Please consider using the following Programmable Low Battery Cut-off / “Battery
Guard” Models manufactured by Samlex America, Inc. www.samlexamerica.com
- BG-40 (40A) – For up to 400W, 12V inverter or 800W, 24V inverter
- BG-60 (60A) - For up to 600W, 12V inverter or 1200W, 24V inverter
- BG-200 (200A) - For up to 2000W, 12V inverter or 4000W, 24V inverter
Depth of Discharge of Battery and Battery Life
The more deeply a battery is discharged on each cycle, the shorter the battery life. Using
more batteries than the minimum required will result in longer life for the battery bank.
A typical cycle life chart is given in the Table 6.5 below:
TABLE 6.5: TYPICAL CYCLE LIFE CHART
Depth of Discharge
% of Ah Capacity
Cycle Life of Group
27 /31
Cycle Life of Group
8D
Cycle Life of Group
GC2
10 1000 1500 3800
50 320 480 1100
80 200 300 675
100 150 225 550
NOTE: It is recommended that the depth of discharge should be limited to 50%.
Series and Parallel Connection of Batteries
Series Connection
Fig 6.2: Series Connection
When two or more batteries are connected in series, their voltages add up but their
Ah capacity remains the same. Fig. 6.2 above shows 4 pieces of 6V, 200 Ah batteries
connected in series to form a battery bank of 24V with a capacity of 200 Ah. The Posi-
tive terminal of Battery 4 becomes the Positive terminal of the 24V bank. The Negative
terminal of Battery 4 is connected to the Positive terminal of Battery 3. The Negative
6V 6V
Battery 4 Battery 3
6V
Battery 2
6V
Battery 1
24V Inverter
or 24V Charger
Cable “A”
Cable “B”
SECTION 6 | General Information on
Lead Acid Batteries