Series 3731 Type 3731-3 Electropneumatic Ex d Positioner with HART® communication Fig. 1 · Type 3731-3 Mounting and Operating Instructions EB 8387-3 EN Firmware version 1.
Definitions of the signal words used in these instructions DANGER! indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING! indicates a hazardous situation which, if not avoided, could result in death or serious injury. 2 EB 8387-3 EN NOTICE indicates a property damage message.
Contents Contents 1 Important safety instructions . . . . . . . . . . . . . . . . . . . . . . 6 2 Article code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 3 3.1 3.2 3.2.1 3.3 Design and principle of operation. . . . . . . . . . . . . . . . . . . . 8 Additional equipment . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Configuration using TROVIS-VIEW software . . . . . . . . . . . . . . 10 Technical data. .
Contents 7.5.1 7.5.2 7.5.3 7.5.4 7.6 7.7 Initialization based on MAX maximum range . . . . Initialization based on NOM nominal range . . . . . Initialization based on MAN manually selected range SUB substitute calibration . . . . . . . . . . . . . . Zero calibration . . . . . . . . . . . . . . . . . . . Reset to default values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 52 53 55 58 59 8 8.1 8.2 8.
Modifications to positioner firmware Modifications to positioner firmware compared to the previous version 1.41 (old) 1.42 (new) After performing a reset to default values, the allocation of the closing position AIR TO OPEN (AtO) /AIR TO CLOSE (AtC) is not reset to the default setting. The setting is kept. 1.42 (old) 1.
Important safety instructions 1 Important safety instructions For your own safety, follow these instructions concerning the mounting, start up and operation of the positioner: 4 The positioner is to be mounted, started up or operated only by trained and experienced personnel familiar with the product.
Article code 2 Article code Positioner Type 3731 - 3 x x x x x x x 00x 1x 000 With LCD, autotune, HART® communication Explosion protection ATEX: II 2G Ex db IIC T6; II 2G Ex db eb IIC T6; II 2G Ex db [ia] IIC T6; II 2G Ex ia IIC T6; II 2D Ex tb IIIC T80°C IP66 21 FM: Class I, Div. 1+2, Groups B, C, D; Class I, Zone 1, Groups IIB+H2; Class I, Div. 1+2 Groups E, F, G; Class III 23 CSA: Class I, Zone 1, Group IIB+H2 T4...T6; Class I, Div. 1+2, Groups B, C, D T4...T6; Class II, Div.
Design and principle of operation 3 variable y) is produced for the pneumatic actuator. Design and principle of operation The electropneumatic Ex d positioner is mounted on pneumatic control valves. It is used to assign the valve stem position (controlled variable x) to the control signal (reference variable w).
Design and principle of operation software or on site at the positioner. A constant air stream to the atmosphere is created by the flow regulator (9) with a fixed set point. The air stream is used to purge the inside of the housing as well as to optimize the air capacity booster (7). The i/p converter (6) is supplied with a constant upstream pressure by the pressure regulator (8) to make it independent of the supply pressure. All parts are enclosed in an Ex d housing.
Design and principle of operation Binary input 3.2 The positioner has an optional binary input. The following actions can be performed over the binary input: The positioner is equipped with an interface for HART® protocol (Highway Addressable Remote Transducer) for communication purposes. Data are transmitted in a superimposed frequency (FSK = Frequency Shift Keying) on the existing signal loop for the 4 to 20 mA reference variable.
Design and principle of operation Additional information on TROVIS-VIEW (e.g. system requirements) can found on the SAMSON website and in the Data Sheet T 6661 EN.
Design and principle of operation 3.3 Technical data Type 3731-3 Ex d Positioner (technical data in test certificates additionally apply for explosion-protected devices) Rated travel Adjustable Direct attachment to Type 3277: 3.6 to 30 mm Attachment acc. to IEC 60534-6 (NAMUR): 3.
Design and principle of operation Type 3731-3 Ex d Positioner (technical data in test certificates additionally apply for explosion-protected devices) Air output Pressurized At ∆p = 6 bar: 8.5 mn³/h · At ∆p = 1.4 bar: 3.0 mn³/h · KVmax(20° C) = 0.09 capacity Vented At ∆p = 6 bar: 14.0 mn³/h · At ∆p = 1.4 bar: 4.5 mn³/h · KVmax(20° C) = 0.15 to actuator Permissible ambient temperature –40 to 80 °C The limits in the test certificate additionally apply. Influences Temperature: ≤ 0.
