Installation guide
Section 5 Input Problems
No Input Events Possible Causes
• Run though Check Communicaons above
• Sengs were never downloaded into Control Panel
• Input Properes Screen, Operaon Tab, RTU transmit must be
selected.
• Set to wrong type of input; 2-state, 3-state, 4-State etc..
• Check Led for input, Led needs to follow state, Led On is closed,
Led goes o is Open.
• Look for A/D Fail Alarm, if yes your Analog to digital chip has
been blown, replace MAC-4R
Input Reversed Input reports as Open when Closed and Closed when Open
• Goto Inputs Seng Tab and Select the Invert Box
Input Alarm when Closed Input goes into Alarm when the door closes
• Goto Inputs Seng Tab and Select the Invert Box
Section 6 Output Problems
Output not Working Possible Causes
• Run though Check Communicaons above
• Sengs were never downloaded into Control Panel
• Does LED go on, go to next. If No, go to Run Mode, show Tree,
Allow Point Sengs. You may have to edit user and set this
opon on. In Run mode, Expand RTU Outputs and Force Output
High, LED should go On, If soware shows it’s forced on but the
LED is not on, replace MAC-4R
Led on but Device not Tripped Possible Causes
• Check Fuse with VOM
• Disconnect wiring from relay and check connuity on N/C side
with relay o, you should have connecvity. If not replace MAC-
4R
• Check connuity on N/O side with relay on, you should have
connecvity. . If not replace MAC-4R
28
REV 2.0