Operating instructions
NOTICE
The adapter uses one of the M20 x 1.5 con
-
nections in the housing which means just
one cable gland can be installed.
Should other valve accessories be used
which vent the actuator (e.g. solenoid valve,
volume booster, quick exhaust valve), this
exhaust air must also be included in the
purging function. The connection over the
adapter at the positioner must be protected
with a check valve, e.g. check valve G ¼
(order no. 8502-0597) mounted in the pip
-
ing. Otherwise the pressure in the positioner
housing would rise above the ambient pres-
sure and damage the positioner when the
exhausting components respond suddenly.
4.10 Required mounting parts and accessories
EB 8384-6 EN 41
Attachment to the control valve – Mounting parts and accessories
Table 2 · Direct attachment to Type 3277-5 Actuator (Fig. 4)
Order no.
Mounting parts Mounting parts for actuators 120 cm² or smaller 1400-7452
Accessories for
the actuator
Connecting plate (9) (new) for Actuator Type 3277-5xxxxxx.01 (new)
1)
,
G ¼ and ¼ NPT
1400-6823
Connecting plate (old) for Actuator Type 3277-5xxxxxx.00 (old): G ¼ 1400-6820
Connecting plate (old) for Actuator Type 3277-5xxxxxx.00 (old): G ¼ 1400-6821
Accessories for
the positioner
Connecting plate (6)
G
1
4
1400-7461
1
4
NPT 1400-7462
Pressure gauge bracket (7)
G
1
4
1400-7458
1
4
NPT 1400-7459
Pressure gauge mounting kit (8) up to max. 6 bar (output/supply)
St. steel/brass 1400-6950
St. steel/St. st. 1400-6951
1)
Only new switchover and connecting plates can be used with new actuators (Index 01).
Old and new plates are not interchangeable.