Design and principle of operation Additional equipment Optional binary output, software limit switch, galvanically isolated Connection: Optionally NAMUR EN 60947-5-6 or PLC, configurable as a limit switch or fault alarm output Signal status Operating voltage Terminals B-C Switching output AC/DC (PLC) Terminals A-B Conductive/remaining voltage < 1.7 V ≥ 2.2 mA Non-conducting/high resist. I < 100 µA ≤ 1.0 mA Switch. capacity: 40 V DC/28 V/AC 0.3 A Static destr. limit: 45 V DC/32 V/AC 0.
Attachment to the control valve – Mounting parts and accessories 4 Attachment to the control valve – Mounting parts and accessories WARNING! Attach the positioner, keeping the following sequence: 1. Mount the positioner on the control valve 2. Connect the supply air 3. Connect the electrical power 4.
Attachment to the control valve – Mounting parts and accessories Travel tables Note: The lever M is included in the scope of delivery. Levers S, L, XL for attachment according to IEC 60534-6 (NAMUR) are available as accessories (see Table 3 on page 32). Direct attachment to Type 3277-5 and Type 3277 Actuators Adjustment range at positioner 1) Actuator size Rated travel [cm²] [mm] Min. Travel Max. Required lever Assigned pin position 120 7.5 5.0 to 25.0 M 25 120/175/240/350 15 7.
Attachment to the control valve – Mounting parts and accessories 4.1 Direct attachment 2. 4.1.1 Type 3277-5 Actuator Refer to Table 1 on page 30 for required mounting parts and accessories. 3. Actuator with 120 cm² NOTICE If a solenoid valve or similar is additionally mounted to the actuator, observe the following instructions which differ from the instructions otherwise described: – The switchover plate (9) is omitted.
Attachment to the control valve – Mounting parts and accessories it in the hole for pin position 25 and screw tight. 9. Insert formed seal (15) into the groove of the positioner housing, pressing the four retaining rings over the housing screws and both fittings into the housing recesses. 10. Thread the bias spring (17) through the crosspiece underneath the lever (1) and push into the hole in the housing. Push the lever (1) until it engages into place.
Attachment to the control valve – Mounting parts and accessories 1 1.1 1.2 2 3 4 5 6 6.1 7 8 9 Symbols Switchover plate (9) Actuator stem extends Left attachment Right attachment Actuator stem retracts A Signal pressure input for left attachment Marking Signal pressure input for right attachment A-A 15 14 Lever Nut Disk spring Follower pin Follower clamp Screw plug Stopper Connecting plate for G ¼ Seal rings Pressure gauge bracket Press.
Attachment to the control valve – Mounting parts and accessories 4.1.2 Type 3277 Actuator Refer to Table 2 on page 31 for the required mounting parts and accessories. Actuators with 175 to 750 cm² Mount the positioner onto the yoke as shown in Fig. 5. The signal pressure is routed to the actuator over the connection block (12), for actuators with fail-safe action "Actuator stem extends" internally through a bore in the valve yoke and for "Actuator stem retracts" through external piping. 1. 2. 3. 4. 5.
Attachment to the control valve – Mounting parts and accessories 1 1.1 1.2 2 3 10 11 11.1 12 Connection block 12.1 Screw 12.2 Stopper or connection for external piping 13 Switch plate 14 Gasket 15 Formed seal 16 Gasket 17 Bias spring (only for direct attachment) Lever Nut Disk spring Follower pin Follower clamp Cover plate G ¼ Cover Vent plug 15 10 14 1 2 3 11 11.1 2 1.1 1.
Attachment to the control valve – Mounting parts and accessories 9. 4.2 Mount cover (11) on the other side. Make sure that the vent plug (11.1) points to the back when the control valve is installed to allow any condensed water that collects to drain off. Attachment according to IEC 60534-6 (NAMUR) Refer to Table 3 on page 32 for the required mounting parts and accessories. The positioner is attached to the control valve using a NAMUR bracket (10). 1. 2.
Attachment to the control valve – Mounting parts and accessories 15 11 10 Attachment to NAMUR rib 9 9.1 1 1.1 1.2 2 3 3.1 6 Lever Nut Disk spring Follower pin Follower plate Follower plate Connecting plate (only for G ¼) 6.1 Seal rings 7 8 Pressure gauge bracket Pressure gauge mounting kit 9 Stem connector 9.1 Bracket 10 NAMUR bracket 11 Screw 14 Bolt 14.1 Screw 15 U-bolt 16 Bracket Attachment to rod-type yoke Rods with 20 to 35 mm Ø 3.
