Datasheet

G
HYGRASREG
®
RH - 2
Connecting diagram
RH - 2
Mechanical room hygrostat HYGRASREG
®
RH-2 with switching output (with single-pole
micro switch as two-position controller with humidity sensor) working without external
voltage, with humidity measuring element made of stabilized synthetic gauze, optional
with setpoint setter for switchpoint adjustment (external or internal setting) in an
elegant enclosure made of plastic, with snap-on lid, base with 4-hole attachment for
installation on vertically or horizontally installed in-wall flush boxes, with predetermined
breaking point for on-wall cable entry. HYGRASREG
®
RH-2 is used for controlling and
monitoring the relative humidity in office and residential rooms, baths, labs, control
cabinets, computer rooms, etc., as minimum or maximum hygrostat. It is applied in
dust-free, pollutant-free, non-aggressive air.
TECHNICAL DATA:
Power supply: ........................ 24 … 230 V AC
> 24 V in dry rooms only according to VDE 0110
Setting range: ....................... 25 …95 % r. H.
Switching capacity: ................. dehumidifying, 5 (0.2) A, min. 100 mA
(Contact load) humidifying, 3 (0.2) A, min. 100 mA
Contact: ............................... 1 changeover contact, (potential-free)
Sensor element: .................... plastic fibres
Operating difference: ............... ca. 4 % r. H.
Tolerance: ............................. max. 3 % r. H.
Enclosure temperature: ........... 0 °C ...+40 °C
Enclosure: ............................. plastic, material ABS,
colour pure white (similar RAL 9010)
Dimensions: 98 x 106 x 34 mm (Frija II, with potentiometer)
Electrical connection: ............. 0.14 - 2.5 mm
2
,
via terminal screws on circuit board
Installation: ........................... wall mounting or on in-wall flush box Ø 55 mm,
base with 4-hole for mounting on vertically or
horizontally installed in-wall flush boxes for cable
entry from the back, with predetermined breaking
point for on-wall cable entry from top ⁄ bottom
in case of plain on-wall installation
Protection class: .................... II (according to EN 60 730)
Protection type: ..................... IP 30 (according to EN 60 529)
Standards: ............................ CE conformity,
EMC directive 2004 ⁄ 108 ⁄ EC,
low-voltage directive 73 ⁄ 23 ⁄ EEC
FUNCTION:
Humidifying: ........................... wire terminals 1 and 3
Dehumidifying:........................ wire terminals 1 and 2
Type ⁄ WG2 Setting Range
Humidity
Hysterese Ausgang Steps Item No.
RH - 2 External setting
RH-2 25 … 95 % r. H. ca. 4 % r. H. 1x Changeover contact one-step 1202-4020-0010-000
RH - 2 U Internal setting
RH-2 U 25 … 95 % r. H. ca. 4 % r. H. 1x Changeover contact one-step 1202-4020-0020-000
6 7
# 14 -4026 (wie Katalog-2014, ab Seite 230)ENDFASSUNG | 23. 01. 2014 PR # 24100 - 2014