Brochure

www.SplusS.dewww.SplusS.de +49 (0) 911 5 19 47- 70+49 (0) 911 5 19 47- 0 +49 (0) 911 5 19 47- 70+49 (0) 911 5 19 47- 0
PREMASGARD
®
1110
110 Pa 110 Pa 110 Pa
Rev. 2017 - V12 GB
Pressure and differential pressure measuring transducers (± 3 %),
including connection set, compact form, adjustable, calibratable,
with multi-range switching and active output
Conversion table for pressure values:
Unit =
bar mbar Pa kPa mH
2
O
1 Pa
0.00001 bar 0.01 mbar 1 Pa 0.001 kPa 0.000101971 mH
2
O
1 kPa
0.01 bar 10 mbar 1000 Pa 1 kPa 0.101971 mH
2
O
1 bar
1 bar 1000 mbar 100000 Pa 100 kPa 10.1971 mH
2
O
1 mbar
0.001 bar 1 mbar 100 Pa 0.1 kPa 0.0101971 mH
2
O
1 mH
2
O
0.0980665 bar 98.0665 mbar 9806.65 Pa 9.80665 kPa 1 mH
2
O
Schematic diagram
*
Output:
4...20 mA
Schematic diagram
Output:
0 -10 V
DIP switch 6
is not assigned!
DIP switch 6
is not assigned!
1 2 3
123456
ON
Pushbutton
Offset
Plug for display
contact is
on the right side
Zero point setting
(auto zero)
Offset correction
see graph
ca.± 10% of
final value
Plug for
display
Offset
auto
zero
LED
DIP
switches
min. max.
+UB 24V DC
Output pressure Pa 4...20mA
GND
(optional for LCD
backlighting)
1 2 3
123456
ON
Pushbutton
Offset
Plug for display
contact is
on the right side
Zero point setting
(auto zero)
Offset correction
see graph
ca.± 10% of
final value
Plug for
display
Offset
auto
zero
LED
DIP
switches
min. max.
Output pressure 0-10V in Pa
–UB GND
+UB 24V AC/DC
PREMASGARD
®
1110
with ⁄ without display
PREMASGARD
®
1110
with ⁄ without display
Mounting diagram
PREMASGARD
®
1110
(A) (B) (C)
Pressure range
(selectable, max. measuring range is depending to the type of device)
PREMASGARD
®
1110
DIP switch 6
is not assigned!
0...1000 Pa 0...5000 Pa 0...10000 Pa –1000...+1000 Pa –5000...+5000 Pa –10000...+10000 Pa
DIP 1 DIP 2
0...100 Pa 0...1000 Pa 0...4000 Pa –100...+100 Pa –1000...+1000 Pa 4000...+4000 Pa
OFF
OFF
0...300 Pa 0...2000 Pa 0...6000 Pa –300...+300 Pa –2000...+2000 Pa 6000...+6000 Pa
O N
OFF
0...500 Pa 0...3000 Pa 0...8000 Pa –500...+500 Pa –3000...+3000 Pa 8000...+8000 Pa
OFF
O N
0...1000 Pa 0...5000 Pa 0...10000 Pa –1000...+1000 Pa –5000...+5000 Pa –10000...+10000 Pa
O N O N
Measuring range mode
(Mode selectable)
DIP 3
Output characteristic line
(Mode selectable)
DIP 4
Measurement signal filtering
(Time interval selectable)
DIP 5
Unidirectional ( 0 ...+MR ) OFF Linear OFF Long (10 s) OFF
Bidirectional (–MR ...+MR )
O N
Square root extracting
O N
Small (1 s)
O N