SolarRiver Grid-tied Inverter Product Manual Samil Power Co., Ltd.
Copyright Declaration The copyright of this manual belongs to Samil Power Co., Ltd. Any corporation or individual should not plagiarize, partially copy or fully copy it (including software, etc.), and no reproduction or distribution of it in any form or by any means. All rights reserved. Samil Power reserves the right of final interpretation. This information is subject to changes without notice.
Contents 1 NOTES ON THIS MANUAL ................................................................................................................. 5 1.1 SCOPE OF VALIDITY .............................................................................................................................. 5 1.2 TARGET GROUP ..................................................................................................................................... 5 1.3 SYMBOLS USED ..........................................
7 OPERATION METHOD ...................................................................................................................... 24 7.1 CONTROL PANEL ................................................................................................................................. 24 7.2 LCD FUNCTION .................................................................................................................................. 25 7.3 LCD INFORMATION.................................................
1 Notes on This Manual This manual is an integral part of the inverter, Please read the product manual carefully before installation, operation or maintenance. Keep this product manual for future reference. 1.1 Scope of Validity This installation guide describes the assembly, installation, commissioning, maintenance and failure search of the following Samil Power SolarRiver Series inverters.
2 Safety 2.1 Appropriate Usage The SolarRiver Series is a PV inverter which converts the DC current of a PV generator into AC current and feeds it into the public grid. Figure 1 PV Grid-tied System 2.2 Important Safety Instructions Danger! Danger to life due to high voltages in the inverter! •All work on the inverter must be carried out by qualified personnel only.
2.3 Explanation of Symbols This section gives an explanation of all the symbols shown on the inverter and on the type label. ●Symbols on the Inverter Symbol Explanation Danger to life due to high voltages in the inverter! There is residual voltage in the inverter. The inverter requires 5 minutes to discharge. • Wait 5 minutes before you open the upper lid or the DC lid. Beware of hot surface. The inverter can become hot during operation. Avoid contact during operation.
Warning! Authorized service personnel must disconnect both AC and DC power from the SolarRiver Series inverter before attempting any maintenance or cleaning or working on any circuits connected to the SolarRiver Series inverter. ● Before using the SolarRiver Series inverter, read all instructions and cautionary markings on the SolarRiver Series inverter, and all appropriate sections of this guide. ● Use only attachments recommended or sold by Samil Power.
3 Introduction 3.1 Basic Features Congratulations on your purchase of a SolarRiver Series inverter from Samil Power. The SolarRiver Series inverter is one of the finest inverter on the market today, incorporating state-of-the-art technology, high reliability, and convenient control features. Advanced MCU control technology. Utilize the latest high-efficiency power component. Optimal MPPT technology. Advanced anti-islanding solutions. Excellent protections. IP65 protection level.
●Terminals of PV inverter Figure 3 Terminals of PV inverter(SolarRiver 1700TL/ SolarRiver 2300TL/SolarRiver 3000TL) Figure 4 Terminals of PV inverters(SolarRiver 3300TL/ SolarRiver 4400TL/SolarRiver 5200TL) Caution! About SF-SW. Risk of electric shock!Only authorized personnel is allowed to set the DIP switch. 3.
Figure 5 SolarRiver 1700TL/SolarRiver 2300TL/SolarRiver 3000TL Figure 6 SolarRiver 3300TL/SolarRiver 4400TL/SolarRiver 5200TL ●Weight Table 1 Weight Model SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver 1700TL 2300TL 3000TL 3300TL 4400TL 5200TL 17.1 17.5 17.9 18.9 19.2 19.4 Weight [kg] 4 Technical Data 4.
Max. input Current [A] 9 11 Number of MPP trackers 180-500 (at rated power) [V] 17.5 1/1 / Strings per MPP tracker MPPT voltage range 13.5 200–500 22 26 1/2 210-500 Shutdown voltage / Start 200-500 200-500 200-500 70 / 100 voltage [V] 4.2 Output (AC) SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver 1700TL 2300TL 3000TL 3300TL 4400TL 5200TL AC nominal power [W] 1500 2000 2600 3000 4000 4600 Max. AC power [W] 1650 2200 2800 3300 4400 5000 Max.
Overvoltage / under- voltage Yes protection DC isolation imped- ance Yes monitoring Ground fault Yes protection Grid monitoring Yes Ground fault current Yes monitoring DC injection Yes monitoring 4.
5 Function Operation Mode 【Stand-by Mode】 The stand-by mode means that the inverter is ready to but still not connect to the grid. Under this mode, it will continue check if PV array has enough power to feedback into grid. When the inverter passes dump load test after startup, it will change from stand-by mode to Checking mode. 【Checking Mode】 If inverter passed dump load test and no error/fault occurs, starts checking to deliver power.
