Brochure

10
G
PREMASGARD
®
1110
Rev. 2017 - V12 GB
Quality product for HVAC sector, accuracy ± 3 %
PREMASGARD
®
1110
series calibratable compact pressure sensors are equipped with eight switchable measuring ranges and with or without
optional display (eight devices in one) and are used for measuring above-atmospheric, below-atmospheric, or differential pressures in air. The piezo-
resistive measuring element is temperature-compensated and guarantees a high degree of reliability and accuracy. These pressure transmitters
have a pushbutton for manual zero point calibration and an adjustable offset. Applications of these pressure sensors are in clean room, medical and
filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale
catering facilities, for monitoring filters, for level
measurement or for triggering frequency converters.
Media measured with these pressure transducers are air (non-precipitating), or other gaseous
non-aggressive, non-combustible media. A PREMASGARD
®
1110 series pressure sensor has eight selectable measuring ranges and therefore,
minimizes the diversity of types and inventory levels while covering a greater range of applications. The differential pressure sensor is supplied
including connection set ASD-06 (2 m connection hose, two pressure connection nipples, screws).
TECHNICAL DATA
Power supply: 24 V AC 20 %); 15...36 V DC for U variant
15...36 V DC for I variant,
depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance: R
a
(ohm) = (U
b
-14 V) 0.02 A for I variant
Load resistance: R
L
> 5 kOhm for U variant
Power consumption: < 1 W at 24 V DC; < 2 VA at 24 V AC
Measuring ranges:
multi-range switching with 8 switchable measuring ranges
(see table)
Output signal: 0 -10 V or 4...20 mA
Electrical connection: 2- or 3-wire connection
Media temperature: 0...+50 °C
Pressure connection: 4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm),
metal pressure connection nozzles
Type of pressure: differential pressure
Medium: clean air and other non-aggressive, non-combustible gases
Accuracy:
± 3
%
of final value
(at +20°C)
Zero point offset: ± 10 % of final value
Above- ⁄ below-
atmospheric pressure: max. 5 x measuring range
Long-term stability: ± 1 % per year
Signal filtering:
switchable 1 s ⁄ 10 s
Hysteresis: 0.3 % of final value
Media contacting parts: ms, Ni, Nylon, PU, Si, PVC with plasticisers
Temperature drift values: ± 0.1 % of final value ⁄ °C
Current consumption: < 20 mA
Linearity: < ± 1 % of final value
Enclosure: plastic, material polyamide, 30 % glass-globe-reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016),
enclosure cover for display is transparent!
Enclosure dimensions: 72 x 64 x 37.8 mm (Tyr 1 without display)
72 x 64 x 43.3 mm (Tyr 1 with display)
Cable gland: M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Electrical connection: 0.14 - 1.5 mm², via terminal screws
Humidity: < 95 % r. H., non-precipitating air
Protection class: III (according to EN 60 730)
Protection type: IP 65 (according to EN 60 529)
Standards: CE conformity, electromagnetic compatibility according
to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU
Features: two-line
display with illumination
,
cutout approx. 36 x 15 mm (W x H), to display ACTUAL pressure
ACCESSORIES
ASD - 06
Connection set (nipple straight) – (included in the scope of delivery)
ASD - 07
Connection nipple (at 90° angle)
DAL-02
Pressure outlet for ceiling or in-wall installation (e.g. in clean rooms)
WS-04
Weather and sun protection, 130 x 180 x 135 mm, stainless steel