Tamper switch management feature is configured by setting the key
app/tamper alarm/level to an appropriate value.
Tamper Alarm Level
app/tamper alarm/level
0 No Alarm.
1 Send Alarm (No Sound Alarm).
2 Send Alarm and Activates Buzzer (Sound Alarm)
0-2
The key app/failure ID/alarm ID defines the value of the alarm ID to send
in Wiegand or Dataclock. This ID permits to distinguish between an user
ID and a error ID.
Tamper Alarm Level
app/failure ID/alarm ID
0- 65535
In Wiegand and Dataclock the alarm ID is sent like other Failure IDs, see
the documentation MA100 Series Remote Messages Specification for a
description of the packet format in UDP and RS-485.
E
E
x
x
a
a
m
m
p
p
l
l
e
e
s
s
Example 1: Send an alarm ID (62221) in Wiegand, and play sound
warning, in case of intrusion detection.
To send an alarm in Wiegand, the key app/send ID wiegand/enabled must
be set to 1.and the key app/tamper alarm/level must be set to 2 (alarm and
buzzer.)
The key app/failure ID/alarm ID must be set to 62221 to link the intrusion
event to this identifier.
Example 2: Send an alarm in UDP quietly in case of intrusion
detection.
To send an alarm in UDP, the key app/send ID UDP/enabled must be set
to 1.
Then the key app/tamper alarm/level must be set to 1 (quiet alarm.)