Operating instructions

Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Default
No
Turn
®
Code
3
, display:
No
Press , Code 3 blinks
Turn
®
YES
Press , display
Enter pin position and nominal range:
Pin position
Default
No
Nominal range
(locked with Code 4 = No)
Turn
®
Code 4
Press , Code 4 blinks
Turn
®
Pin position on lever (read rele
-
vant section on attachment)
Press
Turn
®
Code 5
Press , Code 5 blinks
Turn
®
Nominal travel/angle
Press
Select the initialization mode:
Initialization mode
Default
MAX
Turn
®
Code 6
Press , Code 6 blinks
Turn
®
NOM
Press to confirm the
NOM
as the initial
-
ization mode.
Start initialization:
4
Press INIT key to start initialization!
Note: If the nominal range determined dur-
ing initialization is smaller than the range
entered in Code 5, initialization is canceled
and an error message (Code 52) is gener-
ated.
After initialization, check the direction of
action and, if necessary, change it (Code
7).
7.6.3 MAN – Initialization based
on a manually selected
OPEN position
Before starting initialization, move the con
-
trol valve manually to the OPEN position.
The positioner calculates the differential
travel/angle from the OPEN and CLOSED
62 EB 8384-6 EN
Start-up – Settings
mm
mm