6 Installation 6.1 Packaging Type Equipment Accessories Accessories Files Project No. 1 2 3 4 5 6 7 8 9 Description PV Grid-tied Inverter Backboard Installation Kit AC connector DC connector assembly Packing list Product manual Warranty card Quality certificate QTY Remark 1 unit 1 pc 1 set 1 pc 1/2 1 pc 1 pc 1 pc 1 pc Installation Kit include: M5 flange nut, expansion screw, M5 screw rivet.
SolarRiver 1700TL~3000TL Inverter Backboard SolarRiver 3300TL~5200TL Inverter Backboard Warning! before installation and maintenance, AC and DC side doesn’t carry electricity, but if DC side is just disconnected, capacitance still contains electricity, so please wait for at least 5 minutes to ensure the capacitors completely release the energy and inverter is not electrified. Note! Inverters must be installed by qualified person. 6.
● Little or no air flow and high humidity. ● Exposed to steam, vapor, or water. ● Exposed to direct cool air. ●Near the television antenna or antenna cable. ● Ventilation is not enough to cool the inverter, that is to say, outdoors, the inverter requires. At least 30 cm (see table 2) of clearance among the units is needed, it is recommended that the same clearance between the units and the ground be used.
The depth of the holes should be about 30mm and should be the same. After removing the dust in the holes, measure the net depth of the holes. If the depth is more than 33mm or less than 27mm, the expansion tubes wouldn’t be installed and tightened. Figure 7 Installation of Expansion Pipe Step2: Clean all dust outside/inside the hole and measure pitch-row before installation. It need repositioning and drilling holes if the hole with much error.
SolarRiver series inverters (SolarRiver 3300TL/SolarRiver 4400TL/SolarRiver 5200TL) can be connected in series into 2-strings PV modules. Please select PV modules with excellent function and reliable quality. Open-circuit voltage of module arrays connected in series should be <Max. DC (Table 3) input voltage; operating voltage should be conformed to MPPT voltage range. Table 3 Max.
Warning! When there is something wrong with module arrays, modules can be connected with PV grid-tied inverter only after eliminating these problems. ● AC Output SolarRiver series inverters are designed for single phase grid. Voltage range is from 180V to 260V (200V-270V for Australia), typical frequency is 50Hz. Other technical requests should comply with the requirement of local public grid.
Figure 11 AC Cable Loss for SolarRiver 3300TL This product has a professional IP66 AC waterproof connector. You have to wire AC by yourself. Please see figure 12 and 13 for AC connector disassembling guide.
Below shows the steps of wiring. Step1:Put the threaded sleeve and pressure screw through the AC wire (See figure 14). Figure 14 Step2:Wire the AC wire refer to below instructions. ·Screw the green-yellow wire to the ground terminator in the AC Connector (Figure 15). ·Screw the blue wire to the N(Neutral) terminator in the AC Connector. ·Screw the brown wire to the L(Line) terminator in the AC Connector. Figure 15 AC Connector Step3: Confirm all the wires should be screwed down( Figure 16).
Step5: Screw down the pressure screw (Figure 18). Figure 18 Step6: Connect AC connector to inverter (Figure 19). Figure 19 6.6 Run the inverter ·Start inverter after checking all below steps a. Make sure all the DC breaker and AC breaker are disconnect. b. AC cable is connected to grid correctly. c. All PV panels are connected to inverter correctly,DC connectors which are not used should be sealed by cover. ·Start inverter a. Turn on DC and AC side switches. b.
greater than 100V (lowest start-up voltage) but less than 150V (lowest operating voltage). Checking: Inverter will check output environment automatically when DC output voltage of PV panels exceeds 150V and PV panels have enough energy to start inverter. Normal: Inverter begins to operate normally with green light on. Meanwhile, feedback energy to grid, LCD displays present output power, inverter will stop feedbacks power to grid when PV power is not enough.
7.2 LCD Function The function key is used to set the LCD. It can alternate among different parameters and different languages. Use Function Key to check and set inverter data SolarRiver 4400TL Pac=x.xW Display on LCD at first Inverter will change into standby mode when the dc input >100V. when the PV voltage>150V ,Inveter will change into “Normal State” mode after 30s checking. Waiting Pac=x.xW Checking 30s Pac=x.xW Normal State Pac=x.