Attachment to the control valve – Mounting parts and accessories 7. 4.3 6.2 Screw the long follower pin (2) included in the mounting kit in the pin position of the required lever (1) assigned in the table. 6.3 Place lever (1) on the positioner shaft and screw tight using the disk spring (1.2) and nut (1.1). 6.4 Move the lever once all the way as far as it will go in both directions.
Attachment to the control valve – Mounting parts and accessories 1 1.1 1.2 2 3 6 6.1 7 8 9 9.1 9.2 9.3 10 10.1 11 11.1 12.1 Lever Nut Disk spring Follower pin Follower plate Connecting plate Seal rings Pressure gauge bracket Pressure gauge mounting kit Stem connector Bracket Pin Screws Bracket Screw Hex bar Screws Screws 10.1 11.1 11 9 12.1 9.1 9.2 3 9.3 10 Screw restriction into signal pressure output (38) 6 6.1 1.1 1.2 1 2 Lever S 7 8 Fig.
Attachment to the control valve – Mounting parts and accessories 4.4 Attachment to rotary actuators 6. Refer to Table 4 on page 33 for the required mounting parts and accessories. Both mounting kits contain all the necessary mounting parts. First select correct actuator size. Prepare actuator, and mount required adapter supplied by the actuator manufacturer, if necessary. 1. 2. 3. 4. 5. 26 Mount the housing (10) onto the rotary actuator.
Attachment to the control valve – Mounting parts and accessories 1 1.1 1.2 2 3 4 4.1 4.2 4.3 5 Lever Nut Disk spring Follower pin Adapter Coupling wheel Screw Disk spring Adhesive label Actuator shaft or adapter 5.1 Adapter 6 6.1 7 8 10 10.1 11 Connecting plate (only for G ¼) Seal rings Pressure gauge bracket Pressure gauge mounting kit Adapter housing Screws Spacers Fit screw restriction into signal pressure output for actuators with < 300 cm³ volume 6 6.1 7 8 1 1.1 1.2 2 4.1 4.2 4 4.3 4.1 4.2 4 4.
Attachment to the control valve – Mounting parts and accessories 4.5 Reversing amplifier for double-acting actuators For the use with double-acting actuators, the positioner must be fitted with a reversing amplifier, e.g. the SAMSON Type 3710 Reversing Amplifier (see Mounting and Operating Instructions EB 8392 EN). If a different reversing amplifier (item no. 1079-1118 or 1079-1119) is used, follow the mounting instructions described in section 4.5.1.
Attachment to the control valve – Mounting parts and accessories From the positioner Output 38 A1 Supply 9 Z A2 1.3 1.1 1.2 1.4 1.5 1.6 A2 1 1.1 1.2 1.3 1.4 1.5 1.6 Reversing amplifier Special screws Gasket Special nuts Rubber seal Sealing plug Filter Supply 9 Control signals to the actuator Z Output 38 A1 A1 1.3 1.2 1.1 1 1.6 Fig.
Attachment to the control valve – Mounting parts and accessories 4.6 Required mounting parts and accessories Order no. Table 1 · Direct attachment to Type 3277-5 (Fig. 4) Mounting parts For actuators with 120 cm² effective diaphragm area 1400-7452 Version compatible with paint for actuators 120 cm² or smaller 1402-0940 Switchover plate (old) for Actuator Type 3277-5xxxxxx.00 (old) 1400-6819 Switchover plate new for Actuator Type 3277-5xxxxxx.
Attachment to the control valve – Mounting parts and accessories Table 2 · Direct attachment to Type 3277 (Fig. 5) Mounting parts Order no. Standard version for actuators with 175, 240, 350, 355, 700, 750 cm² Steel 175 cm² Stainl. steel Steel 240 cm² Stainl. steel Steel 350 cm² Stainl. steel Required piping with screw fitting – for "Actuator stem retracts" – with air purging of the top diaphragm chamber Accessories Steel 355 cm² Stainl. steel Steel 700 cm² Stainl. steel Steel 750 cm² Stainl.
Attachment to the control valve – Mounting parts and accessories Table 3 · Attachment to NAMUR ribs or control valves with rod-type yokes (20 to 35 mm rod diameter) according to IEC 60534-6 (Figs. 6 and 7) Order no. Travel in mm Lever For actuators 7.5 S Type 3271-5 Actuator with 60/120 cm² on Type 3510 Valve (Fig.
