Datasheet
G
Mounting and Installation
Rev. 2017 - V12 GB
Connecting diagram
SW
COM NO NC
∆
V
Red
Yellow, flow
switch-on value
Blue, no
flow existing
(flow falling below
the preset
switch-off value)
Table of switching values SW-1EPL ⁄ SW- 2
Pipe Ø
DN
(in inches)
Factory Setting
OFF ⁄ ON
(m
3
⁄ h)
Max. Setting
OFF ⁄ ON
(m
3
⁄ h)
1''
0.6 ⁄ 1.0 2.0 ⁄ 2.1
1 ¼ ''
0.8 ⁄ 1.3 2.8 ⁄ 3.0
1 ½ ''
1.1 ⁄ 1.7 3.7 ⁄ 4.0
2 ''
2.2 ⁄ 3.1 5.7 ⁄ 6.1
2 ½ ''
2.7 ⁄ 4.0 6.5 ⁄ 7.0
3 ''
4.3 ⁄ 6.2 10.7 ⁄ 11.4
4 ''
11.4 ⁄ 14.7 27.7 ⁄ 29.0
4 '' Z
6.1 ⁄ 8.0 17.3 ⁄ 18.4
5 ''
22.9 ⁄ 28.4 53.3 ⁄ 55.6
5 '' Z
9.3 ⁄ 12.9 25.2 ⁄ 26.8
6 ''
35.9 ⁄ 43.1 81.7 ⁄ 85.1
6 '' Z
12.3 ⁄ 16.8 30.6 ⁄ 32.7
8 ''
72.6 ⁄ 85.1 165.7 ⁄ 172.5
8 '' Z
38.6 ⁄ 46.5 90.8 ⁄ 94.2
Table of switching values SW-3 ⁄ SW- 4
Pipe Ø
DN
(in inches)
Factory Setting
OFF ⁄ ON
(m
3
⁄ h)
Max. Setting
OFF ⁄ ON
(m
3
⁄ h)
½ ''
0.174 ⁄ 0.48 0.846 ⁄ 0.948
¾ ''
0.138 ⁄ 0.408 0.768 ⁄ 0.858
Pipe diameters with paddle combinations
Pipe Ø
DN
(in inches)
Pipe Ø
DN
(mm)
Paddle
combination
PSW-09
½ ''
15 mm
1
¾ ''
20 mm
1
1 ''
25 mm
1
1 ¼ ''
32 mm
1
1 ½ ''
40 mm
1
2 ''
50 mm
1, 2
2 ½ ''
65 mm
1, 2
3 ''
80 mm
1, 2, 3
4 '' Z
100 mm
1, 2, 3
plus
4
(shorten to 92 mm)
5 '' Z
125 mm
1, 2, 3
plus
4
(shorten to 117 mm)
6 '' Z
150 mm
1, 2, 3
plus
4
(shorten to 143 mm)
7 - 8 '' Z
200 mm
1, 2, 3
plus
4
(unshortened)