SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) SAFE Flame TM SafeFlame Flame Detector Installation Manual October, 2012 NOTICE: Installers of any SafeFlame products or systems must be trained and hold a current and valid training certificate number. Warranty will be void if installed by unauthorized personnel. SAFE Fire Detection Inc. 5915 Stockbridge Dr. Monroe, NC 28110 Phone: (704) 821-7920 Fax: (704) 821-4327 Website: www.safefiredetection.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) Safe Fire Detection – Home Office Safe Fire Detection, Inc. 5915 Stockbridge Drive. Monroe, North Carolina 28110 USA Phone: 704-821-7920 Fax: 704-821-4327 E-Mail: staff@safefiredetection.com Web Page: http://www.safefiredetection.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) Warranty Information Safe Fire Detection’s new Flame Detector, SafeFlame is a flame detector, not a complete system, and must interface with an approved fire alarm panel that meets all local and national codes to become a system All accessories pertaining to the detector for installation and mounting must be purchased from Safe Fire Detection or the warranty may be void.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) Table of Contents 1. Safe Fire Detection Company Introduction 5 2. SafeFlame IR3 Introduction 2.1 Overview 2.1.1 Model and Types 2.2 Principles of Operation 2.2.1 IR3 Flame Detection 2.2.2 RS-485 Modbus 2.3 Detector Performance Options 2.3.1 Cone of Vision 2.3.2 Detector Sensitivity 2.3.3 LED Indicators 2.3.4 False Alarm Protection and Immunity 2.4 Specifications 2.4.1 Electrical Specifications 2.4.2 Environmental Specifications 2.4.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 1. Safe Introduction Safe Fire Detection, Inc. is committed to providing the be st customer support in the industry. This provides our clients with the satisfaction of knowing that their valuable assets and business operation are our greatest concerns. This trust has been earned through 40 years of proven product reliability, dedica tion, and by providing unparalleled detection helping safeguard facilities around the world.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 2. SafeFlame IR3 Introduction 2.1 Overview SafeFlame is a IR3 type flame detector that utilizes a combination of 3 sensors. One of the sensors monitors the spectral band for CO ² emissions. The other two sensors monitor adjacent spectral bands to reduce radiation interference and reduce false alarms. The spectrum for the radiation emitted by a flame measured by the detector is altered by the distance between the detector and the fire.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 2.2 Principles of Operation 2.2.1 IR3 Flame Detector SafeFlame’s triple IR (IR3) flame detector compares three specific wavelength bands within the IR spectral range of a fire and their ratio to each other. This offers fast response without the fear of typical false alarms. One sensor monitors the 4.4 micrometer range and the other sensors monitor the bands above and below.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 2.3.2 Detector Sensitivity The detector has two alarm levels: Warning (Pre-Alarm) and Alarm. The detection range for the detector is 200 feet (60 meters) for a standard fire. A standard fire is defined as a 1ft² (0.1m²) n-heptane pan fire. The Warning level is an alarm verification system. Having this option enabled will delay the alarm signal by approximately 5 seconds. 2.3.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 2.3.4 False Alarm Protection and Immunity The detector is immune to a variety of potential false alarm sources. Below is a table showing either the immunity to a radiation source or the distance beyond which the detector is immune to the radiation source.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 2.4.3 Mechanical Specifications SafeFlame IR3 Standard (SF200A) Enclosure (Material): Aluminum Weight: Detector- 1.3kg(3.3lbs.), Detector w/ Bracket- 2.5kg (5.5lbs.) Dimensions(Detector): 150 x 103 x 125mm (5.9” x 4.1” x 4.9”) Dimensions (with Bracket): 150 x 171 x 347mm (5.9” x 6.7” x 13.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 3. Installation 3.1 Guidelines for Installation For optimal detector performance and protection of the hazard, please consider the guidelines for installation: Spacing: The number of flame detectors in the protected area is determined by the size of the area, the Cone of Vision, obstructions, and sensitivity. Aiming: The flame detector should be pointed toward the center of the desired area of protection.