Initial State LCD will light on Normal State Pac=xxxx.xW It display the total Energy Etotal=xx.xkwh Pac=xxxx.xW It display the today’s energy. Etoday=.xxxx.xkwh Pac=xxxx.xW It display the PV voltage. Vpv=xx.xV Pac=xxxx.xW It display inverter’s model SolarRiver 4.4kW Pac=xxxx.xW It display the version of the software. Ver. V1.00 Pac=xxxx.xW Language setting. Select Language Pac=xxxx.xW Energy today reset Reset Etoday Pac=xxxx.xW It display PV current. Ipv=xx.xA Pac=xxxx.xW It display the initial state.
(Press Function key to check data, it will go back to initial state after 10s) Lockup function as below: Language setting function as below: Udc=xx.xV Pac=xxxx.xW Normal State Pac=xxxx.xW Press the Function Key for 10 times, it will display the language menu. Press the Function key for 5 seconds, it will be locked. Select language Pac=xxxx.xW Lock Pac=xxxx.x Press and hold the Function Key to change language English Pac=xxxx.xW Udc=xx.xV Pac=xxxx.xW Press the Function key, it will go to next state.
Flash Flash Upgrading software Checking Parameters Real-time Power Pac=xxxxW Real-time output power Etotal=xxxxkwh Total energy feedback to grid Output Voltage Vac=xxx.xV Output voltage Output Frequency Freq.=xx.xHz Output frequency Output Current Iac=xx.
value DC Sensor Fault DC Sensor Fault GFCI Failure GFCI Failure Input DC detector failure Leakage current detecting circuit failure Others Lock Lock Froze the information Reconnect Reconnect Reconnect to grid after relay disconnect Inverter’s Version Ver xx.xx Version information 8 Communication and Monitoring 8.1 Communication Interface This product has an optional communication interface RS485/RS232. Operating information like output voltage, current, frequency, fault information, etc.
Figure 22 RS232 Communication Cable and Interface Table 6 RS232 Pin Definition Pin 1 2 3 4 5 6 7 8 9 Function NC TxD RxD NC Common (GND) NC NC NC NC One inverter can only be communicated with one PC at the same time through RS232 port. Thus this method is generally used for single inverter’s communication, for examples,software updating and serviceman’s testing. ② RS485 Communication (Several inverters) ●Communication RS485 is generally for multi inverters’ communication.
Table 7 RS485 Pin Definition Pin 1 2 3 4 Function TX+ TX- RX+ RX- ●Connections Select high-quality network cable, peel the isolation surface, Select 4 wires (brown, white brown, orange, white orange), then follow the same order with the press pliers push into the 4-wire RJ11 crystal head. Figure 24 4-line RJ11 Table 7 4-line RJ11 4-line RJ11 Wire No. Wire Color 1 Brown 2 White Brown 3 Orange 4 White Orange Connect the system as blow (Figure25), you can easily monitoring the PV power station.
9 Troubleshooting 9.1 Troubleshooting This section contains information and procedures for solving possible problems with the SolarRiver series inverters, and provides you with troubleshooting tips to identify and solve most problems that could occur with the SolarRiver series inverters. This section will help you narrow down the source of any problems you may encounter. Please read the following troubleshooting steps.
Table 8 Troubleshooting list Faults Diagnosis and Solutions -Waiting for one minute, grid will go back to normal working state. Grid Faults -Making sure that grid voltage and frequency complies with standards. -Or, please seek for help from us. -Off to grid. -Please check grid-connection, like wire, interface, etc. No Utility -Checking grid usability. -Or seek for help from us. -Checking the panel’s open-circuit voltage whether the value is PV Over Voltage similar or already >Max.DC voltage.
-Check the fan whether it is blocked . Fan Fault -Check the wire of fan whether it is normal . -Please seek for help from us if it can not go back to normal state . -Disconnect the PV (+), PV (-) with DC input, then reconnect Relay Failure them. -Please seek for help from us if it can not go back to normal state. -Leakage current is too high. -Disconnect DC and AC connector, check the surrounding equipment on the AC side.
fan. ●Cooling fin cleaning To ensure inverter performance and long-period usage, back heat emitter needs to be left with available space, side fan cannot be covered with dust or snow as it will affect airflow. Please use compressing air, soft cloth or brush to clean cooling fin, not water, corrosive chemical substance or intense cleaning agent. 10 Decommissioning 10.1 Dismantling the Inverter ● Disconnect the inverter from DC Input and AC output. ● Remove all connection cables from the inverter.
11 Contact Samil Power If you have any questions about SolarRiver series inverter, please call service support hotline: +86 510 83593131. Please keep following information to better our service for you. a. Inverter’s Model. b. Inverter’s Serial No.. c. Communication Method. d. PV modules’ Model.