Operating instructions

8 Operation
WARNING!
The actuator stem moves while the positioner
is being operated.
Do not touch the actuator stem or obstruct it
to avoid risk of injury to hands or fingers.
8.1 Enabling and selecting
parameters
The code list in section 14 on page 83 on
-
wards contains all codes with their meaning
and default settings.
The codes which are marked with an aster-
isk (*) must be enabled with Code 3 before
the associated parameters can be config-
ured as described below.
Code 3
Configuration
not enabled
Configuration
enabled
Turn
®
Code 3, display:
No
Press , Code 3 blinks.
Change the setting of Code 3.
Turn
®
YES
Press , display:
Configuration is enabled.
You can now configure codes one after the
other:
Turn and select the required code.
Press to access the selected code. The
code number starts to blink.
Turn and select the setting.
Press to confirm the selected setting.
Note: If no settings are entered within 120
seconds, the enabled configuration function
becomes invalid and the display changes to
Code 0.
Canceling a value before it is confirmed
Canceling the reading
To cancel a value before it is confirmed (by
pressing ) proceed as follows:
Turn
®
ESC
Press . The entered value is not adopted.
74 EB 8384-6 EN