Product manual

20
Warning
When there is something wrong with module arrays, modules can be
connected with PV grid-tied inverter only after eliminating these
problems.
AC Output
SolarRiver series inverters are designed for single phase grid. Voltage range is from 180V
to 260V (200V-270V for Australia), typical frequency is 50Hz. Other technical requests
should comply with the requirement of local public grid.
Table 4 Cable and Micro-breaker Requirement
Model
SolarRiver
1700TL
SolarRiver
2300TL
SolarRiver
3000TL
SolarRiver
3300TL
SolarRiver
4400TL
SolarRiver
5200TL
Cable (Cu) 4mm
2
4mm
2
4mm
2
4mm
2
4mm
2
4mm
2
Micro-Breaker 16A 20A 20A 25A 25A 32A
Micro-breaker should be installed between inverter and grid, and its rated fault current:
30 mAI
fn
300 mAAny load should not be connected with inverter directly.
Figure 10 Incorrect Connections between Load and Inverter
Impedance of SolarRiver inverter AC connecting dot should be less than 2. To ensure
reliable anti-islanding function , PV cable should be used to ensure wire loss 1% than
normal power. Moreover, length between AC side and grid connecting dot should be less
than 50m. Below chart is cable length for SolarRiver 3300TL, section area and wire loss.