-controlled partial stroke test.
In these cases, codes can only read over the SSP interface.
EB 8384-6 EN 83
Code list