Datasheet

Datasheet | Energy meters ALE3 with integrated M-Bus interface www.sbc-support.com |
9
Secondary address
Query: SND_UD
Response: 0xE5
Telegram structure (brief)
68 0B 0B 68 53 FD
52 ID1 ID2 ID3 ID4 MAN1
MAN2 DEV MED CSum 16
Telegram structure (detailed)
Byte Value Description
1 0x68 Start
2 0x0B Field length
3 0x0B Field length
4 0x68 Start
5 0x53 C
6 0xFD Address selection for secondary addressing
7 0x52 CI
8 ID1 ID1
9 ID2 ID2
10 ID3 ID3
11 ID4 ID4
12 MAN1 MAN1
13 MAN2 MAN2
14 DEV DEV
15 MED MED
16 Csum Csum
17 0x16 Stop