Attachment to the control valve – Mounting parts and accessories Order no. Table 4 · Attachment to rotary actuators (Figs. 8 and 9) Attachment acc. to VDI/VDE 3845 (September 2010), see section 12.1 for details Mounting parts Actuator surface corresponds to level 1 Size AA1 to AA4, heavy-duty version Size AA5, heavy-duty version (e.g.
Connections 5 Connections WARNING! Mount the positioner, keeping the following sequence: 1. Mount the positioner on the control valve 2. Connect the supply air 3. Connect the electrical power 4. Perform the start-up settings The connection of the electrical auxiliary power may cause the actuator stem to move, depending on the operating mode. Do not touch the actuator stem or obstruct it to avoid risk of injury to hands or fingers. 5.
Connections 5.1.1 Signal pressure gauges If there are no specifications, calculate as follows: To monitor the supply air (Supply) and signal pressure (Output), we recommend that pressure gauges be attached (see accessories in Tables 1 to 5). Required supply pressure = Upper bench range value + 1 bar 5.1.2 Supply pressure The required supply pressure (of supply air) depends on the bench range and the actuator's operating direction (fail-safe action).
Connections 5.2 Electrical connections DANGER! Risk of electric shock and/or the formation of an explosive atmosphere! 4 For electrical installation, you are required to observe the relevant 4 electrotechnical regulations and the accident prevention regulations that apply in the country of use. The following standard applies for assembly and installation in hazardous areas: EN 60079-14 (VDE 0165 Part 1) Explosive atmospheres - Electrical installations design, selection and erection.
Connections Connection to conform with the type of protection Ex i (EN 60079-11): For connection to a certified, external instrinsically safe circuit, the terminal compartment of the positioner may be opened within the hazardous area. Only the terminal compartment is to be opened within the hazardous area to connect it to a certified instrinsically safe circuit. Positioners that are connected to non-intrinsically safe circuits are no longer permitted to be used as instrinsically safe equipment.
Connections Cable entry mum (reverse polarity protection, see Technical data). NOTICE The demanded degree of protection might not be met because the terminal compartment is not sealed tightly. Only operate the positioner with sealed cable entries and with the lid screwed on properly. Fig. 11 · Location of the terminals (lid unscrewed) The threaded connections for the terminal compartment are designed with ½ NPT or M20x1.5 threads.
Connections Signal Option A B C A 4...20 mA HART® 2-wire transmitter Supply unit for position transmitter + _ 11...35 V DC Control signal polarity insensitive A B C Forced venting L/+ N/_ 0...40 V DC 0...28 V AC A B C + Binary output Signal converter acc. to EN 60947-5-6 _ A B C Binary output PLC DC/AC A B C Binary input Voltage input, polarity insensitive 0...24 V DC A B C Binary input Contact input for external contact Fig.
Connections 5.2.1 Establishing communication Communication between PC and the FSK modem or handheld communicator and positioner is based on the HART® protocol. Type Viator FSK modem RS-232 not ex Order no. 8812-0130 USB not ex Order no. 8812-0132 If the load impedance of the controller or control station is too low, an isolation amplifier functioning as load converter is to be connected between controller and positioner. via point-to-point or standard bus (Multidrop).
Connections Note: Communication errors may occur when the process controller/control station output is not HART-compatible. For adaptation, the Z box (order no. 1170-2374) can be installed between output and communication interface. At the Z box a voltage of 330 mV is released (16.5 Ω at 20 mA). Alternatively, a 250-Ω resistor can be connected in series and a 22-µF capacitor can be connected in parallel to the analog output. Note that in this case, the controller output load will increase.
Operator controls and readings 6 6.1 Operator controls and readings Operating modes: 4 Rotary pushbutton The rotary pushbutton ( ) is located underneath the front protective cover. The positioner is operated on site using the rotary pushbutton: Turn to select codes and values. Press to confirm setting. 6.2 4 4 Serial interface The serial interface connection is located underneath the display lid: Unscrew and remove retaining screw and then unscrew display lid.
Operator controls and readings 4 each error. Classifications include “No message”, “Maintenance required”, “Maintenance demanded”, “Out of specification” and “Maintenance alarm“ (see section 8.3). Configuration enabled This indicates that the codes marked with an asterisk (*) in the code list (section 11) are enabled for configuration (see section 8.1).
