Datasheet

G
KINASGARD
®
ABWF ⁄ LF
NOTES (W):
This device is used for the detection of persons in up to 10 meters distance. The temperature difference between persons to be detected and
ambience must be greater than 5 K.
When motion is detected, the potential-free relay output switches. The hold time for the output, measured from the time when last motion
was detected, can be pre-set between 4 seconds and ca. 16 minutes. The sensor is characterized by its wide reach while being small in size. The
potential-free changeover contact is used for switching extra-low voltage only.
Type ⁄ WG1 Detection, Measuring Range Output Item No.
ABWF ⁄ LF Room motion sensor and light sensor
ABWF-LF
Presence ⁄ Motion: Yes ⁄ No Changeover contact
1401-1111-2100-000
Light Intensity:
0…500 Lux / 1 / 2 / 5 / 20 / 60 kLux
0 - 10 V
(linearised)
ABWF Room motion sensor
ABWF-W Presence ⁄ Motion: Yes ⁄ No Changeover contact 1401-1110-4000-000
AHKF Room light intensity sensors
AHKF-I Light Intensity:
0…500 Lux / 1 / 2 / 5 / 20 / 60 kLux
4 … 20 mA
(linearised) 1601-1112-1000-000
AHKF-U Light Intensity:
0…500 Lux / 1 / 2 / 5 / 20 / 60 kLux
0 - 10 V
(linearised) 1601-1111-1000-000
The room motion and light sensor KINASGARD
®
ABWF LF is a combined instru-
ment that detects motions and light intensity as well as the presence of persons
and is used to recognize conditions. ABWF ⁄ LF issues a standard signal of 0 - 10 V
for light intensity and has a switching (changeover contact) output for the detection
of motions. The motion sensor ⁄ presence detector detects the presence of persons
and motions. It is used for the observation and recognition of conditions and for
a motion-dependent control of room functions, e.g. as motion detector to lower
temperatures in unused rooms. The motion sensor is applied in corridors, in outdoor
areas, in industrial halls, in offices, residential rooms and business facilities. The
light intensity sensor twilight sensor with six switchable measuring ranges (six
devices in one) measures the luminous intensity and is used to control lumi naries,
lighting systems, Venetian blinds and canvas blinds, etc., to monitor lighting
condi tions at workplaces, in greenhouses, storage halls, workshops, corridors, in
outdoor areas, in industrial halls, in offices as well as in residential and business
facilities, for daylight-dependant constant light control, as light intensity or twilight
sensor and to control sunshade equipment avoiding unnecessary heating-up of rooms.
TECHNICAL DATA:
Power supply: ................. 24V AC ⁄ DC
Power consumption: ......... < 1 W at 24 V DC
< 2 VA at 24 V AC
Sensor:.......................... infrared motion sensor and
light sensor
Output, motion sensor: ..... without ⁄ with motion
potential-free normally open contact 24 V ⁄ 1A
After-running time: .......... adjustable from 4 s to 16 min
Measuring ranges: ...........
multi-range switching
(via DIP switches)
with 6 switchable measuring ranges
0…500 Lux 1 kLux 2 kLux 5 kLux ⁄ 20 kLux ⁄ 60 kLux
(other individual ranges optional,
e. g.
100 kLux)
Output: .......................... 0 -10 V (linearised, active, 3-wire connection)
Ambient temperature: ...... - 10…+ 50 °C
Electrical connection: ....... 0.14 - 1.5 mm², via terminal screws on circuit board
Measuring error: ............. < ± 10 % of final value
Temperature drift: ........... < ± 5 % of final value ⁄ 10 K
Enclosure: ...................... plastic, material polyamide,
30 % glass-globe-reinforced, with quick-locking screws
(slotted ⁄ Phillips head combination),
colour pure traffic white (similar RAL 9016),
enclosure cover for
AHKF
is transparent!
Dimensions: .................... 72 x 64 x 37.8 mm (
ABWF ⁄ LF, ABWF
)
72 x 64 x 43.3 mm (
AHKF
)
Cable gland: .................... M 16 x 1.5 , including strain relief, exchangeable,
max. inner diameter 10.4 mm
Installation: .................... on-wall
Protection class: ............. III (according to EN 60 730)
Protection type: .............. IP 30 (according to EN 60 529)
Standards: ..................... CE conformity, electromagnetic compatibility
according to EN 61 326 + A1 + A2,
EMC directive 2004 ⁄ 108 ⁄ EC
Schematic diagram
ABWF ⁄ LF
Connecting diagram
ABWF ⁄ LF
Measuring ranges
(selectable)
DIP
1
DIP
2
DIP
3
DIP
4
0…500 Lux OFF OFF OFF
0… 1 kLux
O N
OFF OFF
0… 2 kLux OFF
O N
OFF
0… 5 kLux
O N O N
OFF
0… 20 kLux OFF OFF
O N
0… 60 kLux
O N
OFF
O N
1 2 3
13 11 12
4'' 16'
time
min. max.
offset
1234
ON
UB+ 24V AC/DC
Output Light Intensity in lux
UB- GND
Normally
open contact
Breaker
Plug for
presence detector
1
2
3
13
11
12
UB- GND
UB+ supply voltage 24V AC/DC
Output light intensity 0-10V (linearised)
Breaker
Normally
open contact
changeover
(24 V)