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 3.3 Mounting Bracket 3.3.1 Specifications Angle Adjustment: Weight: Dimensions(Bracket): Color: Enclosure Material: Wall Mounted Size: Horizontal 180°, Vertical 180° 1kg 276 x 100 x 88mm (10.9” x 3.9” x 3.4”) Metal 316 Stainless Steel 6Φ x 4 (5mm bolt) 3.3.2 Installation Necessary Tool: Components: Hexagon Wrench Driver, Screw Driver Metric M6-10 x 2pcs, Metric M5-30 x 4pcs [Figure 6] Bracket and Product 3.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) Alarm Relay Output: Wiring Diagram Relay Status Terminal TB1 Normal (De-Energized) Alarm (Energized) ALM_N.C. Normally Closed (N.C.) Normally Open (N.O.) ALM_N.O. Normally Open (N.O.) Normally Closed (N.C.) ALM_COM Common Common Rating: 2A@28VDC, 4A@125VAC, 2A@250VAC CONTROLLER [Figure 8] Terminal wiring diagram at fire alarm relay Warning Relay Output: Wiring Diagram Relay Status Terminal WARN_N.O. Normally Open (N.O.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) Fault Relay Output: Wiring Diagram Relay Status Terminal TB1 FLT_N.C. Normal (De-Energized) Normally Closed (N.C.) FLT_COM Fault (Energized) Normally Open (N.O.) Common Common Rating: 2A@28VDC, 4A@125VAC, 2A@250VAC -FLT_N.C. is default.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) RS-485: Wiring Diagram RS-485 Terminals and their Connection Description TB2 Terminal Connection 485+ RS-485 A 485- RS-485 B ㆍ Communication Specification Non-Isolation Communication Full-Duplex, Half-Duplex 4800, 9600, 19200, 38400bps are available (dip-switch selectable) 1:N support (Client) Support Protocol: Manufacturer CONTROLLER [Figure 11] RS-485 Network wiring diagram Remote Reset: Wiring Diagram TB2 Terminal Connect
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) External Self-Diagnosis Test: Wiring Diagram External Self-Diagnosis Connection TB2 Terminal Connection 485- External self diagnosis signal line Operating Signal: Operating Delayed Time: Operating Continuous Time: Same level of Signal with 24V-_IN 5 Seconds Operating delayed time + 10 sec. Result Signal Fault Normal - Fault Relay output (De-Energized) - 2mA (0.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 3.5 Setting up the Detector The detector has 3 programmable dip-switches (SW1, SW2, and SW3) which can set and change various detector functions. Dip-Switch SW1 SW2 Description Controls and sets Sensitivity, Alarm Delay, and Output Relays Sets detector address, and Baud rate SW3 JP1 Controls other output functions Connect remote reset signal 3.5.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 3.5.3 Alarm Delay The SafeFlame is equipped with an Alarm delay option, which provides programmable time delays by changing settings. The alarm signal will be activated if the fire still exists after the programmed delay time. But if the fire disappears within the programmed delay time, the detector will return to its standby state. The alarm delay option affects the output relays and the 0-20mA.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) Fault Relay Output This is a feature to enable the fault relay and energize (N.C.) the relay in the standby state. The setting can be disabled to save power. SW1 Switch Setting Function SW1-8 Off Fault relay Enable (default) Fault relay Disabled ON 0-20mA Current Relay Output This is a feature to enable the 0-20mA current output signal. This can be disabled to save power.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) Setting Communication Baud Rate The detector can change the RS-485 communication baud rate. If communication is not available (SW3-2 is OFF), the baud rate setting is not applicable. After changing the baud rate, the detector must be reset before using the communication. SW2 Switch Setting SW2-7 Off SW2-8 Off ON Off Off ON ON ON Function 9600 bps (default) 4800 bps 19200 bps 38400 bps 4. Operating and Testing the Detector 4.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 4.3 Testing 4.3.1 Built-in-Test The detector will automatically perform a self-diagnostic test every 12 hours. 4.3.2 Test Lamp The TL305 generates specific IR3 radiation which can be detected by the SafeFlame detector series as a fire. It has an individual built-in internal power supply, making it portable with up to a 30 minute charge.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 5. Maintenance and Troubleshooting This section deals with preventive maintenance, describes possible faults, and indicates corrective measures. Ignoring these instructions may cause problems with the detector and may invalidate the warranty. Whenever a unit requires service, please contact Safe Fire Detection or its authorized distributor for assistance. Please record the maintenance process for the detector in the maintenance book.
SafeFlame Installation and Operation Manual (Publication#: MA-SF200OM) 5915 Stockbridge Dr. • Monroe, NC 28110 Tel.