Operator controls and readings Manual mode Closed-loop operation Condensed state: Maintenance alarm Code % mm mm Designation Position Parameter % S Limit switch Alarm 1 Bar elements for system deviation or lever position Units Limit switch Alarm 2 Configuration enabled Condensed state: Maintenance required Maintenance demanded NOM OVERLOAD RES RUN SAFE SUB TunE YES ZP ää Increasing/increasing Nominal travel äæ Increasing/decreasing w > 22 mA Reset blinking Emergency mode, Start see Code 62 F
Operator controls and readings 6.4 ® HART communication The positioner must be supplied with at least 3.8 mA current. A DTM file (Device Type Manager) conforming to the Specification 1.2 is available for communication. This allows the device, for example, to be run with the PACTware operator interface. All the positioner's parameters are then accessible over the DTM and the operator interface.
Start-up – Settings ® Assignment of dynamic HART variables Variable Meaning % Direction of action set point % Set point after transit time specification % Valve position % Set point deviation e % Absolute total valve travel – Binary input status – 1 = Active 0 = De-energized Condensed state 0 = No message – 1 = Energized 2 = Not installed – 1 = Maintenance required Reading on display after connecting the electrical auxiliary power: blinks on the display when the positioner has not yet
Start-up – Settings NOTICE Perform the start-up settings in the same sequence as listed (section 7.1 to section 7.5). 7.1 Adapting the display Enable configuration at the positioner before activating the pressure limit function: Note: If no settings are entered within 120 seconds, the enabled configuration function becomes invalid. The reading on the display can be turned by 180° to adapt it to how the positioner is attached.
Start-up – Settings 7.3 Checking the operating range of the positioner A horizontal lever (mid-position) is equal to 0°. To check the mechanical attachment, the valve should be moved through the operating range of the positioner in the manual mode using the manual reference variable w. Select manual operating mode (MAN) : Mode Default: MAN Turn → Code 0 Press , Code 0 blinks. Turn → MAN Press mode.
Start-up – Settings 7.4 Allocating the closed position Taking into account the type of valve and the operating direction of the actuator, allocate the closed position (0 % travel): Turn until the required closed position appears on the display. Press Turn Press to confirm the closed position. → ESC to exit or: 4 AIR TO OPEN (AtO) Start initialization as described in section 7.5.
Start-up – Settings NOTICE If the positioner is mounted onto another actuator or its mounting position is changed, reset the positioner to its default settings before re-initializing it. Refer to section 7.7. During initialization the positioner adapts itself optimally to the friction conditions and the signal pressure requirements of the control valve.
Start-up – Settings 7.5.1 Initialization based on MAX maximum range Start initialization: The positioner determines travel/angle of rotation of the closing member from the CLOSED position to the opposite side and adopts this travel/angle of rotation as the operating range from 0 to 100 %. Initialization Fail-safe position setting Enable configuration: Note: If no settings are entered within 120 seconds, the enabled configuration function becomes invalid.
Start-up – Settings Enter pin position: mm Enable configuration: Pin position Default: No Turn → Code 4 Press , Code 4 blinks. Note: If no settings are entered within 120 seconds, the enabled configuration function becomes invalid. Configuration enabled Default: No Turn → Pin position on lever (see relevant section on attachment). Press . The reading of the nominal range appears in mm/°. Turn → Code 3, display: No Press , Code 3 blinks. 7.5.
Start-up – Settings Press Select initialization mode: Initialization mode Default: MAX Turn → Code 6 Press , Code 6 blinks. Turn → NOM Press mode. to confirm the NOM initialization Start initialization: Initialization Fail-safe position setting Keep pressed down for 6 seconds. Initialization starts after the progress indication has stopped. Note: After initialization, check the direction of action and, if necessary, change it (Code 7). 7.5.
Start-up – Settings Turn until the OPEN position of the valve is reached. Press Select initialization mode: to confirm the OPEN position. Initialization mode Default: MAX Enable configuration: Note: If no settings are entered within 120 seconds, the enabled configuration function becomes invalid. Turn Press , Code 6 blinks. Turn → MAN Press mode. Configuration enabled Default: No Turn → Code 3, display: No Press , Code 3 blinks.
Start-up – Settings 7.5.4 SUB substitute calibration A complete initialization procedure takes several minutes and requires the valve to move through its entire travel range several times. This initialization mode, however, is an emergency mode, in which the control parameters are estimated and not determined by an initialization procedure. As a result, a high level of accuracy cannot be expected. You should always select a different initialization mode if the plant allows it.
