Datasheet

| 43
www.saia-cc.com
5
12
Company
presentation
Product overviewTime relayMonitoring relayEnergy meterCounterItem number
3456
Contact addresses
78
Technical Data
Accuracy class 1 (1%) as per IEC 62 053-21 or B in accordance with EN 50 470-3 (devices in accordance with MID)
Nominal/maximum current
AAD1 - 20 A AAD1 - 32 A AAE1 - 65 A
I
N
= 5 A, I
max
= 20 A I
N
= 5 A, I
max
= 32 A I
N
= 10 A, I
max
= 65 A
Starting current 20 mA 20 mA 40 mA
Voltage
230 VAC, 50 Hz
Tolerance -20%/+15%
Power consumption Active 0.4 W
Measurement Direct
Counting range 0…99 999.9 kWh 0…999 999.9 kWh 0…999 999.9 kWh
Display 4 mm tall figures, decimal place in red
S0 output Optocoupler max. 30 V/20 mA and 5 V min., impedance 100, impulse range 50 ms
Impulse per kWh 1000 Imp./kWh
Transmission distance Maximum 1000 m (with 30 V/20 mA)
LED Red, 2000 Imp./kWh Red, 200 Imp./kWh Red, 1000 Imp./kWh
Mounting On DIN rail 35 mm
Screwdrivers
Primary circuit: Pozidrive no. 1, Phillips no. 1, slotted head no. 1
SO output: Pozidrive no. 0, Phillips no. 0, slotted head no. 1
Primary circuit connections Max. 6 mm², M4 Max. 6 mm², M4 Max. 16 mm², M4
S0 impulse outputs Max. 2.5 mm², M3 Max. 2.5 mm², M3 Max. 2.5 mm², M3.5
Insulation characteristics
4 kV/50 Hz test in accordance with VDE 0435
6 kV 1.2/50 µs surge voltage in accordance with IEC 255-4
Equipment class II
Ambient temperature
MID product: -10°…+55°C
PTB product and without Approval: -10°…+45°C
EMC/resistance to interference
Surge voltage in accordance with IEC 61 000-4-5 on primary circuit, 4 kV
Surge voltage in accordance with IEC 61 000-4-5 at S0 impulse outputs, 1 kV
Burst voltage in accordance with IEC 61 000-4-4, 4 kV
ESD in accordance with IEC 61 000-4-2, contact 8 kV, air 15 kV
Accessories
Order no.
Lead-sealing cap for AAD1 32 A (2 units are recommended for contact protection) 4 104 7420 0
Lead-sealing cap for AAE1 65 A (2 units are recommended for contact protection)
4 104 7485 0