Operating instructions

Pressure limit
Default
No
KP level
Default
7
TV level
Default
Turn
®
Code
16/17/18
Press , Code 16/17/18 blinks
Turn to set the control parameter selected
Press to confirm the setting.
Enter closing direction and blocking posi-
tion:
Closing direction
Direction of rotation causing
the valve to move to the
CLOSED position (view onto
positioner display)
Default: CCL (counterclock
-
wise)
Blocking position
Default: 0
Turn
®
Code 34
Press , Code 34 blinks
Turn
®
Closing direction (CCL counter
-
clockwise/CL clockwise)
Press
Turn
®
Code 35
Press , Code 35 blinks
Turn
®
Blocking position, e.g. 5 mm
(read off at travel indicator scale of the
blocked valve or measure with a ruler).
Define the valve closed position:
4
Set switch for valve closed position AIR
TO OPEN or AIR TO CLOSE as de
-
scribed in section 7.1 on page 56.
4
Set volume restriction as described in
section 7.2 on page 57.
Start initialization:
4
Press INIT key!
The operating mode is changed to auto-
matic mode .
Note:
As initialization has not been carried out
completely, the error code 76 (no emer-
gency mode) and possibly also error
code 57 (control loop) may appear on
the display.
These alarms do not influence the
positioner’s readiness for operation.
If the positioner shows a tendency to os
-
cillate in automatic operating mode, the
parameters K
P
and T
V
must be slightly
corrected. Proceed as follows:
Set T
V
to 4 (Code 18).
If the positioner still oscillates, the gain
K
P
(Code 17) must be decreased until the
positioner shows a stable behavior.
EB 8384-6 EN 67
Start-up – Settings
mm