Datasheet
G
THERMASGARD
®
HTF
The sleeve sensor ⁄ cable temperature sensor THERMASGARD
®
HTF is used for the detection
of temperatures in liquid and gaseous media, e.g. by installing it in an immersion sleeve.
The cable sensor can be implemented as immersion or duct sensor, with silicone, glass fibre,
or PVC leads, for two-wire, three-wire, or four-wire connection, depending on the application.
The sleeve length varies, depending on request, from 30 ... 500 mm (standard is 50 mm respectively
200 mm), the cable length is arbitrary (standard is 1.5 m).
TECHNICAL DATA:
Measuring ranges: ................... - 35 ...+105 °C
PVC
, LiYY, 2 x 0.25 mm²
- 50 ...+180 °C
Silicone
, SiHF, 2 x 0.25 mm²
- 50 ...+250 °C
PTFE
, 2 x 0.25 mm²
- 50 ...+350 °C
glass fibre
, 2 x 0.25 mm²
ends stripped with wire end sleeves
(extended measuring range limits optional,
depending on connection leads,
T
max
NTC = +150 °C
/
LM235Z = +125°C
/
Ni1000 = +180 °C
)
Sensors ⁄ output: ..................... see table, passive
(optional also with 2 sensors)
Connection type: ...................... 2-wire connection
(4-wire connection optional)
Testing current: ....................... ca. 1 mA
Protective tube: ...................... stainless steel, 1.4571, V 4A, Ø = 6 mm
(sensor sleeve)
HTF 50
.... NL = 50 mm
HTF 200
.. NL = 200 mm
(other lengths and diverse materials see table)
Sensor cable: .......................... KL = 1,5 m
(optional also 3 m, 5 m, 8 m, 10 m)
Insulating resistance: ............... ≥ 100 MΩ, at 20 °C (500 V DC)
Process connection: ................. by mounting flange, plastic
(for HTF 200 included in the scope of delivery)
(galvanised steel optional, see accessories)
Protection class: ..................... III (according to EN 60 730)
Protection type: .....................
IP 65
(according to EN 60 529) stamped humidity-tight
IP 68
(optional sensor sleeve watertight compound-filled)
IP 54
(optional glass fibre connecting cable)
1x two-wire connection
Standard
1x two-wire connection
LM 235 Z (KP 10)
1x four-wire connection
(optional)
Type ⁄ WG1 – Sensor ⁄ Output Measuring ranges
PVC
Silicone
PTFE glass fibre
(IP 65)
*
(IP 65)
*
(IP 65)
*
(IP 54)
HTF 50 Pt100
- 35...+105 °C - 50...+180 °C - 50...+250 °C - 50...+350 °C
HTF 50
Pt1000
- 35...+105 °C - 50...+180 °C - 50...+250 °C - 50...+350 °C
HTF 50
Ni1000
- 35...+105 °C - 50...+180 °C – –
HTF 50
Ni1000 TK5000,
LG - Ni1000
- 35...+105 °C - 50...+180 °C – –
HTF 50 NTC 1,8 K, 5K, 10K, 20K, 30K, 10K Precon
- 35...+105 °C -
50
...
+150 °C
– –
HTF 50 KTY 81-210, 81-110, 81-121, 81-122, 11-6
- 35...+105 °C -
40
...
+125 °C
– –
HTF 50
LM235Z
(TCR = 10 mV ⁄ K, 2.73 V at 0 °C), KP10
- 35...+105 °C -
40
...
+125 °C
– –
HTF 200 Pt100
- 35...+105 °C - 50...+180 °C – –
HTF 200
Pt1000
- 35...+105 °C - 50...+180 °C – –
HTF 200
Ni1000
- 35...+105 °C - 50...+180 °C – –
HTF 200
Ni1000 TK5000,
LG - Ni1000
- 35...+105 °C - 50...+180 °C – –
HTF 200 NTC 1,8 K, 5K, 10K, 20K, 30K, 10K Precon
- 35...+105 °C -
50
...
+150 °C
– –
HTF 200 KTY 81-210, 81-110, 81-121, 81-122, 11-6
- 35...+105 °C -
40
...
+125 °C
– –
HTF 200
LM235Z
(TCR = 10 mV ⁄ K, 2.73 V at 0 °C), KP10
- 35...+105 °C -
40
...
+125 °C
– –
Optional:
Cable lengths
(KL) 3 m, 5 m, 8 m, 10 m (standard lengths)
Connection type
4-wire
(4-conductor)
Protection type
* IP 68
(sensor sleeve watertight compound-filled)
Accessories:
MF - 06 - K
Mounting flange, plastic (included in the scope of delivery)
TH
Immersion sleeves
6 7