Datasheet

19
F
AERASGARD
®
RCO
2
- W RLQ - CO
2
- W RFTM - LQ - CO
2
- W RTM - CO
2
- SD
Rev. 2019 - V29
Schéma de raccordement
RFTM - LQ
- CO
2
- W
Interrupteur DIP (Baldur 2)
RFTM - LQ
- CO
2
- W
Sensibilité COV DIP 1 DIP 2
LOW OFF OFF
MEDIUM (default)
O N
OFF
HIGH OFF
O N
Type d’étalonnage COV DIP 3
désactivé OFF
activé (default)
O N
Teneur en CO
2
DIP 4
0...2000 ppm (default) OFF
0...5000 ppm
O N
Type d’étalonnage CO
2
DIP 6
désactivé OFF
activé (default)
O N
Affectation relais DIP 7 DIP 8
CO
2
(default) : 600...1900 ppm / 900...4700 ppm OFF OFF
COV : 10...95 %
O N
OFF
Température : +5...+48 °C OFF
O N
Humidité : 10...95% h.r.
O N O N
Sortie DIP 9
Tension 0 -10 V (default) OFF
Courant 4...20 mA
O N
Attention :
DIP 5
n'est pas affecté !
4
5
6
1 2 3
SET REL.
OFFSET
ZERO
CO
²
CO
²
VOC VOC
r.H.°C
121113
123 456 789
ON
DIP
ON ON
VOC CO
²
Mode
NC = Normally Closed
COM = Common
NO = Normally Open
Plug for
display
humidity in % r.H.
air quality (VOC)
Outputs
temperature in °C
–UB GND
+UB 24V AC/DC
Output CO
²
in ppm
VOC
sensor
Reset
button
NC
COM
NO
relay
switch
point
Schéma de raccordement
RTM - CO
2
- SD
4
5
6
1 2 3
ZERO
CO
²
free
free
Outputs
temperature in °C
–UB GND
+UB 24V AC/DC
Output CO
²
in ppm
Reset
button