Operating instructions

Actuator stem extends FA (air to open)
Fail-safe position "Valve closed"
(for globe and angle valves):
Actuator stem retracts FE (air to close)
Fail-safe position "Valve open"
(for globe and angle valves):
For tight-closing valves, the maximum signal
pressure pst
max
is roughly estimated as fol
-
lows:
pst
max
= F +
dp
A
2
4
××
×
pD
[bar]
d = Seat diameter [cm]
D
p = Differential pressure across the valve
[bar]
A = Actuator diaphragm area [cm²]
F = Upper bench range value [bar]
If there are no specifications, calculate as
follows:
Required supply pressure =
Upper bench range value + 1 bar.
5.1.3 Signal pressure (output)
The signal pressure at the output (Output
38) of the positioner can be limited in steps
of 0.1 bar to a pressure between 1.4 and
7.0 bar in Code 16.
The limitations is not activated [7.0 bar] by
default.
5.2 Electrical connections
DANGER!
Risk of electric shock and/or
the formation of an explosive
atmosphere!
For electrical installation, observe the rel
-
evant electrotechnical regulations and
the accident prevention regulations that
apply in the country of use.
NOTICE
Adhere to the terminal assignment!
Switching the assignment of the electrical
terminals may cause the explosion pro-
tection to become ineffective!
Do not loosen enameled screws in or on
the housing.
The maximum permissible values speci-
fied in the national EC type examination
certificates apply when interconnecting
intrinsically safe electrical equipment (U
i
or U
o
; I
i
or I
o
; P
i
or P
o
; C
i
or C
o
, and L
i
or
L
o
).
Selecting cables and wires:
For installing intrinsically safe circuits, ob
-
serve
Paragraph 12 in EN 60079-14: 2008
(VDE 0165 Part 1).
To install and select cables and wires as well
as to run several intrinsically safe circuits in
one multi-core cable, observe the installation
regulations valid in the country of use. The
diameter of an individual wire in a
fine-stranded conductor must not be smaller
than 0.1 mm. Protect the conductor ends
against splicing, e.g. by using wire-end fer
-
rules.
When two separate cables are used for con
-
46 EB 8384-6 EN
Connections