Enter the pin position and nominal range:
Pin position
Default
No
Nominal range
(locked with Code 4 = No)
Turn
®
Code 4
Press , Code 4 blinks
Turn
®
Pin position on lever (see relevant
section on attachment)
Press
Turn
®
Code 5
Press , Code 5 blinks
Turn
®
Nominal travel/angle
Press
Select the initialization mode:
Initialization mode
Default
MAX
Turn
®
Code 6
Press
Turn
®
SUB
Press to confirm
SUB
as the initialization
mode.
Enter the direction of action:
Direction of action
Default ää
Turn
®
Code 7
Press , Code 7 blinks
Turn
®
Direction of action (ää/äæ)
Press
Deactivate travel limit:
Travel limit
Default
100.0
Turn
®
Code 11
Press , Code 11 blinks
Turn
®
No
Press
Change pressure limit and control parame
-
ters:
Note: Do not change the pressure limit
(Code 16). Only change the control param
-
eters K
P
(Code 17) and T
V
(Code 18) if the
settings of the replaced positioner are
known.
66 EB 8384-6 EN
Start-up – Settings
mm
mm