Datasheet
G
HYGRASREG
®
RHT
Connecting diagram
RHT
The mechanical room hygro-thermostat HYGRASREG
®
RHT, a room hygro-
stat with (bi metal) temperature controller, is used for controlling and
monitoring the relative humidity (humidifying and dehumidifying) and the
temperature in office and residential rooms, baths, winter gardens, labs,
computer rooms, etc. HYGRASREG
®
RHT is applied in dust-free, pollut-
ant-free, non-aggressive air.
TECHNICAL DATA: HYGROSTAT
Power supply: ........................ 24 … 230 V AC
> 24 V in dry rooms only according to
VDE 0110
Setting range: ....................... 35…100 % r. H.
Switching capacity: ................. dehumidifying 5 (0.2) A, min. 100 mA
(Contact load) humidifying 3 (0.2) A, min. 100 mA
Contact: ............................... 1 changeover contact (potential-free)
Sensor element: .................... plastic fibres
Tolerance: ............................. max. 3 % r. H.
Operating difference: ............... ca. 4 % r. H.
Enclosure temperature: ........... 0 °C ...+ 60 °C
FUNCTION:
Humidifying: ........................... wire terminals 5 and 6
Dehumidifying:........................ wire terminals 5 and 7
THERMOSTAT
Switching capacity: ................. 10 (4) A, 24 ⁄ 230V AC
Control range: ........................ +10 °C …+ 35 °C
Contact: ............................... 1 changeover contact (potential-free)
Sensor element: ..................... bimetal, with thermal feedback
FUNCTION:
Heating: ................................ wire terminals 2 and 5
Cooling: ................................ wire terminals 3 and 5
Enclosure: ............................. plastic, material ABS,
colour pure white (similar RAL 9010)
Dimensions: ........................... 127,5 x 75 x 28,6 mm
Installation: ........................... wall mounting or on in-wall flush box, Ø 55 mm
Electrical connection: ............. 0.14 - 2.5 mm
2
,
via terminal screws on circuit board
Protection class: .................... II (according to EN 60 730)
Protection type: ..................... IP 30 (according to EN 60 529)
Standards: ............................ CE conformity,
EMC directive 2004 ⁄ 108 ⁄ EC,
low-voltage directive 73 ⁄ 23 ⁄ EEC
Type ⁄ WG2 Setting Range
Humidity
Temperature
Steps Features Item No.
RHT External setting
RHT-1 35 … 100 % r. H. +10 … + 35 °C one-step main switch 1202-4010-0000-000
Note: When mounting indoor room enclosures on in-wall flush boxes with horizontal fixing holes,
adapter frame
ARA 1,7 E
must be included in the order.
6 7 8