Start-up – Settings Select initialization mode: Initialization mode Default: MAX → Code 6 Turn Press Change pressure limit and control parameters: Note: Do not change the pressure limit (Code 16). Only change the control parameters KP (Code 17) and TV (Code 18) if the settings of the replaced positioner are known. → SUB Turn Press mode.
Start-up – Settings Turn mm Blocking position Default: 0 Press , Code 0 blinks. Turn → Init Press . The setting of the fail-safe position AtO or AtC appears. Turn → Code 34 Press , Code 34 blinks. Turn → Closing direction (CCL counterclockwise/CL clockwise) Press Turn → Code 35 Press , Code 35 blinks. Turn → Blocking position, e.g. 5 mm (read off at travel indicator scale of the blocked valve or measure with a ruler).
Start-up – Settings Press The positioner changes to automatic mode (AUTO). The current valve position is indicated in % on the display. Note: If the positioner shows a tendency to hunt in automatic operating mode, the parameters KP and TV must be slightly corrected. Proceed as follows: – Set TV (Code 18) to 4. – Reduce KP (Code 17) until the positioner shows a stable behavior. Zero point correction Finally, if process operations allow it, the zero point must be calibrated as described in section 7.6. 7.
Start-up – Settings Press display: MAN, Code 0 blinks. Turn → Init Press The setting of the fail-safe position AtO or AtC appears. Keep pressed down for 6 seconds. Zero calibration is started, the positioner moves the control valve to the CLOSED position and recalibrates the internal electrical zero point. 7.7 Reset to default values This function resets all start-up parameters and diagnosis data to their default values (see code list in section 11).
Operation 8 Operation WARNING! The actuator stem moves while the positioner is being operated. Do not touch the actuator stem or obstruct it to avoid risk of injury to hands or fingers. 8.1 Enabling and selecting parameters All codes with their meanings and default settings are listed in the code list in section 11 on page 65 onwards. The codes which are marked with an asterisk (*) must be enabled with Code 3 before the associated parameters can be configured as described below.
Operation 8.2 Adjust the manual reference variable Operating modes 8.2.1 Automatic (AUTO) and manual (MAN) modes After initialization has been completed successfully, the positioner is in automatic mode (AUTO). Automatic mode % Switching to manual mode (MAN) % Turn → Code 1 Press , Code 1 blinks. Turn until sufficient pressure has been built up in the positioner and the control valve moves to the required position. Note: If no settings are entered within approx.
Operation 8.2.2 Fail-safe position (SAFE) If you want to move the valve to fail-safe position determined during start-up (see section 7.4), proceed as follows: → Code 0 Turn Press , display: current operating mode (AUtO or MAN), Code 0 blinks. → SAFE Turn Press , display: S The valve moves to the fail-safe position. If the positioner is initialized, the current valve position is indicated on the display in %. Exit the fail-safe position Turn → Code 0 Press , Code 0 blinks.
Operation 4 Out of specification Fault alarm output The positioner is operated outside specified operating conditions. Note: If an event is assigned to the “No message” status, this event does not have any effect on the condensed state. The condensed state is represented by the following icons on the positioner display: Positioner display Condensed state Maintenance alarm 4 The “Function check” condensed state can also switch the fault alarm contact in Code 32.
Maintenance 9 Maintenance The positioner does not require any maintenance. There are filters with a 100 µm mesh size in the pneumatic connections for supply and output which can be removed and cleaned, if required. The maintenance instructions of any upstream supply air pressure reducing stations must be observed.
Code list 11 Code list Code Parameter – Display, values Description no. [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. 0 Operating mode AUtO [MAN] MAN Automatic mode Manual mode AUtO · SAFE SAFE Fail-safe position ESC ESC Escape In MAN and AUtO mode, the system deviation is represented by bar elements on the display.
Code list Code Parameter – Display, values Description no. [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. 4* [No] The follower pin must be inserted into the correct pin position according to the valve travel/angle of rotation. 17, 25, 35, 50, 70, 100, 200 mm The pin position must be entered for initialization using NOM or SUB.
Code list Code Parameter – Display, values Description no. [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. 7* Direction of action w/x [ää] äæ ESC Direction of action of the reference variable w in relation to the travel/angle of rotation x (increasing/increasing or increasing/decreasing).
Code list Code Parameter – Display, values Description no. [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. 11* Travel/angle upper limit (upper x-limit) Limitation of the travel/angle of rotation upwards to the entered value. 50.0 to 120.0 [100] % of the operating range When set to No, the valve can be opened past the nominal travel with a reference variable outside of the 0 to 100 % range. No · ESC The characteristic is not adapted.
