Datasheet

Main features
3-phase energy meter, 3 × 230/400 VAC 50 Hz
Direct measurement up to 65 A
Display of active power, voltage and current for every phase
Display of active power for all phases
Modbus RTU Interface to query the data
Reactive power for every and/or all Phases available
through interface
Up to 247 meters can be connected to the Modbus Interface
7-digits display for 1 or 2 taris
Lead seal possible with cap as accessory
Accuracy class B according to EN50470-3,
accuracy class 1 according to IEC62053-21
3 phase energy meters
with integrated Serial
Modbus interface
Energy meters with an integrated Serial RS-485 Modbus
interface allow direct reading of all relevant data, such as
energy (Total and partial), current and voltage for every
phase and active and reactive power for every phase and
for the three phases.
Order Number
Standard Version: ALE3D5FD10C2A00
MID Version: ALE3D5FD10C3A00
Sealing caps: 4 104 7485 0
Technical Data
Precision class B according to EN50470-3
1 according to IEC62053-21
Operationg voltage 3 × 230 / 400 VAC, 50 Hz
Tolerance -20%/+15%
Reference / maximum
current
Iref = 10 A, Imax = 65 A
Starting / minimum current Ist = 40 mA, Imin = 0.5 A
Power consumption Active 0.4 W per phase
Counting range 00’000,00…99’999,99
100’000,0…999’999,9
Display LCD backlit, digits 6 mm high
Display without mains power Capacitor based LCD
Max. 2 times over 10 days
Pulses per kWh LED 1000 Imp./kWh
Mounting
Mounting On 35 mm rail, according to EN60715TH35
Terminal connections
Main circuit
Conductor cross-section 1.5 – 16 mm
2
.
Screwdriver Pozidrive no. 1
Slot no.2, torque 1.5 – 2 Nm
Terminal connections
Control circuit
Conductor cross-section max. 2.5 mm
2
.
Screwdriver Pozidrive no. 0.
Slot no. 2, torque 0.8 Nm
Insulation
characteristics
4 kV/50 Hz test according to VDE0435 for Energy Meter
part
6 kV 1.2/50 µs surge according to IEC255-4
2 kV/50 Hz test according to VDE0435 for Interface
device protection class II
Ambient temperature –25 °…+55 °C
Storage temperature –30 °…+85 °C
Environment Mechanical M2
Electromagnetic E2
Relative humidity 75 %, without condensation
EMC/
interference immunity
Surge according to IEC61000-4–5
at main circuit 4 kV,
at Modbus interface, 1 kV
Burst according to IEC61000-4-4,
at main circuit, 4 kV,
at Modbus interface 1 kV
ESD according to IEC61000-4-2,
contact 8 kV, air 15 kV
www.sbc-support.com
Data sheet