HUGO User Manual

HUGO-X1 User Manual
www.safeguardpowersolutions.com 855.484.6797 P a g e | 13
11. Technical Specifications:
Model No.
HUGO-X1
Input
Voltage
92-138V
Frequency
50 Hz/60Hz ±10%
Output
P.F. (VA/W) = 0.6
500VA/350W
Voltage 113-117V (at Battery Mode)
Frequency
Utility power mode: Output frequency is the same as input.
Battery mode: 50/60Hz ±0.1
Protection
Utility Power Under
Voltage
Under 92 VAC
Utility Surge
Protection
When the utility power is >138VAC, it will transfer to battery mode
Battery Under Voltage
Protection
The UPS turns off automatically when the battery voltage too low
Overload or Short-
Circuit Protection
Battery mode: 105%<load<150%, it lasts 5s then protect; 150%
load, it lasts 200ms
then protect; when short circuit, it protects immediately.
Utility mode: 105%<load<130%, alarm but no protection; 130%
load<150%, it lasts 5min
then protect; 150%
load, it last 10s then protect.
Transfer Time
less than 15ms
Others
LED display
Refer to this manual
Weight
48.5 lbs.
Dimensions
(W x D x H)
14 x 9 x 12 inches
Operating
Temperature
23 to +104°F
Humidity
< 95% (non-condensing)