Code list Code Parameter – Display, values Description no. [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. 14* Setpoint cutoff decrease (final position w <) 0.0 to 49.9 [1.0] % No · ESC If reference variable w reaches the percentage adjusted that causes the valve to close, the actuator is immediately completely vented (with AIR TO OPEN) or filled with air (with AIR TO CLOSE). This action always lead to maximum tight-closing of the valve.
Code list Code Parameter – Display, values Description no. [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. 19* 20* Tolerance band Used for error monitoring 0.1 to 10.0 [5] % of the operating range ESC Determination of the tolerance band in relation to the operating range. Associated lag time [30] s is a reset criterion.
Code list Code Parameter – Display, values Description no. [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. 24* Limit of total valve travel 7 1000 to 99 · 10 [1 000 000] Limit value of total valve travel. If the limit is exceeded, the fault alarm and the wrench icons appear on the display. Exponential reading from 9999 travel cycles onwards ESC 25* Binary output [A1 - / -] ESC 26* Limit value A1 No 0.0 to 100.0 [2.
Code list Code Parameter – Display, values Description no. [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. 28* Testing the software limit switches alarm A1 and A2 as well as the fault alarm contact A3. If the test is activated, the respective limit switches five times.
Code list Code Parameter – Display, values Description no. [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. 32* “Function check” alarm No · [YES] ESC 33* “Maintenance required” alarm No · [YES] ESC 34* The condensed state can be used for a fault alarm output over the optional binary contact and the optional position transmitter (see Code 25).
Code list Code Parameter – Display, values Description no. [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. 40 Minimum transit time OPEN Time [s] needed by the system (positioner, actuator and valve) to move through the nominal travel/angle to open the valve (100 % 0 to 240 s [0 s] position).
Code list Code Parameter – Display, values Description no. [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. When the write protection function is activated, device data can ® only be read, but not overwritten over HART communication.
Code list Initialization errors Error codes – Recommended action Condensed state message active, when prompted, Err appears. When fault alarms exist, they are displayed here. 50 x > range The value supplied by the measuring signal is either too high or too low, the measuring sensor is close to its mechanical limit. • Pin positioned incorrectly. • Bracket slipped in case of NAMUR attachment or positioner is not central. • Follower plate incorrectly attached.
Code list Error codes – Recommended action Condensed state message active, when prompted, Err appears. When fault alarms exist, they are displayed here. 53 Initialization time exceeded The initialization routine lasts too long. (Init time >) • No pressure on the supply line or there is a leak. • Supply air failure during initialization. Status classification [Maintenance required] Recommended action Check attachment and supply pressure. Re-initialize the positioner.
Code list Operational errors Error codes – Recommended action Condensed state message active, when prompted, Err appears. When fault alarms exist, they are displayed here. 57 Control loop Additional alarm at the fault alarm output Control loop error, the control valve does not react within the tolerable times of the controlled variable (tolerance band alarm Code 19). • Actuator mechanically blocked. • Attachment of the positioner subsequently shifted. • Supply pressure not sufficient.
Code list Hardware errors Error codes – Recommended action Condensed state message active, when prompted, Err appears. When fault alarms exist, they are displayed here. 62 x signal Additional alarm at the fault alarm output Determination of the measured data for the actuator has failed. Conductive plastic element is defective. The positioner continues to run in emergency mode, but should be replaced as soon as possible.
Code list Error codes – Recommended action Condensed state message active, when prompted, Err appears. When fault alarms exist, they are displayed here. 65 Hardware Initialization key jammed (firmware version 1.51 and higher) Additional alarm at the fault alarm output A hardware error has occurred, the positioner changes to the fail-safe position (SAFE).
Code list Data errors Error codes – Recommended action Condensed state message active, when prompted, Err appears. When fault alarms exist, they are displayed here. 68 Control parameter Control parameter error Additional alarm at the fault alarm output Status classification [Maintenance required] Recommended action Confirm error, perform reset and re-initialize the positioner. 69 Poti parameter Parameter error of the digital potentiometer.
Code list Error codes – Recommended action Condensed state message active, when prompted, Err appears. When fault alarms exist, they are displayed here. 75 Info parameters Info parameter errors that are not critical for the control. Status classification [Maintenance required] Recommended action Confirm error. Check and, if necessary, reset required parameters. 76 No emergency mode The travel measuring system of the positioner has a self-monitoring function (see Code 62).
