| www.sbc-support.com Energy meters ALE3 with integrated M-Bus interface | Datasheet
Wiring diagram
Technical data M-Bus
Bus System M-Bus
Standard EN13757
Bus length According to M-Bus specication
Transmission rates 300, 2400, 9600 Bd. The transmission rate is automatically detected
Response time Write: up to 60 ms
Read: up to 60 ms
Data transfer
When reading out the values, all values are transferred in a telegram
It supports the following telegrams (see p.6 for more detailed information):
Initialisation SND_NKE Response: 0xE5
Reading meter REQ_UD2 Response: RSP_UD
Changing primary address SND_UD Response: 0xE5
Reset T
part
SND_UD Response: 0xE5
The device does not respond to unknown queries
The transmission rate is automatically detected
The device has a voltage monitor. In the case of a power failure, all the registers are saved in the EEPROM.
Changing the M-Bus primary address
In order to change the M-Bus primary address, hold down
In the following menu, increases the address by 10, increases the primary address by 1
When the desired address is set, wait until the main display appears again
Secondary addressing
It is possible to communicate with the energy meter usint the secondary address, according to EN13757
T
he use of Wild Cards is possible
4
| www.sbc-support.com Energy meters ALE3 with integrated M-Bus interface | Datasheet
Terminals E1 and E2
Connection for the control signal of the
ripple control receiver for tari switching