3.3 Mounting Bracket
3.3.1 Specifications
Angle Adjustment: Horizontal 180°, Vertical 180°
Weight: 1kg
Color: Metal
Enclosure Material: 316 Stainless Steel
Wall Mounted Size: 6 x 4 (5mm bolt)Φ
Dimensions(Bracket): 276 x 100 x 88mm (10.9” x 3.9” x 3.4”)
3.3.2 Installation
Necessary Tool: Hexagon Wrench Driver, Screw Driver
Components: Metric M6-10 x 2pcs, Metric M5-30 x 4pcs
[Figure 6] Bracket and Product
3.4 Wiring and Conduit Connections
3.4.1 Terminal Connections
[Figure 7] TB1 Terminal address at product cover
The detector has terminal blocks TB1 and TB2 as shown in Figure 12. Each of the
terminals has a label which indicates its proper connection.
Terminal Block
TB2
VCC
GND
FLT_N.C.
FLT_COM
ALM_N.O.
ALM_COM
ALM_N.C.
SELF TEST
EXT_RST
WARN_N.O.
WARN_COM
485+
485-
0-20mA
24VDC +
24VDC -
Fault loop normally closed
Fault loop common
Alarm loop normally open
Alarm loop common
Alarm loop normally closed
Self diagnosis (BIT) input
External reset input
Warning loop normally open
Warning loop common
RS-485 communication A
RS-485 communication B
Current output line
TB1
Terminal
Connection
SafeFlame Installation and Operation Manual