Code list Diagnosis errors Error codes – Recommended action Condensed state message active, when prompted, Err appears. When fault alarms exist, they are displayed here. 79 Diagnostic alarms Error messages are generated in the extended EXPERTplus diagnostics (refer to EB 8389 EN on EXPERTplus valve diagnostics) Status classification Maintenance required (cannot be classified) 80 Diagnostic parameters Errors that are not critical for control.
Dimensions in mm 12 Dimensions in mm Pressure gauge bracket or connecting plate (G ¼ only) Attachment acc. to IEC 60534-6 → Lever in mm 70 15 S = 17 M = 50 L = 100 XL = 200 58 46 Electrical connections: 2 x female thread ½ NPT or M20 x 1.5 34 34 14 122 Direct attachment → NPT ½, ¼ 58 236 95 53 Fig.
Dimensions in mm Output Y1 Output Y1 Supply (9) 86 56 80 52 80 130 166 30 86 Ø 101 Output Y2 Output Y2 Type 3710 Reversing Amplifier Output A1 Supply (9) 50 Z 76 A1 86 56 A2 Output A2 30 86 Ø 101 80 130 166 Reversing amplifier Fig. 16b · Attachment to rotary actuators VDI/VDE 3845 (Sept.
Dimensions in mm 12.1 Fixing levels according to VDI/VDE 3845 (September 2010) Mmin Level 2 (bracket surface) 25 M6 C Level 1 (actuator surface) Actuator Dimensions in mm Ød B ØD A Size A B C ∅d Mmin ∅D* AA0 50 25 15 5.5 for M5 66 50 AA1 80 30 20 5.5 for M5 96 50 AA2 80 30 30 5.5 for M5 96 50 AA3 130 30 30 5.5 for M5 146 50 AA4 130 30 50 5.5 for M5 146 50 AA5 200 50 80 6.
Appendix 13 Appendix 13.1 Selecting the valve characteristic The characteristics that can be selected in Code 20 are shown in following in graph form. Note: A characteristic can only be defined (user-defined characteristic) using a workstation/ operating software (e.g. TROVIS-VIEW). Linear (select characteristic: 0) Travel/ angle of rotation [%] 100 50 Reference variable [%] 0 0 50 100 Equal percentage (select characteristic: 1) Travel/ angle of rotation [%] Rev.
SAMSON butterfly valve linear (select characteristic: 3) SAMSON butterfly valve equal percentage (select characteristic: 4) Travel/ angle of rotation [%] Travel/ angle of rotation [%] 100 100 50 50 Reference variable [%] 0 0 50 Reference variable [%] 0 0 100 VETEC rotary plug valve linear (select characteristic: 5) Travel/ angle of rotation [%] 50 100 VETEC rotary plug valve equal percentage (select characteristic: 6) Travel/ angle of rotation [%] 100 100 50 50 Reference variable [%] 0 0
EB 8387-3 EN 89
EB 8387-3 EN
EB 8387-3 EN 91
EB 8387-3 EN
EB 8387-3 EN 93
EB 8387-3 EN
EB 8387-3 EN 95
EB 8387-3 EN
EB 8387-3 EN 97
Index Index A Accessories. . . . . . . . . . . . . . . . . . . 30, 32 Additional equipment binary contact . . . . . . . . . . . . . . . . . . 9 binary input. . . . . . . . . . . . . . . . . . . 10 forced venting . . . . . . . . . . . . . . . . . . 9 position transmitter. . . . . . . . . . . . . . . 9 Article code . . . . . . . . . . . . . . . . . . . . . . 7 Attachment acc. to IEC 60534-6 (NAMUR) . . . . . 22 direct attachment to Type 3277 Actuator . . . . . 20 to Type 3277-5 Actuator . . . .
Index M T Maintenance. . . . . . . . . . . . . . . . . . . . . 64 Malfunction. . . . . . . . . . . . . . . . . . . . . . 62 Manual mode . . . . . . . . . . . . . . . . . . . . 61 Mounting parts . . . . . . . . . . . . 30, 32 - 33 Technical data . . . . . . . . . . . . . . . . 12 - 13 additional equipment . . . . . . . . . . . . 14 Travel tables . . . . . . . . . . . . . . . . . . . . . 16 O Valve characteristic, selecting. . . . . . . . . 87 Operating modes . . . . . . . . . . . . . .
EB 8387-3 EN 2015-02 SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.samson.