Operating instructions
positions and adopts it as the operating
range with limits of lower travel/angle
range value (Code 8) and upper travel/an
-
gle range value (Code 9).
Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Enable configuration
Default
No
Turn
®
Code
3
, display:
No
Press , Code 3 blinks
Turn
®
YES
Press , display
Enter the pin position:
Pin position
Default
No
Turn
®
Code 4
Press , Code 4 blinks
Turn
®
Pin position on lever (see relevant
section on attachment)
Press
Turn
®
Skip nominal range (Code 5)
and go to Code 6.
Select the initialization mode:
Initialization mode
Default
MAX
Turn
®
Code 6
Press , Code 6 blinks
Turn
®
MAN
Press to confirm the
MAN
as the initial
-
ization mode.
Enter OPEN position:
Manual set point
(the current angle of rotation
is displayed)
Turn
®
Code 0
Press , Code 0 blinks
Turn
®
MAN
Press
Turn
®
Code 1
Press , Code 1 blinks
Turn clockwise in small steps until the re
-
quired valve position is reached. The valve
must be moved with a monotonically in
-
creasing signal pressure.
Press to confirm the OPEN position.
Start initialization:
4
Press INIT key to start initialization!
EB 8384-6 EN 63
Start-up – Settings
mm