Operating instructions
After initialization, the maximum travel is in
-
dicated in mm or the maximum angle in ° in
Code 5.
7.6.4 MAN2 – Initialization based
on manually selected end
positions
Before starting initialization, move the con
-
trol valve manually to the end positions. The
positioner calculates the travel/angle differ
-
ence from the positions that the valve moved
to and adopts it as the operating range with
limits of lower travel/angle range value
(Code 8) and upper travel/angle range
value (Code 9).
Note: This initialization mode can only be
started when the valve position differs in the
end positions and the positioner has not yet
been initialized.
Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Enable configuration
Default
No
Turn
®
Code
3
, display:
No
Press , Code 3 blinks
Turn
®
YES
Press , display
Enter the pin position:
Pin position
Default
No
Turn
®
Code 4
Press , Code 4 blinks
Turn
®
Pin position on lever (see relevant
section on attachment
Press
Turn
®
Skip nominal range (Code 5) and
go to Code 6.
Select the initialization mode and enter end
positions:
Initialization mode
Default
MAX
POS1 (end position 1)
POS2 (end position 2)
Turn
®
Code 6
Press , Code 6 blinks
64 EB 8384-6 EN
Start-up – Settings
mm